HomeMy WebLinkAbout1735 - ORDINANCES - 2/20/2008 ORDINANCE NO. 1735
AN ORDINANCE OF THE CITY OF PALM SPRINGS,
CALIFORNIA, ADOPTING AND AMENDING THE 2007
EDITIONS OF THE CALIFORNIA BUILDING CODE WITH
APPENDIX CHAPTER 1, APPENDICES C, I, AND J, AND
THE CALIFORNIA ELECTRICAL CODE AND ADOPTING
THE 2007 EDITIONS OF THE CALIFORNIA MECHANICAL,
PLUMBING, EXISTING BUILDING, AND ENERGY CODES,
AND THE 1997 EDITION OF THE UNIFORM HOUSING
CODE.
City Attorney Summary
This Ordinance adopts the 2007 Editions of the California
Building, Plumbing, Electrical, Mechanical, California Energy
Code and Existing Building Codes, adapted by the State of
California and amends the 2007 Edition of the California
Building Code and Electrical Code. This Ordinance readopts
the 1997 Edition of the Uniform Housing Code.
THE CITY COUNCIL OF THE CITY OF PALM SPRINGS ORDAINS:
SECTION 1. Section 8.04.005 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.005 Citation of Building Code.
This chapter, the California Building Code, Volumes 1 & 2, 2007 edition; the California
Mechanical Code, 2007 edition; the California Plumbing Code, 2007 edition; the
California Electrical Code, 2007 edition; the California Existing Building Code, 2007
edition; the California Energy Code, 2007 edition; the Uniform Housing Code, 1997
edition; and the California Seismic Safety Commission Model Ordinance, may be
collectively referred to and cited as the "Palm Springs Building Code."
SECTION 2. Section 8.04.010 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.010 California Building Code —Adopted.
These certain documents, a copy of each of which are on file in the office of the City
Clerk, being marked and designated as "California Building Code, Volumes 1 & 2, 2007
edition; and Appendix Chapter 1, Appendices C, I and J, including tables and indices
thereto, except as hereinafter modified, are hereby adopted as the Building Code of the
City of Palm Springs by reference, pursuant to the provisions of Section 50022.1 et seq.
of California Government Code."
Ordinance No. 1735
Page 2
SECTION 3. Section 8.04.015 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.015 California Building Code —Additions, Amendments and Deletions.
The California Building Code adopted herein by reference is hereby amended by the
following additions, deletions and amendments:
(1) Section 202 Definitions is amended by adding the following definitions:
FIVE MINUTE FIRE DEPARTMENT RESPONSE TIME: The Five-Minute Fire
Department Response Time is defined as the time the fire station or response
personnel receive notification of a call for emergency Service, allowing one-
minute for "firefighter turnout" and four-minutes for travel on paved streets. The
Palm Springs Fire Department Five-Minute Response Time Map is identified in
Appendix I.
MID RISE BUILDING: Every building of any type of construction or occupancy
having floors used for human occupancy located 60 feet to 75 feet above the
lowest floor level of fire department access at ground level to the top of the
structure shall be enhanced with high-rise provisions as set forth in Section 509.1
of the California Fire Code.
MODEL ROCKET: shall mean any toy or educational device which weighs not
more than 500 grams, including the engine and any payload that is propelled by
model rocket engines.
MODEL ROCKET ENGINE: shall mean a commercially manufactured, non-
reusable rocket propulsion device which is constructed of a nonmetallic casing
and solid propellant, wherein all of the ingredients are self-contained so as not to
require mixing or handling by the user and which have design and construction
characteristics determined by the State Fire Marshal to provide a reasonable
degree of safety to the user-
(2) Amend subsection 902.1 Definitions.
AUTOMATIC SPRINKLER SYSTEM. A sprinkler system, for fire protection
purposes, is an integrated system of underground and overhead piping designed
in accordance with fire protection engineering standards. The system includes a
suitable water supply, such as a gravity tank, fire pump, reservoir or pressure
tank and/or connection by underground piping to a city or water district water
main. The portion of the system above ground is a network of specifically sized
or hydraulically designed piping installed in a structure or area, generally
overhead, and to which automatic sprinklers are connected in a systematic
pattern. The system is usually activated by heat from a fire and discharge water
over the fire area.
Ordinance No. 1735
Page 3
(3) Amend subsection 903.2 Where required.
Approved automatic sprinkler systems in new buildings and structures shall be
provided in locations described in this section. With the exception of one and
two-family dwellings an approved automatic fire sprinkler system shall be
installed in every building where the gross fire area exceeds 3,000 square feet.
An approved automatic fire sprinkler system shall be installed in any building,
regardless of gross fire area, which is built beyond a five-minute fire department
emergency response time as defined in Section 202. For purposes of this code
subsection regarding building size, fire resistive construction shall not be
considered for purposes of reducing the gross fire area of that building.
An approved automatic fire sprinkler system shall be installed in all new detached
one and two-family dwellings where more than 1,500 GPM fire flow is required.
(1,500 GPM fire flow equals 3,600 square feet in Type V wood frame buildings)
Section 903 shall apply to any buildings undergoing construction or alteration
which adds square footage to an existing building resulting in the total floor area
of the building exceeding 3,000 square feet said building shall require an
approved automatic fire sprinkler system.
Exception: One and two-family dwellings adding gross floor area that results in
the total floor area of the building where not more than 1,500 GPM fire flow is
required. (1,500 GPM fire flow equals 3,600 square feet in Type V wood frame
buildings).
An approved automatic fire sprinkler system shall be installed in every Group A
Occupancy per 903.2.1 including those that result from a change of use in an
existing building or portion thereof.
(4) Amend #1 in subsection 903.2.2 Group E.
1. Throughout all Group E fire areas greater than 3,000 square feet in area.
(5) Amend Exception to subsection 903.2.2 Group E.
Exception: An automatic sprinkler system is not required in any fire area or area
below the level of exit discharge where every classroom throughout the building
has at least one exterior exit door at ground level and the fire area does not
exceed 3,000 square feet-
(6) Amend subsection 903.2.3 Group F-1 #1 & #3 to read as follows:
1. Where a Group F-1 fire area exceeds 3,000 square feet;
3. Where the combined area of all Group F-1 fire areas on all floors, including
any mezzanines, exceeds 3,000 square feet.
Ordinance No, 1735
Page 4
(7) Amend subsection 903.2.6 Group M #1 & #3 to read as follows:
1. Where a Group M fire area exceeds 3,000 square feet;
3. Where the combined area of all Group M fire areas on all floors, including any
mezzanines, exceeds 3,000 square feet.
(8) Repeal and replace 9032.7 Exceptions.
Detached one and two-family dwellings and multiple single-family dwellings (town
houses) 3,600 square feet or less that are inside the Palm Springs Fire
Department five minute response zone (See Appendix 1).
(9) Amend subsection 9032.8 Group S-1 #1 & #3 to read as follows:
1. A Group S-1 fire area exceeds 3,000 square feet;
3. The combined area of all Group S-1 fire areas on all floors, including any
mezzanines, exceeds 3,000 square feet.
(10) Amend subsection 903.2.8.1 Repair garages #1 & #2 to read as follows:
1. Buildings two or more stories in height, including basements, with a fire area
containing a repair garage exceeding 3,000 square feet.
2. One-story buildings with a fire area containing a repair garage exceeding
3,000 square feet.
(11) Amend subsection 903.2.9 Group S-2.
An automatic sprinkler system shall be provided throughout all buildings
containing Group S-2 occupancy where one of the following conditions exists:
1. A Group S-2 fire area exceeds 3,000 square feet;
2. A Group S-2 fire area is located more than three stories above grade plane; or
3. The combined area of all Group S-2 fire areas on all floors, including any
mezzanines, exceeds 3,000 square feet.
An automatic sprinkler system shall be provided throughout buildings classified
as enclosed parking garages in accordance with Section 406.4 of the California
Building Code or where located beneath other groups.
(12) Delete "Exception" in subsection 903.2.9 Group S-2.
(13) Amend subsection 903.3.1.3 NFPA 13D sprinkler systems.
Where required, automatic sprinkler systems installed in one-and two-family
dwellings shall be installed throughout in accordance with NFPA 13D, including
Ordinance No. 1735
Page 5
attached garages, attached carports and storage areas. Pilot heads shall be
required in attic areas every 1,000 square feet or portion thereof.
(14) Amend subsection 903.4.3 Floor control valves.
Approved supervised indicating control valves shall be provided at the point of
connection to the riser on each floor in buildings three or more stories in height
unless otherwise approved by the Fire Chief. Valve locations will be determined
and approved by the fire code official.
(15) Add subsection 903.6.2 Increased square footage.
Any building under 3,000 square feet of gross floor area which is undergoing
construction or alteration which adds square footage resulting in the total floor
area of the building exceeding 3,000 square feet, said building shall require an
approved automatic fire sprinkler system.
Exception: One and two-family dwellings adding gross floor area that results in
the total floor area of the building where not more than 1,500 GPM fire flow is
required. (1,500 GPM fire flow equals 3,600 square feet in Type V wood frame
buildings)
(16) Add subsection 907.2.10.5.4 to read as follows:
Upon sale of any residential dwelling and factory-built housing, the seller shall
have installed therein, permanently wired or battery powered approved detectors
of products of combustion other than heat only, commonly known as smoke
detectors. The smoke detectors are required to be State Fire Marshal approved
and listed. The seller must obtain certification from the Palm Springs Fire
Department of the installation and proper operation prior to close of sale of
property.
(17) Amend subsection 907.2.12 High-rise buildings-
High-rise buildings and buildings with a floor used for human occupancy located
more than 55 feet above the lowest level of fire department vehicle access shall
be provided with an automatic fire alarm system and emergency voice/alarm
communication systems in accordance with Section 907.2.12.2.
(18) Amend subsection 907.2.19 Underground buildings.
All underground buildings shall be equipped throughout with a manual fire alarm
system, including an emergency voice/alarm communication system installed in
accordance with section 9072.12.2,
Ordinance No. 1735
Page 6
(19) Add subsection 908.3.1 Alarms.
The gas detection system shall initiate a local alarm and transmit a signal to a
constantly attended control station when a short-term hazard condition is
detected. The alarm shall be both visible and audible and shall provide warning
both inside and outside the area where gas is detected. The audible alarm shall
be distinct from all other alarms.
Exception: Signal transmission to a constantly attended control station is not
required when not more than one cylinder of highly toxic or toxic gas is stored.
(20) The following is added to Section 1207.1-1 Purpose and Scope, is amended to
read as follows: The purpose of this section is to establish uniform minimum
noise insulation performance standards to protect persons within hotels, motels,
dormitories, apartment houses, attached dwellings, and those detached single-
family dwellings located within the airport 'N' zone overlay from the effects of
excessive noise, including, but not limited to, hearing loss or impairment and
interference with speech and sleep.
(21) The following is added to Section 1505, Fire Classification: all wood, shakes or
shingles, as defined in Section 1505, shall be pressure treated fire retardant with
a minimum Class B rating.
(22) Subsection 1509, Rooftop Structures, is amended by the addition of the following
paragraph: All roof top equipment, unless exempted by the Building Official, shall
be provided with an approved six (6) inch high platform equipped with a sheet
metal cover. Design of the platform shall be as per City detail or approved equal.
(23) Appendix Chapter 1, Administration, Subsection 1052, Work exempt from permit
is amended as follows: Under "Building" list, items 2, 3, 4, 5, 6, 8, 9, 10, 11 and
12 are deleted.
(24) The following is added to Appendix J, Grading: For the purpose of administration
and enforcement of this Appendix Chapter, Grading, the Building Official shall
mean the Director of Public Works or his designated representative.
(25) The following is added to Appendix J, Section J104.1: Grading in excess of 2,000
cubic yards shall be performed in accordance with the approved grading plan
prepared by a civil engineer, and shall be designated as "engineered grading."
Grading involving less than 2,000 cubic yards shall be designated as "regular
grading" unless the permittee chooses to have the grading performed as
engineered grading, or the Building Official determines that special conditions or
unusual hazards exist, in which case, grading shall conform to the requirements
for engineered grading.
Ordinance No. 1735
Page 7
Exception: Grading in excess of 2,000 cubic yards which is primarily of a
landscaping and "fine grading" nature, where no flood hazard is present, may be
termed "regular grading" at the discretion of the Building Official.
(26) The following paragraph is added to Appendix J, Section J104.2, Site Plan
Requirements: An effective means of dust control, which shall include provisions
or adequate watering during the grading provisions for adequate watering during
the grading process and provision For continuance of dust control after grading,
until such time that the graded surface presents sufficient protective cover
against wind or water erosion so that special dust control measures are no longer
necessary."
SECTION 4. Section 8.04.020 of the Palm Springs Municipal Code is amended to read
as follows:
"8.04.020 California Mechanical Code —Adopted.
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "California Mechanical Code, 2007 edition", and all
appendices, tables and indices thereto, except as hereinafter modified, is hereby
adopted as the Mechanical Code for the City of Palm Springs, by reference, pursuant to
the provisions of Section 50022.1 et seq. of the California Government Code."
SECTION 5_ Section 8.04.025 of the Palm Springs Municipal Code titled "California
Mechanical Code, Additions and Amendments" is hereby repealed in its entirety.
SECTION 6. Section 8.04.030 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.030 California Plumbing Code —Adopted.
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "California Plumbing Code, 2007 edition", including
Appendix Chapters 1, A, B, D, I and K, including tables and indices thereto, except as
hereinafter modified, is hereby adopted as the Plumbing Code for the City of Palm
Springs by reference, pursuant to the provisions of Section 50022,1 et seq. of the
California Government Code."
SECTION 7. Section 8.04.032 of the Palm Springs Municipal Code titled "California
Plumbing Code, Additions and Amendments" is hereby repealed in its entirety.
SECTION 8. Section 8.04.035 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.035 Uniform Housing Code —Adopted.
Ordinance No. 1735
Page 8
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "Uniform Housing Code, 1997 edition", and all appendices,
tables and indices thereto, is hereby adopted as the Uniform Housing Code of the City
of Palm Springs by reference, pursuant to the provisions of Section 50022.1 et seq. of
the California Government Code."
SECTION 9. Section 8.04.040 of the Palm Springs Municipal Code is hereby amended
to read as follows:
11
8.04.040 California Existing Building Code Appendix A-1 —Adopted.
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "California Existing Building Code Appendix A-1, 2007
edition", is hereby adopted as the Existing Building Code of the City of Palm Springs by
reference, pursuant to the provisions of Section 50022.1 et seq. of the California
Government Code."
SECTION 10. Section 8.04.045 of the Palm Springs Municipal Code titled "Uniform
Solar Energy Code—Adopted." is hereby repealed in its entirety.
SECTION 11. Section 8.04.050 of the Palm Springs Municipal Code titled "Uniform
Swimming Pool, Spa and Hot Tub Code—Adopted." is hereby repealed in its entirety.
SECTION 12. Section 8.04.055 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.055 California Electrical Code—Adopted.
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "California Electrical Code, 2007 Edition", and all
appendices, tables and indices thereto except as amended herein, is hereby adopted as
the Electrical Code of the City of Palm Springs by reference, pursuant to all the
provisions of Section 50022.1 et seq. of the California Government Code; and all of its
provisions (except as hereinafter modified) shall regulate the installation, arrangement,
alternative, repair, use, and generation of electric wiring, connections, fixture,
apparatus, machinery, appliances, and other electric devices on premises within the
City."
SECTION 13. Section 8.04.060 of the Palm Springs Municipal Code is hereby amended
as follows:
"8.04.060 California Electrical Code —Additions and Amendments.
The California Electrical Code adopted herein by reference is hereby amended by the
following additions and amendments:
Ordinance No. 1735
Page 9
1. Add the following to the end of Subsection 90-8(A):
SERVICE LOAD. The main switch and/or distribution panel of a single family dwelling or
condominium occupancy shall have an adequate capacity and space to carry the
calculated load, plus an 8 KW future with four (4) spare spaces at the time of final
inspection- The 8 KW load is not to be reduced by any demand factor-
2. Add the following to the end of Subsection 310-2(B):
ALUMINUM CONDUCTOR LIMITATIONS- No aluminum wiring shall be used-
EXCEPTION: Aluminum wiring in sizes 1/0 and larger may be used for main feed to
sub-panels only and shall be enclosed in a raceway."
SECTION 14. Section 8.04.065 of the Palm Springs Municipal Code is hereby amended
to read as follows:
"8.04.065 California Energy Code —Adopted-
That certain document, a copy of which is on file in the office of the City Clerk, being
marked and designated as "California Energy Code, 2007 edition", is hereby adopted as
the California Energy Code of the City of Palm Springs by reference, pursuant to the
provisions of Section 50022.1 et seq. of the California Government Cade-"
SECTION 15- Section 8-04-067 of the Palm Springs Municipal Code titled "Uniform
Administrative Code—Additions and amendments-" is hereby repealed in its entirety-
SECTION 16. OPERATIVE DATE. The provisions of this Ordinance shall become
operative on March 31, 2008, which is the effective date of the 2007 edition of the
California Building Standards Code, published by the State of California.
SECTION 17. EFFECTIVE DATE. The Mayor shall sign and the City Clerk shall certify
to the passage and adoption of this Ordinance and shall cause the same, or the
summary thereof, to be published and posted pursuant to the provisions of law and this
Ordinance shall take effect thirty (30) days after passage.
SECTION 18. SEVERABILITY. If any section, subsection or clause of this ordinance
shall be deemed to be unconstitutional or otherwise invalid, the validity of the remaining
section, subsection and clauses shall not be affected thereby.
PASSED, APPROVED, AND ADOPTED THIS, 20" DAY OF FEBRUARY, 2008.
STAVE POUGN , MAYOR
ATTEST.
� ES THOMPSON, CITY CLERK
Ordinance No- 1735
Page 10
CERTIFICATION
STATE OF CALIFORNIA )
COUNTY OF RIVERSIDE ) ss-
CITY OF PALM SPRINGS )
I, JAMES THOMPSON, City Clerk of the City of Palm Springs, California, do hereby
certify that Ordinance No. 1735 is a full, true, and correct copy, and was introduced at
an adjourned regular meeting of the Palm Springs City Council on February 13, 2008,
and adopted at a regular meeting of the City Council held on the 20th day of February.
2008, by the following vote:
AYES: Councilmember Hutcheson, Councilmember Mills, Councilmember
Weigel, Mayor Pro Tern Foat, and Mayor Pougnet.
NOES: None-
ABSENT: None. -
ABSTAIN: None
Ymes Thompson, City Clerkf Palm Springs, California