HomeMy WebLinkAbout10/15/2014 - STAFF REPORTS - 1.B. ;oFVALMSA4
iy
a
V N
• cOnuuita`
°q<,FORN�P CITY COUNCIL STAFF REPORT
DATE: October 15, 2014 APPEAL HEARING
SUBJECT: AN APPEAL BY ADVOCATES FOR BETTER COMMUNITY DESIGN
(ABCD) OF THE DECISION BY THE PLANNING COMMISSION TO
APPROVE A MAJOR ARCHITECTURAL APPLICATION FOR THE
CONSTRUCTION OF A TWO-STORY COMMERCIAL BUILDING
PROPOSED ON BLOCK "B" OF THE MUSEUM MARKET PLAZA
SPECIFIC PLAN AT THE SOUTHWEST CORNER OF ANDREAS ROAD
AND PALM CANYON DRIVE, CASE 3.3606 MAJ.
FROM: David H. Ready, City Manager
BY: Department of Planning Services
SUMMARY
At its regular meeting of September 10, 2014, the Planning Commission approved a
revised Major Architectural Application by Palm Springs Promenade, LLC. for a two-
story commercial building on Block "B" of the Downtown Palm Springs Renovation
Project. Advocates for Better Community Design (ABCD) filed an appeal of this
decision, citing improper review procedures and inadequate public notification.
RECOMMENDATION:
1. Open the hearing and receive public testimony.
2. Adopt Resolution No. "A RESOLUTION OF THE CITY COUNCIL OF
THE CITY OF PALM SPRINGS, CALIFORNIA, DENYING THE APPEAL BY
ADVOCATES FOR BETTER COMMUNITY DESIGN AND UPHOLDING THE
DECISION OF PLANNING COMMISSION TO APPROVE A MAJOR
ARCHITECTURAL APPLICATION FOR THE CONSTRUCTION OF A TWO-
STORY COMMERCIAL BUILDING AT THE SOUTHWEST CORNER OF
ANDREAS ROAD AND PALM CANYON DRIVE, CASE NO. 3.3606 MAJ."
nW NM 1
City Council Staff Report
October 15,2014--Page 2
3.3606 MAJ—Appeal of Planning Commission Decision
PRIOR ACTIONS:
On June 25, 2014, the Planning Commission reviewed a Major Architectural Application
for a one-story commercial building at the subject site and voted 6-1 (Hudson opposed)
to approve the application.
On September 8, 2014, the AAC reviewed a revised Major Architectural Application for
a two-story commercial building at the subject site and voted 7-0 to recommend
approval to the Planning Commission.
On September 10, 2014, the Planning Commission reviewed the revised commercial
building and by a vote of 5-0 (2 absent) approved the project.
On September 22, 2014, an appeal of the revised Major Architectural Application (two-
story building) was filed by ABCD. The appeal letter is attached to this staff report.
Additional prior actions related to this site and the overall Downtown Palm Springs
Renovation Project can be found in the attached Planning Commission Staff Report.
BACKGROUND AND SETTING:
The subject site is located within the boundaries of the Museum Market Plaza Specific
Plan, which encompasses lands bounded by Belardo Road and the Hyatt Hotel to the
north, Tahquitz Canyon Way to the south, Museum Drive to the west and North Palm
Canyon Drive to the east, as well as lands directly east between North Palm Canyon
and Indian Canyon Drives. Specifically, the site is located within Block "B" of the
Specific Plan.
STAFF ANALYSIS:
The revised application consists of a two-story building with a complete redesign. Both
floors will be retail and other commercial uses as permitted by the Museum Market
Specific Plan. First floor is proposed at 17,500 square feet and second floor at 14,300
square feet for a total of 31,800 square feet.
General Plan
CBD (Central Business District) Retail and Yes
The CBD serves as the main activity center and cultural core of the commercial
community and, as such, theatres, museums, retail, and other uses at
entertainment venues are encouraged here. Uses such as grocery stores, 0.77 FAR
hardware stores, and convenience or pharmacy stores that provide
services to the Downtown's residential population are also encouraged.
The Central Business District is subdivided into zones or areas that
provide for diversity in development standards and land use intensities.
02
City Council Staff Report
October 15,2014—Page 3
3.3606 MAJ—Appeal of Planning Commission Decision
The Downtown Central Core (roughly bounded by Amado Road, Tahquitz
Canyon Way, Museum Drive, and Indian Canyon Drive) and the Gateway
areas (at roughly the north and south ends of the CBD) may be
developed with a maximum FAR of 3.5. If projects in these areas provide
substantial public spaces or plazas, an FAR of up to 4.0 may be
developed upon approval of a Planned Development District or Specific
Plan.
Additionally, the proposed project is consistent with the vision of Downtown Palm
Springs as described by the General Plan and Downtown Design Guidelines. The
General Plan states,
"it is envisioned that Downtown will become a high-intensity, mixed-use are
characterized by residential, office, commercial, and entertainment uses. To
stimulate vitality, the Downtown will contain activity areas with differing
intensities, which are further defined by the scale and design of building in each
area."
The proposed site plan introduces significant new retail opportunities directly on Palm
Canyon Drive and surrounding streets, which will provide desirable space for national,
regional and local businesses on the City's prime commercial street. The two-story
building is ideally suited to provide retail commercial uses on the ground floor and
commercial office uses on the second floor with pedestrian and vehicular accessibility
around all sides of the building, allowing maximum access. The development is within
walking distance of the approved hotel on Block C, and the future residential units
anticipated on the western portions of the Specific Plan area. Therefore, the proposed
project is consistent with the General Plan.
Specific Plan
The project implements the goals and objectives of the Museum Market Plaza Specific
Plan, including the six identified "guiding principles,"
1. The highest quality development which provides an exciting
and safe living, working and shopping experience for all.
2. The creation of a pedestrian and vehicular connection from the
Palm Springs Art Museum through Palm Canyon and Indian Canyon
Drives to the Resort/Convention Center District.
3. The development of retail commercial development which
successfully mixes national and regional chain stores with local
businesses, focused on the major roadways which bound the site,
including North Palm Canyon, Indian Canyon, Tahquitz Canyon and
Belardo.
03
City Council Staff Report
October 15,2014—Page 4
3.3606 MAJ—Appeal of Planning Commission Decision
4. A balance of commercial and residential development which
assures the success of the area by increasing the number of homes in the
downtown, thereby increasing the customer base of the commercial uses.
5. The development of residential units which related
synergistically to the commercial development around them, and
encourage a pedestrian lifestyle with little use for the automobile.
6. The development of additional resort hotels which provide
luxury accommodations and increase the visitors to the City's downtown.
The Planning Commission found the project to be in conformance with all of the above.
The Commission's findings are contained within the draft resolution attached to this
report.
As it relates to Development Standards, the project is consistent with the Conformity
Review completed by the City Council on October 17, 2012 and the architectural
approval granted for the site on December 19, 2012. Specific details on compliance
can be found in the attached Planning Commission Memorandum, dated September 10,
2014.
APPEAL:
In accordance with the appropriate procedure, ABCD filed a timely appeal of the
Planning Commission's decision to approve a Major Architectural Application for a
proposed building located within Block "B" of the Specific Plan. The appeal references
a letter submitted to the Planning Commission, prior to acting on the project. The
appellant argues inadequate and improper review procedure by the City.
Staff summarized the basic grounds for the appeal and responded to each below.
Point 1: "The agenda lists these items under New Business, meaning
that the items would not be open for public comment."
Response 1: All items on the Planning Commission agenda are available
for public inspection and comment. Any individual wishing to speak on an
agenda item is able to do so during the Public Comment portion of the
meeting. Furthermore, during the review of this specific item on
September 10th, the Planning Commission allowed public comment.
Point 2: "According to the Museum Market Plaza Specific Plan, once the
Planning Department finds the Major Architectural Application is complete,
the Architectural Advisory committee must hold a hearing within 30 days,
followed by a public meeting'by the Planning Commission within 45 days.
'The Commission, upon closing the public hearing,' can request changes
to the application and continue the matter, or approve the project, or deny
04
City Council Staff Report
October 15,2014—Page 5
3.3606 MAJ—Appeal of Planning Commission Decision
the project. Actions of the Planning Commission are final unless appealed
to the City Council. Specific Plan, V-2. Thus, according to the Specific
Plan, the Planning Commission must convene a public hearing to consider
any Major Architectural Application."
Response 2: When reviewing a Major Architectural application within the
Specific Plan area, Section V requires, "a meeting [emphasis added]...by
the Architectural Advisory Committee, and a public meeting [emphasis
added]...before the Planning Commission." In accordance with this
procedure, staff scheduled the project for review by the Architectural
Advisory Committee (AAC) and Planning Commission on September 8th
and 10th, respectively. Both meetings were public meetings where
members of the public were afforded the opportunity to speak on the
application.
The Specific Plan continues, "Such review shall include any evaluation
required under the California Environmental Quality Act (CEQA). The
Commission, upon closing the public hearing, shall (1) request changes to
the application and continue the matter; or (2) approve the project,
including the addition or modification of project conditions; or (3) deny the
project." In the instance where a Major Architectural application is subject
to discretionary action under CEQA, a public hearing would be required
and the Commission would "close the public hearing." However, since the
project had previously been evaluated under CEQA, including the Specific
Plan EIR and subsequent evaluations and addendums, it was determined
that no further environmental review was required for this project.
Therefore, no public hearing was held, nor required, by the Commission.
Notwithstanding the above, the Architectural Advisory Committee and
Planning Commission opened public comments during their review of the
item. Upon closing public comments, the Commission approved the
project, subject to conditions, in accordance with the proper procedures
outlined in the Specific Plan.
Point 3: "Another problem with the City's handling of these items is that
the Staff Report and agenda do not include the applicant's proposed
development plans."
The City posted and distributed the agenda and staff report in compliance
with local and state laws. Distribution of project plans is not required at
the time of positing of an agenda. The development plans were available
for public review and inspection at both the AAC and Planning
Commission meetings.
05
City Council Staff Report
October 15,2014—Page 6
3.3606 MAJ—Appeal of Planning Commission Decision
Based on the foregoing, staff recommends the City Council reject the appeal and
uphold the Planning Commission's decision to approve the Major Architectural
application, subject to conditions. A draft resolution is attached.
FISCAL IMPACT:
No Fiscal Impact.
Flinn Fagg, AICP David H. Ready, P
Director of Planning Services City Manager
Attachments:
1. Vicinity Map
2. Draft Resolution
3. Letter of Appeal
4. Planning Commission Meeting Minutes, September 10, 2014 (excerpt)
5. Planning Commission Staff Report, September 10, 2014
6. Planning Commission Memorandum, September 10, 2014
7. Architectural Advisory Committee Meeting Minutes, September 8, 2014 (excerpt)
8. Exhibits
06
4 GE PP IM yp4y N
Department of Planning Services W�E
Vicinity Map
CA/IiOAN`P,
I CBD I € CBD REO
J 3
Ir AMADO RO
LU
CU
! [ CBD
1 of
! � -
.-
t } ,.,.w ..�
4 ANQREAS RD Z ; RA
CBD _ Q {g{
CBD ice. 4 U t
W
_ CBD I 2
PD
TAHQUITZ DR
Legend c 0 o
Site a
J
590fl Site Radius = R3 X.. CBD U RA
Zoning R J
W
_._._... Parcels m. a CBD
CITY OF PALM SPRINGS
CASE NO: 3.3606 MAJ (Appeal) DESCRIPTION:
An appeal of the Planning Commission decision
APPELLANT: Advocates for Better to approve a Major Architectural Application to
Community construct a two-story building at the northwest
Development (ABCD) corner of new "Main Street' and North Palm
Canyon Drive, Block "B" of the Museum Market
APPLICANT: Palm Springs Plaza Specific Plan, Zone CBD Section 15.
Promenade, LLC
07
RESOLUTION NO.
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF
PALM SPRINGS, CALIFORNIA, DENYING THE APPEAL
BY ADVOCATES FOR BETTER COMMUNITY DESIGN
AND UPHOLDING THE DECISION OF PLANNING
COMMISSION TO APPROVE A MAJOR ARCHITECTURAL
APPLICATION FOR THE CONSTRUCTION OF A TWO-
STORY COMMERCIAL BUILDING AT THE SOUTHWEST
CORNER OF ANDREAS ROAD AND PALM CANYON
DRIVE, CASE NO. 3.3606 MAJ.
WHEREAS, Advocates for Better Community Design (ABCD) ("Appellant") filed
an appeal, pursuant to Chapter 2.05 of the Municipal Code, of the Planning
Commission's September 10, 2014 decision to approve Case 3.3606 MAJ for the
construction of a two-story commercial building totaling roughly 31 ,800-square feet in
size at the southwest corner of Andreas Road and North Palm Canyon Drive, which is
identified as Block "B" in the Museum Market Plaza Specific Plan, Zone CBD; and
WHEREAS, Palm Springs Promenade, LLC, ("Applicant") filed a Major
Architectural application (Case 3.3606 MAJ) with the City, pursuant to the Museum
Market Specific Plan and Section 94.04.00 of the Zoning Code, to allow the
redevelopment of portions of the Desert Fashion Plaza, specifically Block B as it relates
to this resolution of the Museum Market Plaza Specific Plan located at the northwest
corner of N. Palm Canyon Drive and "New Main Street", (APN's: 513-560-025, -010 and
-021), Section 15/R4/T4; and
WHEREAS, on December 2, 2009, the City Council made findings, adopted a
Mitigation Monitoring and Reporting Program, adopted a Statement of Overriding
Considerations, and certified the Museum Market Specific Plan Environmental Impact
Report ("Specific Plan EIR") and adopted Ordinance 1764, thereby approving the
Museum Market Plaza Specific Plan which covers the design guidelines and
development standards for the Specific Plan area; and
WHEREAS, on September 29, 2011, the City and Palm Springs Promenade,
LLC, entered into a Project Financing Agreement applicable to the financing,
development, redevelopment, creation and refurbishment of public and private
improvements in downtown Palm Springs within the Specific Plan area (the
"Agreement") which included, among other things, a Site Plan and Project Description
depicting the proposed improvements; and
WHEREAS, on October 17, 2012, the City Council approved Amendment No. 2
to the Project Financing Agreement between the City and Palm Springs Promenade,
LLC (the "Amendment") which included an Updated Site Plan and "Updates to Project
Description," reflecting modifications to the proposed improvements originally approved
in the Agreement, and that amended and superseded the original Site Plan and Project
Description, respectively, in the Agreement; and
03
City Council Resolution
Page 2
WHEREAS, on October 17, 2012 the City Council also conducted a conformity
review of the project described in the Amendment, as allowed by the Museum Market
Specific Plan, and concluded that the project described in the Amendment conformed
to the policies and objectives of the Specific Plan; and
WHEREAS, in support of its actions on October 17, 2012, the City Council
adopted an Addendum to the Specific Plan EIR pursuant to the California
Environmental Quality Act ("CEQA"), finding that the proposed project described in the
Amendment was within the scope of the Specific Plan EIR, and, based on the Specific
Plan EIR and Addendum, that no further environmental review was required. (Public
Resources Code § 21166; California Code of Regulations, Title 14, §§ 15162, 15164);
and
WHEREAS, on December 19, 2012, the City Council reviewed an architectural
application for the development of Block B with two two-story buildings, determined said
application implemented the project approved by City Council for CEQA purposes on
October 17, 2012; and approved said application by Resolution No. 23268; and
WHEREAS, on September 4, 2014, Palm Springs Promenade, LLC submitted a
revised architectural application (Case 3.3606-MAJ) for the construction of a two-story
retail commercial building on the easterly half of Block B located at the southwest
corner of Andreas Road and North Palm Canyon Drive; and
WHEREAS, the revised architectural application (Case No. 3.3606-MAJ)
implements a portion of the project approved by the City Council for CEQA purposes on
October 17, 2012; and
WHEREAS, on September 8, 2014, the Architectural Advisory Committee (AAC)
reviewed the proposed project and unanimously recommended approval as submitted;
and
WHEREAS, on September 10, 2014, the Planning Commission reviewed revised
Case No. 3.3606-MAJ in accordance with applicable law, accepted public comments on
the item, considered all evidence presented and unanimously approved the proposed
two-story building by Resolution No. 6436; and
WHEREAS, on September 22, 2014, ABCD filed the appeal in accordance with
Chapter 2.05 of the PSMC; and
WHEREAS, the City Council has carefully reviewed and considered all of the
evidence presented in connection with the hearing on the project, including but not
limited to the project description and exhibits, the staff report and memoranda, and
written and oral testimony presented at the meetings.
THE CITY COUNCIL OF THE CITY OF PALM SPRINGS DOES HEREBY
RESOLVE AS FOLLOWS:
09
City Council Resolution
Page 3
SECTION 1 . The City Council's approval of Major Architectural Application
(Case No. 3.3606-MAJ) is within the scope of the Specific Plan EIR, as supplemented
by the Addendum adopted on October 17, 2012, and none of the circumstances
triggering further environmental review have occurred since the adoption of the
Addendum: (i) there are no substantial changes in the project requiring major revisions
of the Specific Plan EIR and Addendum due to the involvement of new significant
environmental effects or a substantial increase in the severity of previously identified
significant effects; (ii) there are no substantial changes with respect to the
circumstances under which the project is being undertaken which will require major
revisions of the Specific Plan EIR and Addendum due to the involvement of new
significant environmental effects or a substantial increase in the severity of previously
identified effects; and (iii) there is no new information of substantial importance, which
was not known and could not have been known with the exercise of reasonable
diligence at the time the Specific Plan EIR and Addendum was certified showing that:
(a) the project will have one or more significant effects not discussed in the Specific
Plan EIR and Addendum; (b) significant effects previously examined will be
substantially more severe than shown in the Specific Plan EIR and Addendum; (c)
mitigation measures or alternatives previously found not feasible would in fact be
feasible, and would substantially reduce one or more significant effects of the project,
but the mitigation measures or alternatives have not been adopted; or (d) mitigation
measures or alternatives considerably different from those analyzed in the Specific Plan
EIR and Addendum would substantially reduce one or more significant effects on the
environment, but the mitigation measures or alternatives have not been adopted. No
further environmental review is required (Public Resources Code § 21166; California
Code of Regulations § 15162.)
SECTION 2. The Palm Springs Zoning Code Section 94.04.00(D) provides
guidelines for the architectural review of development projects, with conformance
evaluated based on the following guidelines:
1. Site layout, orientation, location of structures and relationship to
one another and to open spaces and topography. Definition of pedestrian
and vehicular areas, i.e., sidewalks as distinct from parking lot areas,-
The project proposes a new two-story building with pedestrian
circulation around entire building. Pedestrian pathways will be separated
from vehicular streets with curbs and landscape treatment. Pavers,
landscaping and sidewalk furniture will provide an enhanced experience
on the site. Sidewalks and other walkways are provided to accommodate
the change in topography across the site.
2. Harmonious relationship with existing and proposed adjoining
developments and in the context of the immediate
neighborhood/community, avoiding both excessive variety and
monotonous repetition, but allowing similarity of style, if warranted;
10
City Council Resolution
Page 4
The proposed structure will be lower than both buildings across
streets to the north and south. The varying structure height from 26 to 37
feet is generally consistent with other structures in the downtown vicinity.
The proposed architecture is of a contemporary style consistent with
surrounding development, but introduces design elements, colors and
materials of a higher quality than the existing development in the vicinity.
The selection of design elements differs from those of the adjacent blocks
within the Museum Market Plaza Specific Plan area, yet they contribute to
the overall identity of an up-scale contemporary center.
3. Maximum height, area, setbacks and overall mass, as well as
parts of any structure (buildings, walls, screens, towers or signs) and
effective concealment of all mechanical equipment;
The proposed building's overall height will be thirty-seven (37) feet,
consistent with the standards of the Specific Plan. The building has a
recessed second floor and varying floating roof plans along the street
frontage. Mechanical equipment will be contained within an equipment
well below the roofline.
4. Building design, materials and colors to be sympathetic with
desert surroundings;
The building architecture is contemporary in style, with a color and
material palette that introduces muted desert colors, with limited use of
accent colors via metal, composite wood and glass.
5. Harmony of materials, colors and composition of those
elements of a structure, including overhangs, roofs, and substructures
which are visible simultaneously,-
The building architecture is contemporary in style, with a color and
material palette that introduces muted desert colors, with limited use of
accent colors via metal, composite wood and glass. Covered walkways
for outdoor seating, pedestrian circulation and solar control are integrated
into the building design.
6. Consistency of composition and treatment;
The building design uses forms and treatments across each tenant
elevations in a consistent and well composed manner. The contemporary
elements and planes are used around all sides of the building.
11
City Council Resolution
Page 5
7. Location and type of planting, with regard for desert climate
conditions. Preservation of specimen and landmark trees upon a site, with
proper irrigation to insure maintenance of all plant materials;
Landscape plans have not been submitted at this time. Required
review at a later is incorporated into the attached conditions of approval.
8. Signs and graphics, as understood in architectural design
including materials and colors;
A sign program not been submitted to evaluate against this
guideline and recommendations for further review are incorporated into
the attached conditions of approval.
9. The planning architectural advisory committee may develop
specific written guidelines to supplement the design criteria and carry out
the purposes of this chapter.
The Architectural Advisory Committee provided preliminary
comments regarding retail fagade design, shading and streetscape
design.
SECTION 3. The City Council finds and determines that Case No. 3.3606-MAJ
does hereby conform to the goals and objectives ("guiding principles") of the Specific
Plan as follows:
1. The highest quality development which provides an exciting
and safe living, working and shopping experience for all.
The project is designed to fit within the approved grid of public and
private streets that allows for safe pedestrian and vehicular access to the
shopping, dining, lodging and entertainment facilities planned for the
overall Specific Plan. The proposed project has pedestrian circulation
around the entire building, allowing for safe pedestrian access. The
project provides space for retail, creating shopping areas within the
Specific Plan area. The design of the proposed project is contemporary,
consistent with surrounding development, but introduces design elements
and materials of a higher quality.
2. The creation of a pedestrian and vehicular connection from the
Palm Springs Art Museum through Palm Canyon and Indian Canyon
Drives to the Resort/Convention Center District.
The pedestrian and vehicular connection to the Museum was
created with the approval of the project's tentative map in December,
12
City Council Resolution
Page 6
2012. The proposed project fits within the street pattern established by
that map, and therefore respects the planned connections to the Museum.
3. The development of retail commercial development which
successfully mixes national and regional chain stores with local
businesses, focused on the major roadways which bound the site,
including North Palm Canyon, Indian Canyon, Tahquitz Canyon and
Belardo.
The proposed project introduces significant new retail opportunities
directly on Palm Canyon Drive, which will provide desirable space for
national, regional and local businesses on the City's prime commercial
street. The proposed project also provides commercial exposure
internally within the project, along Andreas Road (new).
4. A balance of commercial and residential development which
assures the success of the area by increasing the number of homes in the
downtown, thereby increasing the customer base of the commercial uses.
No residential development is proposed as part of the Case No.
3.3606-MAJ, but rather, it proposes commercial uses along Palm Canyon
Drive, a necessary part of the overall land use mix within the Specific Plan
area. The balance of commercial and residential uses will be best served
by the commercial uses being located along Palm Canyon Drive as shown
in the current application. The commercial uses within the proposed
project will also serve visitors staying in the approved hotel on Block C.
5. The development of residential units which related
synergistically to the commercial development around them, and
encourage a pedestrian lifestyle with little use for the automobile.
The proposed project is ideally suited to provide commercial
development within walking distance of the approved hotel on Block C,
and the future residential units anticipated on the western portions of the
Specific Plan area. The proposed project is surrounding by sidewalk
access on all sides, allowing for maximum pedestrian access.
6. The development of additional resort hotels which provide
luxury accommodations and increase the visitors to the City's downtown.
A resort hotel has been approved for Block C of the Specific Plan
area. The success of that hotel, and any others to be built in the area,
depend on providing a viable mix of commercial, retail and entertainment
opportunities within the downtown area. The proposed project provides
those commercial/retail opportunities within walking distance of the Block
13
City Council Resolution
Page 7
C hotel, thereby contributing to the positive synergy of the overall Specific
Plan.
SECTION 4. Pursuant to Municipal Code Section 2.05.030, the appellant's
submitted a written notice of appeal. The appellant's assertions and a response are
found below:
Point 1 : "The agenda lists these items under New Business,
meaning that the items would not be open for public comment."
Response 1: All items on the Planning Commission agenda are
available for public inspection and comment. Any individual wishing to
speak on an agenda item is able to do so during the Public Comment
portion of the meeting. Furthermore, during the review of this specific
item on September 10th, the Planning Commission allowed public
comment.
Point 2: "According to the Museum Market Plaza Specific Plan,
once the Planning Department finds the Major Architectural Application is
complete, the Architectural Advisory committee must hold a hearing within
30 days, followed by a public meeting'by the Planning Commission within
45 days. 'The Commission, upon closing the public hearing,' can request
changes to the application and continue the matter, or approve the
project, or deny the project. Actions of the Planning Commission are final
unless appealed to the City Council. Specific Plan, V-2. Thus, according
to the Specific Plan, the Planning Commission must convene a public
hearing to consider any Major Architectural Application."
Response 2: When reviewing a Major Architectural application
within the Specific Plan area, Section V requires, "a meeting [emphasis
added]...by the Architectural Advisory Committee, and a public meeting
[emphasis added]—before the Planning Commission." In accordance with
this procedure, staff scheduled the project for review by the Architectural
Advisory Committee (AAC) and Planning Commission on September 8th
and 10th, respectively. Both meetings were public meetings where
members of the public were afforded the opportunity to speak on the
application.
The Specific Plan continues, "Such review shall include any
evaluation required under the California Environmental Quality Act
(CEQA). The Commission, upon closing the public hearing, shall (1)
request changes to the application and continue the matter; or(2) approve
the project, including the addition or modification of project conditions; or
(3) deny the project." In the instance where a Major Architectural
application is subject to discretionary action under CEQA, a public hearing
14
City Council Resolution
Page 8
would be required and the Commission would "close the public hearing."
However, since the project had previously been evaluated under CEQA,
including the Specific Plan EIR and subsequent evaluations and
addendums, it was determined that no further environmental review was
required for this project. Therefore, no public hearing was held, nor
required, by the Commission.
Notwithstanding the above, the Architectural Advisory Committee
and Planning Commission opened public comments during their review of
the item. Upon closing public comments, the Commission approved the
project, subject to conditions, in accordance with the proper procedures
outlined in the Specific Plan.
Point 3: "Another problem with the City's handling of these items is
that the Staff Report and agenda do not include the applicant's proposed
development plans."
The City posted and distributed the agenda and staff report in
compliance with local and state laws. Distribution of project plans is not
required at the time of positing of an agenda. The development plans
were available for public review and inspection at both the AAC and
Planning Commission meetings.
NOW, THEREFORE, BE IT RESOLVED that, based upon the foregoing, the City
Council hereby denies the appeal and upholds the decision of the Planning
Commission to approve the revised Major Architectural Application, Case No. 3.3606
MAJ, for the redevelopment of a portion of the existing Desert Fashion Plaza with a
two-story retail commercial building on the easterly portion of Block B of the Museum
Market Plaza Specific Plan located at the southwest corner of N. Palm Canyon Drive
and Andreas Road (new extension), subject to those conditions set forth in Exhibit A,
attached hereto and made a part of this resolution.
ADOPTED THIS 15TH DAY OF OCTOBER, 2014.
David H. Ready, City Manager
ATTEST:
James Thompson, City Clerk
CERTIFICATION
15
City Council Resolution
Page 9
STATE OF CALIFORNIA )
COUNTY OF RIVERSIDE ) ss.
CITY OF PALM SPRINGS )
I, JAMES THOMPSON, City Clerk of the City of Palm Springs, hereby certify that
Resolution No. is a full, true and correct copy, and was duly adopted at a regular
meeting of the City Council of the City of Palm Springs on
by the following vote:
AYES:
NOES:
ABSENT:
ABSTAIN:
James Thompson, City Clerk
City of Palm Springs, California
EXHIBIT A
26
City Council Resolution
Page 10
Case 3.3606 MAJ
Downtown Palm Springs / Block B
October 15, 2014
CONDITIONS OF APPROVAL
Before final acceptance of the project, all conditions listed below shall be completed to
the satisfaction of the City Engineer, the Director of Planning Services, the Director of
Building and Safety, the Chief of Police, the Fire Chief or their designee, depending on
which department recommended the condition.
Any agreements, easements or covenants required to be entered into shall be in a form
approved by the City Attorney.
PROJECT CONDITIONS
1. Building B-1 shall be submitted and reviewed under separate application.
2. Review by the AAC and Planning Commission of conceptual landscape plan at time
of 25% design development stage review, with AAC review of detailed plans to
follow.
3. Review by the AAC of exterior elevations for all individual tenancies.
4. Review by the AAC and Planning Commission of landscape, lighting and hardscape
plans, including all street furniture, subject to the following
a. Use a variety of plant materials in landscape palette.
5. Review by the AAC and Planning Commission of street paving plans, and traffic
movement patterns.
6. Submission and review by AAC and Planning Commission of a sign program for
Block B.
7. The applicant shall submit for review by the AAC and Planning Commission a
unified landscape plan for the entire project consistent with the Project Financing
Agreement, including the following elements:
a. Preliminary Landscape Development Plan: The applicant shall indicate,
on a separate site plan or incorporated into the colored site plan, the basic
landscape concepts for the project. This should include tree and shrub
grouping, groundcover areas, flatwork concepts, significant grading
concepts and a written statement of the landscape development concept
for the project.
17
City Council Resolution
Page 11
b. Project Master Streetscape Plan
i. Establishment of a basic design theme for street furniture and
similar hardscape elements
ii. Proposed location of hardscape elements including planters,
fountains, retaining walls, others
iii. Proposed location of street furniture including benches, trash
receptacles, bus stops, bicycle racks
iv. Proposed thematic plantings
v. Proposed street signage and way finding
vi. Transitions to existing improvements
vii. Locations for public art
viii. Plans for temporary and permanent preservation of the Palm
Springs Walk of Fame
ix. Plans for temporary pedestrian routes during construction
c. Master Pedestrian Paseo Plan. The project proposes a pedestrian
promenade from the Hilton Hotel to the new public square at the corner of
Tahquitz and North Palm Canyon. The promenade includes four elements
from north to south:
i. The connection from the Hyatt Hotel through Building "A"
ii. Market street between Building "b" and "B-1"
iii. Pedestrian Plaza from New Main Street and to the new public
square at the corner of Tahquitz and North Palm Canyon
8. As part of the Landscape Plan, the applicant shall prepare a master plan for this
promenade element including the following elements.
i. Establishing a unified "brand" for the four elements of the Paseo to
encourage pedestrians to follow the entire Paseo.
ii. proposed location of hardscape elements including planters, fountains,
retaining walls
iii. Proposed location of street furniture including benches, trash receptacles,
bus stops, bicycle racks
iv. Proposed thematic plantings
v. Proposed Paseo signage and way finding
vi. Locations for public art
vii. Easements required to ensure public access along the Paseo, including
through Building A.
viii. Operational Plan for Market Street, including timing and procedures for
opening and closure of the street to vehicles
ix. Establishing of a minimum clear width for the Paseo between New Main
Street and Tahquitz in this segment.
x. Considerations for bicycle usage on the Paseo segment between New
Main Street and Tahquitz.
A. Establishing guidelines for business encroachment (i.e., outdoor dining)
into Market Street and the pedestrian connection from New Main Street to
Tahquitz. 18
City Council Resolution
Page 12
xii. Master Plan for the Public Square at Tahquitz and North Palm Canyon
9. The landscape plans for the buildings in Block B shall be consistent with the
approved Master Landscape plan.
10. Applicant shall provide shading and cooling plan and return to the Planning
Commission for review.
11. Applicant shall provide energy conservation plan and return to the Planning
Commission for review.
12. Spandrel glass above storefront shall not be backlit.
ADMINISTRATIVE CONDITIONS
ADM 1. Project Description. This approval is for the project described per Case 3.3606
— MAJ, except as modified by the conditions below.
ADM 2. Reference Documents. The site shall be developed and maintained in
accordance with the approved plans, including site plans, architectural elevations,
exterior materials and colors, landscaping, and grading on file in the Planning Division,
except as modified by the conditions below.
ADM 3. Conform to all Codes and Regulations. The project shall conform to the
conditions contained herein, all applicable regulations of the Palm Springs Zoning
Ordinance, Municipal Code, and any other City County, State and Federal Codes,
ordinances, resolutions and laws that may apply.
ADM 4. Minor Deviations. The Director of Planning or designee may approve minor
deviations to the project description and approved plans in accordance with the
provisions of the Palm Springs Zoning Code.
ADM 5. Indemnification. The owner shall defend, indemnify, and hold harmless the City
of Palm Springs, its agents, officers, and employees from any claim, action, or
proceeding against the City of Palm Springs or its agents, officers or employees to
attach,. set aside, void or annul, an approval of the City of Palm Springs, its legislative
body, advisory agencies, or administrative officers concerning Case 3.3606-MAJ. The
City of Palm Springs will promptly notify the applicant of any such claim, action, or
proceeding against the City of Palm Springs and the applicant will either undertake
defense of the matter and pay the City's associated legal costs or will advance funds to
pay for defense of the matter by the City Attorney. If the City of Palm Springs fails to
promptly notify the applicant of any such claim, action or proceeding or fails to
cooperate fully in the defense, the applicant shall not, thereafter, be responsible to
defend, indemnify, or hold harmless the City of Palm Springs. Notwithstanding the
foregoing, the City retains 'the right to settle or abandon the matter without the
applicant's consent but should it do so, the City shall waive the indemnification herein,
19
City Council Resolution
Page 13
except, the City's decision to settle or abandon a matter following an adverse judgment
or failure to appeal, shall not cause a waiver of the indemnification rights herein.
ADM 6. Maintenance and Repair. The property owner(s) and successors and assignees
in interest shall maintain and repair the improvements including and without limitation all
structures, sidewalks, bikeways, parking areas, landscape, irrigation, lighting, signs,
walls, and fences between the curb and property line, including sidewalk or bikeway
easement areas that extend onto private property, in a first class condition, free from
waste and debris, and in accordance with all applicable law, rules, ordinances and
regulations of all federal, state, and local bodies and agencies having jurisdiction at the
property owner's sole expense. This condition shall be included in the recorded
covenant agreement for the properly if required by the City.
ADM 7. Time Limit on Approval. Approval of the Major Architectural Application (MAJ)
shall be valid for a period of two (2) years from the effective date of the approval.
Extensions of time may be granted by the Planning Commission upon demonstration of
good cause.
ADM 8. Right to Appeal. Decisions of an administrative officer or agency of the City of
Palm Springs may be appealed in accordance with Municipal Code Chapter 2.05.00.
Permits will not be issued until the appeal period has concluded.
ADM 9. Public Art Fees. This project shall be subject to Chapters 2.24 and 3.37 of the
Municipal Code regarding public art. The project shall either provide public art or
payment of an in lieu fee. In the case of the in-lieu fee, the fee shall be based upon the
total building permit valuation as calculated pursuant to the valuation table in the
Uniform Building Code, the fee being '/z% for commercial projects or '/4% for residential
projects with first $100,000 of total building permit valuation for individual single-family
units exempt. Should the public art be located on the project site, said location shall be
reviewed and approved by the Director of Planning and Zoning and the Public Arts
Commission, and the property owner shall enter into a recorded agreement to maintain
the art work and protect the public rights of access and viewing.
ADM 10. Comply with City Noise Ordinance. This use shall comply with the provisions
of Section 11.74 Noise Ordinance of the Palm Springs Municipal Code.
ENVIRONMENTAL ASSESSMENT CONDITIONS
ENV 1 Coachella Valley Multiple-Species Habitat Conservation Plan (CVMSHCP) Local
Development Permit Fee (LDMF) required. All projects within the City of Palm Springs
are subject to payment of the CVMSHCP LDMF prior to the issuance of certificate of
occupancy.
PLANNING DEPARTMENT CONDITIONS
20
City Council Resolution
Page 14
PLN 1. Water Efficient Landscaping Conformance. The project is subject to the Water
Efficient Landscape Ordinance (Chapter 8.60.00) of the Palm Springs Municipal Code
and all other water efficient landscape ordinances. The applicant shall submit a
landscape and irrigation plan to the Director of Planning or designee for review and
approval prior to the issuance of a building permit. Landscape plans shall be wet
stamped and approved by the Riverside County Agricultural Commissioner's Office
prior to submittal. Prior to submittal to the City, landscape plans shall also be certified
by the local water agency that they are in conformance with the water agency's and the
State's Water Efficient Landscape Ordinances.
PLN 2. Sign Applications Required. No signs are approved by this action. Separate
approval and permits shall be required for all signs in accordance with Zoning
Ordinance Section 93.20.00.
PLN 3. Flat Roof Requirements. Roof materials on flat roofs must conform to California
Title 24 thermal standards for "Cool Roofs". Such roofs must have a minimum initial
thermal emittance of 0.75 and minimum initial solar reflectance of 0.70. Only matte
(non-specular) roofing is allowed in colors such as beige or tan.
PLN 4. Screen Roof-mounted Equipment. All roof mounted mechanical equipment shall
be screened per the requirements of Section 93.03.00 of the Zoning Ordinance.
PLN 5. Surface Mounted Downspouts Prohibited. No exterior downspouts shall be
permitted on any facade on the proposed building(s) that are visible from adjacent
streets or residential and commercial areas.
PLN 6. Exterior Alarms & Audio Systems. No sirens, outside paging or any type of
signalization will be permitted, except approved alarm systems.
PLN 7. Outside Storage Prohibited. No outside storage of any kind shall be permitted
except as approved as a part of the proposed plan.
POLICE DEPARTMENT CONDITIONS
POL 1 . Developer shall comply with Section II of Chapter 8.04 "Building Security
Codes" of the Palm Springs Municipal Code.
BUILDING DEPARTMENT CONDITIONS
BLD 1. Prior to any construction on-site, all appropriate permits must be secured.
21
City Council Resolution
Page 15
ENGINEERING DEPARTMENT CONDITIONS
The Engineering Division recommends that if this application is approved, such approval is
subject to the following conditions being completed in compliance with City standards and
ordinances.
Before final acceptance of the project, all conditions listed below shall be completed to the
satisfaction of the City Engineer.
STREETS
ENG 1 . Any improvements within the public right-of-way require a City of Palm
Springs Encroachment Permit.
ENG 2. Submit street improvement plans prepared by a registered California civil
engineer to the Engineering Division. The plan(s) shall be approved by the
City Engineer prior to issuance of any building permits.
ENG 3. The public street improvements outlined in these conditions of approval are
intended to convey to the applicant an accurate scope of required
improvements, however, the City Engineer reserves the right to require
reasonable additional improvements as may be determined in the course of
the review and approval of street improvement plans required by these
conditions.
ENG 4. All proposed decorative pavement shall vary from location to location, but
shall be the same type as approved by the City Engineer.
N. PALM CANYON DRIVE: ALL BLOCKS
ENG 5. Dedicate public utility easements for utilities located under the existing
sidewalk in areas for which public right-of-way has been abandoned by
Parcel Map No. 36446 or by separate instrument.
ENG 6. Dedicate a minimum sidewalk easement of 8 feet (or as needed to match
existing sidewalk) for those portions of sidewalk located outside of the public
right-of-way after abandonment of right-of-way on N. Palm Canyon Drive. Any
existing underground utilities under the existing sidewalk shall not be
relocated in conjunction with this project.
ENG 7. Remove sidewalk along the entire project frontage on Palm Canyon Drive
except for the sidewalk composed of city-owned pavers adjacent to the edge
of pavement.
22
City Council Resolution
Page 16
ENG 8. All broken or off grade street improvements shall be repaired or replaced.
PALM CANYON DRIVE: BLOCK A — Phase 1 AND BLOCK B — Phase 1
ENG 9. There shall be no vehicular access between Block A or Block B and Palm
Canyon Drive, Andreas Road, or Belardo Road (Lot "C"). There will be
vehicular access between Block A — Phase 1 or Block B — Phase 1 and New
Main Street (Lot "A") and Market Street (a private alleyway easement).
ENG 10. Remove existing street improvements as necessary to construct the
intersection of Palm Canyon Drive and Andreas Road. Construct a 25 feet
radius curb return at the northwest and southwest corners of the intersection
of Palm Canyon Drive and Andreas Road, in accordance with City of Palm
Springs Standard Drawing No. 200 and 206.
ENG 11. Construct two (2) Type A curb ramps meeting current California State
Accessibility standards at the northwest corner and one (1) Type A curb ramp
at the southwest corner of the intersection of Palm Canyon Drive and
Andreas Road in accordance with City of Palm Springs Standard Drawing No.
212.
PALM CANYON DRIVE: BLOCK B —Phase 1
ENG 12. Remove existing street improvements as necessary to construct the intersection
of Palm Canyon Drive and New Main Street (Lot "A"). Construct a 25 feet radius
curb return at the northwest and southwest corners of the intersection of Palm
Canyon Drive and New Main Street, in accordance with City of Palm Springs
Standard Drawing No. 200 and 206.
ENG 13. Construct a Type A curb ramp meeting current California State Accessibility
standards at the northwest and southwest corners of the intersection of
Palm Canyon Drive and New Main Street (Lot "A"), in accordance with City of
Palm Springs Standard Drawing No. 212.
ANDREAS ROAD (LOT "D"): BLOCK A — Phase 1 AND BLOCK B — Phase 1
ENG 14. Dedicate full street right-of-way width of 41 feet as shown on the approved
version of the site plan for Tentative Parcel Map No. 36446, together with
property line - corner cut-backs at the intersection of Andreas Road (Lot "D")
and Palm Canyon Drive Road, as required by the City Engineer.
ENG 15. Dedicate a minimum sidewalk easement of 8 feet (or as needed to match
proposed sidewalk) for those portions of sidewalk located outside of the
public right-of-way.
23
City Council Resolution
Page 17
ENG 16. Andreas Road shall have one eastbound and one westbound lane, as well as
parallel parking on each side of Andreas Road (except at curb returns).
ENG 17. Construct 6 inch curb along the north side of Andreas Road (Lot "D") as
shown on the approved site plan for Tentative Parcel Map 36446 in
accordance with City of Palm Springs Standard Drawing No. 200 and 206.
ENG 18. Zero curb face ribbon gutter shall be constructed on the south side of
Andreas Road adjacent to Block B — Phase 1 in conjunction with the
Downtown Palm Springs project.
ENG 19. Zero curb face ribbon gutter shall be constructed on the north side of
Andreas Road across from the intersection of Market Street, in conjunction
with the Downtown Palm Springs project. Bollards shall be placed along this
location to protect the public and buildings from accidental vehicular contact
in Block A — Phase 1. All bollards shall be maintained by the developer.
ENG 20. Construct sidewalk ranging in width from 8 feet to 15 feet wide along both
sides of Andreas Road (Lot "D") as shown on approved improvement plans,
in accordance with City of Palm Springs Standard Drawing No. 210 and the
Museum Market Plaza Specific Plan.
ENG 21. Construct pavement with a minimum pavement section of 3 inches asphalt
concrete pavement over 6 inches crushed miscellaneous base with a
minimum subgrade of 24 inches at 95% relative compaction, or equal,
between the edges of proposed gutters on each side of the street along the
entire Andreas Road frontage in accordance with City of Palm Springs
Standard Drawing No. 110 and the Museum Market Plaza Specific Plan. If an
alternative pavement section is proposed, the proposed pavement section
shall be designed by a California registered Geotechnical Engineer using "R"
values from the project site and submitted to the City Engineer for approval.
ENG 22. The intersection of Andreas Road with Palm Canyon Drive and with Market
Street (private alleyway) shall be constructed with enhanced or decorative
paving.
NEW MAIN STREET (LOT "A"): BLOCK B — Phase 1
ENG 23. Dedicate full street right-of-way width of 41 feet as shown on the approved
version of the site plan for Tentative Parcel Map No. 36446, together with a
property line - corner cut-backs at the northwest and southwest corners of the
intersection of New Main Street (Lot "A") and existing Palm Canyon Drive, as
required by the City Engineer).
24
City Council Resolution
Page 18
ENG 24. Dedicate a minimum sidewalk easement of 8 feet (or as needed to match
proposed sidewalk) for those portions of sidewalk located outside of the public
right-of-way.
ENG 25. New Main Street (Lot "A") shall have one eastbound and one westbound lane, as
well as parking on both sides of New Main Street (except at curb returns and
curb pop-outs) to the Market Street northwest curb.
ENG 26. Remove street improvements as necessary to construct a 25 feet radius curb
return at the northwest and southwest corners of the intersection of New Main
Street (Lot "A") in Block B — Phase 1 , with existing Palm Canyon Drive, in
accordance with City of Palm Springs Standard Drawing No. 200 and 206.
ENG 27. Zero curb face curb shall be constructed on the south side of New Main Street
from Palm Canyon Drive to west side of Market Street in conjunction with the
Downtown Palm Springs project.
ENG 28. Construct sidewalk ranging in width from 8 feet to 15 feet wide along both sides
of New Main Street (Lot "A") as shown on approved improvement plans, in
accordance with City of Palm Springs Standard Drawing No. 210 and the
Museum Market Plaza Specific Plan.
ENG 29. Construct a Type A curb ramp meeting current California State Accessibility
standards at the northwest and southwest corners of the intersection of New
Main Street (Lot "A") in Block C- Phase 1, with existing Palm Canyon Drive, in
accordance with City of Palm Springs Standard Drawing No. 212.
ENG 30. Construct a curb ramp meeting current California State Accessibility standards at
the proposed entry into Block B- Phase1 .
ENG 31. Construct pavement with a minimum pavement section of 3 inches asphalt
concrete pavement over 6 inches crushed miscellaneous base with a minimum
subgrade of 24 inches at 95% relative compaction, or equal, between the edges
of proposed gutters on each side of the street along the New Main Street (Lot
"A"), in accordance with City of Palm Springs Standard Drawing No. 110 and the
Museum Market Plaza Specific Plan. If an alternative pavement section is
proposed, the proposed pavement section shall be designed by a California
registered Geotechnical Engineer using "R" values from the project site and
submitted to the City Engineer for approval.
ENG 32. The intersection of New Main Street (Lot "A) with Palm Canyon Drive shall be
constructed with enhanced or decorative paving.
MARKET STREET (PRIVATE ALLEYWAY EASEMENT BETWEEN BLOCK B — Phase
1 AND BLOCK B- Phase 2) 25
City Council Resolution
Page 19
ENG 33. A 30 feet wide private alleyway easement shall be centered on the mutual lot line
of Parcel 1 (Phase 1) and Parcel 2 (Phase 2), between the proposed buildings
located in Block B - Phase 1 and Block B —Phase 2.
ENG 34. No curbs shall be constructed on Market Street in conjunction with the
Downtown Palm Springs project. Bollards shall be placed along the east and
west sides of Market Street to protect the public and buildings from accidental
vehicular contact. All bollards shall be maintained by the developer.
ENG 35. A modified driveway approach shall be constructed at the south end of Market
Street at its intersection with New Main Street (Lot "A").
ENG 36. Deleted.
ENG 37. Construct pavement with a minimum pavement section of 3 inches asphalt
concrete pavement over 6 inches crushed miscellaneous base with a minimum
subgrade of 24 inches at 95% relative compaction, or equal, between the edges
of proposed gutters on each side of the street along the Market Street, in
accordance with City of Palm Springs Standard Drawing No. 110 and the
Museum Market Plaza Specific Plan. If an alternative pavement section is
proposed, the proposed pavement section shall be designed by a California
registered Geotechnical Engineer using "R" values from the project site and
submitted to the City Engineer for approval.
ENG 38. There shall be no on-street parking on the west side of Market Street. Regulatory
Type R26 "No Parking" signs shall be installed along the west side of Market
Street, as necessary to enforce parking restrictions.
SANITARY SEWER
ENG 39. All sanitary facilities shall be connected to the public sewer'system. New laterals
shall not be connected at manholes.
ENG 40. All on-site sewer systems (not located in public streets) shall be privately
maintained.
ENG 41. Submit sewer improvement plans prepared by a California registered civil
engineer to the Engineering Division. The plan(s) shall be approved by the City
Engineer prior to issuance of any building permits.
ENG 42. Construct 8 inch V.C.P. sewer mains across the proposed New Main Street (Lot
"A") frontage along Block B — Phase 1 to Belardo Road (Lot B) and from the
intersection of Belardo Road (Lot B) and New Main Street (Lot A) to the
intersection of Tahquitz Canyon Way and Belardo Road (Lot B) located 5 feet
from centerline (or as required by the City Engineer), including a sewer lateral for
26
City Council Resolution
Page 20
future connection of the on-site sewer system to the public sewer, as required by
the City Engineer. The northerly units in Block B shall connect to the existing
sewer main in Palm Canyon Drive where feasible. Block A shall connect to the
existing sewer main in Palm Canyon Drive.
ENG 43. All sewer mains constructed by the developer and to become part of the City
sewer system shall be digitally video recorded by the City prior to acceptance of
the sewer system for maintenance by the City. Any defects of the sewer main
shall be removed, replaced, or repaired to the satisfaction of the City Engineer
prior to acceptance.
ENG 44. Any sewer connection fees shall be paid at the Building Department counter at
time of building permit issuance.
ENG 45. Upon completion of the construction of public sewer lines, an as-built drawing in
digital format shall be provided to the City as required by the City Engineer, if the
sewer was not constructed in accordance with the original approved sewer plans.
GRADING: BLOCK A— Phase 1 , BLOCK B - Phase1
ENG 46. Submit a Precise Grading Plan prepared by a California registered Civil engineer
to the Engineering Division for review and approval. The Precise Grading Plan
shall be approved by the City Engineer prior to issuance of grading permit.
a. A Fugitive Dust Control Plan shall be prepared by the applicant and/or its
grading contractor and submitted to the Engineering Division for review and
approval. The applicant and/or its grading contractor shall be required to
comply with Chapter 8.50 of the City of Palm Springs Municipal Code, and
shall be required to utilize one or more "Coachella Valley Best Available
Control Measures" as identified in the Coachella Valley Fugitive Dust Control
Handbook for each fugitive dust source such that the applicable performance
standards are met. The applicant's or its contractor's Fugitive Dust Control
Plan shall be prepared by staff that has completed the South Coast Air
Quality Management District (AQMD) Coachella Valley Fugitive Dust Control
Class. The applicant and/or its grading contractor shall provide the
Engineering Division with current and valid Certificate(s) of Completion from
AQMD for staff that has completed the required training. For information on
attending a Fugitive Dust Control Class and information on the Coachella
Valley Fugitive Dust Control Handbook and related "PM10" Dust Control
issues, please contact AQMD at (909) 396-3752, or at http://www.AQMD.-gov.
A Fugitive Dust Control Plan, in conformance with the Coachella Valley
Fugitive Dust Control Handbook, shall be submitted to and approved by the
Engineering Division prior to approval of the Grading plan.
b. The first submittal of the Grading Plan shall include the following information:
a copy of final approved conformed copy of Conditions of Approval; a copy of
27
City Council Resolution
Page 21
a final approved conformed copy of the Site Plan or Tentative Parcel Map No.
36446; a copy of current Title Report; a copy of Soils Report; a copy of the
associated Hydrology Study/Report (one hydrology study for Block A — Phase
land Block B — Phase 1); and a copy of the project-specific Final Water
Quality Management Plan (one WQMP for Block A — Phase 1 and Block B —
Phase 1).
ENG 47. Prior to approval of a Grading Plan (or issuance of a Grading Permit), the
applicant shall obtain written approval to proceed with construction from the
Agua Caliente Band of Cahuilla Indians, Tribal Historic Preservation Officer or
Tribal Archaeologist. The applicant shall contact the Tribal Historic Preservation
Officer or the Tribal Archaeologist at (760) 699-6800, to determine their
requirements, if any, associated with grading or other construction. The applicant
is advised to contact the Tribal Historic Preservation Officer or Tribal
Archaeologist as early as possible. If required, it is the responsibility of the
applicant to coordinate scheduling of Tribal monitors during grading or other
construction, and to arrange payment of any required fees associated with Tribal
monitoring.
ENG 48. In accordance with an approved PM-10 Dust Control Plan, temporary dust
control perimeter fencing shall be installed. Fencing shall have screening that is
tan in color or be decorative in nature; green screening will not be allowed.
Temporary dust control perimeter fencing shall be installed after issuance of
Grading Permit, and immediately prior to commencement of grading operations.
ENG 49. Temporary dust control perimeter fence screening shall be appropriately
maintained, as required by the City Engineer. Cuts (vents) made into the
perimeter fence screening shall not be allowed. Perimeter fencing shall be
adequately anchored into the ground to resist wind loading.
ENG 50. Within 10 days of ceasing all construction activity and when construction
activities are not scheduled to occur for at least 30 days, the disturbed areas on-
site shall be permanently stabilized, in accordance with Palm Springs Municipal
Code Section 8.50.022. Following stabilization of all disturbed areas, perimeter
fencing shall be removed, as required by the City Engineer.
ENG 51. A Notice of Intent (NOI) to comply with the California General Construction
Stormwater Permit (Water Quality Order 2009-0009-DWQ as modified
September 2, 2009) is required for the proposed development via the California
Regional Water Quality Control Board online SMARTS system. A copy of the
executed letter issuing a Waste Discharge Identification (WDID) number shall be
provided to the City Engineer prior to issuance of a grading or building permit.
ENG 52. Projects causing soil disturbance of one acre or more, must comply with the
General Permit for Stormwater Discharges Associated with Construction Activity,
and shall prepare and implement a stormwater pollution prevention plan
28
City Council Resolution
Page 22
(SWPPP) for all Blocks of the Downtown Palm Springs project. As of September
4, 2012, all SWPPPs shall include a post-construction management plan
(including Best Management Practices) in accordance with the current
Construction General Permit. Where applicable, the project applicant shall cause
the approved final project-specific Water Quality Management Plan to be
incorporated by reference or attached to the project's SWPPP as the Post-
Construction Management Plan. A copy of the up-to-date SWPPP shall be kept
at the project site and be available for review upon request.
ENG 53. In accordance with City of Palm Springs Municipal Code, Section 8.50.022 (h),
the applicant shall post with the City a cash bond of two thousand dollars
($2,000.00) per disturbed acre at the time of issuance of grading permit for
mitigation measures for erosion/blowsand relating to this property and
development.
ENG 54. A Geotechnical/Soils Report prepared by a California registered Geotechnical
Engineer shall be required for and incorporated as an integral part of the grading
plan for the proposed development. A copy of the Geotechnical/Soils Report
shall be submitted to the Engineering Division with the first submittal of a grading
plan.
ENG 55. The applicant shall provide all necessary geotechnical/soils inspections and
testing in accordance with the Geotechnical/Soils Report prepared for the
project. All backfill, compaction, and other earthwork shown on the approved
grading plan shall be certified by a California registered geotechnical or civil
engineer, certifying that all grading was performed in accordance with the
Geotechnical/Soils Report prepared for the project. Documentation of all
compaction and other soils testing are to be provided. No certificate of
occupancy will be issued until the required certification is provided to the City
Engineer.
ENG 56. The applicant shall provide pad elevation certifications for all building pads in
conformance with the approved grading plan, to the Engineering Division prior
to construction of any building foundation.
ENG 57. In cooperation with the Riverside County Agricultural Commissioner and the
California Department of Food and Agriculture Red Imported Fire Ant Project,
applicants for grading permits involving a grading plan and involving the export
of soil will be required to present a clearance document from a Department of
Food and Agriculture representative in the form of an approved "Notification of
Intent To Move Soil From or Within Quarantined Areas of Orange, Riverside,
and Los Angeles Counties' (RIFA Form CA-1) prior to approval of the Grading
Plan (if required). The California Department of Food and Agriculture office is
located at 73-710 Fred Waring Drive, Palm Desert (Phone: 760-776-8208).
WATER QUALITY MANAGEMENT PLAN: ALL BLOCKS
29
City Council Resolution
Page 23
ENG 58. This project shall be required to install measures in accordance with applicable
National Pollution Discharge Elimination System (NPDES) Best Management
Practices (BMP's) included as part of the NPDES Permit issued for the
Whitewater River Region from the Colorado River Basin Regional Water Quality
Control Board (RWQCB). The applicant is advised that installation of BMP's,
including mechanical or other means for pre-treating contaminated stormwater
and non-stormwater runoff, shall be required by regulations imposed by the
RWQCB. It shall be the applicant's responsibility to design and install
appropriate BMP's, in accordance with the NPDES Permit, that effectively
intercept and pre-treat contaminated stormwater and non-stormwater runoff
from the project site, prior to release to the City's municipal separate storm
sewer system ("MS4"), to the satisfaction of the City Engineer and the
RWQCB. Such measures shall be designed and installed on-site; and
provisions for perpetual maintenance of the measures shall be provided to the
satisfaction of the City Engineer, including provisions in Covenants, Conditions,
and Restrictions (CC&R's) required for the development (if any).
ENG 59. A Final Project-Specific Water Quality Management Plan (WQMP) for Blocks A
and B shall be submitted to and approved by the City Engineer prior to issuance
of a grading or building permit. The WQMP shall address the implementation of
operational Best Management Practices (BMP's) necessary to accommodate
nuisance water and storm water runoff from the site. Direct release of nuisance
water to the adjacent property (or public streets) is prohibited. Construction of
operational BMP's shall be incorporated into the Precise Grading Plan.
ENG 60. Prior to issuance of any grading or building permits, the property owner shall
record a "Covenant and Agreement" with the County-Clerk Recorder or other
instrument on a standardized form to inform future property owners of the
requirement to implement the approved Final Project-Specific WQMP. Other
alternative instruments for requiring implementation of the approved Final
Project-Specific WQMP include: requiring the implementation of the Final
Project-Specific WQMP in Home Owners Association or Property Owner
Association Covenants, Conditions, and Restrictions (CC&R's); formation of
Landscape, Lighting and Maintenance Districts, Assessment Districts or
Community Service Areas responsible for implementing the Final Project-
Specific WQMP; or equivalent. Alternative instruments must be approved by
the City Engineer prior to the issuance of any grading or building permits.
ENG 61. Prior to issuance of certificate of occupancy or final City approvals (OR of "final"
approval by City), the applicant shall: (a) demonstrate that all structural BMP's
have been constructed and installed in conformance with approved plans and
specifications; (b) demonstrate that applicant is prepared to implement all non-
structural BMP's included in the approved Final Project-Specific WQMP,
conditions of approval, or grading/building permit conditions; and (c)
30
City Council Resolution
Page 24
demonstrate that an adequate number of copies of the approved Final Project-
Specific WOMP are available for the future owners (where applicable).
DRAINAGE: ALL BLOCKS
ENG 62. All stormwater runoff passing through the site shall be accepted and conveyed
across the property in a manner acceptable to the City Engineer. For all
stormwater runoff falling on the site, on-site retention or other facilities approved
by the City Engineer shall be required to contain the increased stormwater runoff
generated by the development of the property. Provide a single hydrology study
(for Blocks A and B) to determine the volume of increased stormwater runoff due
to development of the site, and to determine required stormwater runoff
mitigation measures for the proposed development. Final retention basin sizing
and other stormwater runoff mitigation measures shall be determined upon
review and approval of the hydrology study by the City Engineer and may require
redesign or changes to site configuration or layout consistent with the findings of
the final hydrology study. On-site open space, in conjunction with dry wells and
other subsurface solutions should be considered as alternatives to using
landscaped parkways for on-site retention.
ENG 63. Direct release of on-site nuisance water or stormwater runoff shall not be
permitted to Palm Canyon Drive, Tahquitz Canyon Way, Museum Drive, existing
sections of Belardo Road, proposed New Main Street (Lot A), proposed Belardo
Road (Lot B and C), and Andreas Road (Lot D). Provisions for the interception of
nuisance water from entering adjacent public streets from the project site shall
be provided through the use of a minor storm drain system that collects and
conveys nuisance water to landscape or parkway areas, and in only a
stormwater runoff condition, pass runoff directly to the streets through parkway
or under sidewalk drains. Much of the drainage shall go into the existing public
storm drain line in Tahquitz Canyon Way.
ENG 64. Construct all necessary on-site storm drain improvements, including but not
limited to catch basins and storm drain lines, for drainage of site into the on-site
underground detention system(s) and other specifications for construction of
required on-site storm drainage improvements, as described in a final Hydrology
Study for the Downtown Palm Springs project (Tentative Parcel Map No. 36446),
reviewed and approved by the City Engineer.
ENG 65. All on-site storm drain systems shall be privately maintained.
ENG 66. The underground stormwater detention system(s) shall be sized to have
sufficient capacity equal to the volume of increased stormwater runoff due to
development of the site, as identified in a final hydrology study approved by the
City Engineer. A decrease to the required detention volume may be allowed for
percolation of the stormwater runoff into the underlying gravel and soil, not to
exceed 2 inches per hour. Maintenance of the underground stormwater
31
City Council Resolution
Page 25
detention systems are the sole responsibility of the development owner(s);
maintenance and/or replacement of the system(s), will be at the sole expense of
the development owner(s). The Final Project-Specific Water Quality
Management Plan Covenant and Agreement shall reserve the right of the City to
inspect and ensure that the underground detention system(s) are operable, and
in the event of its failure, shall provide the City the right to advise the owner(s) of
the development and require its repair or replacement within 30 days' notice, to
the satisfaction of the City Engineer.
ENG 67. The project is subject to flood control and drainage implementation fees. The
acreage drainage fee at the present time is $9,212.00 per acre in accordance
with Resolution No. 15189. Fees shall be paid prior to issuance of a building
permit unless developer can provide evidence that fee or a partial fee was paid
by the Desert Fashion Plaza in previous years.
GENERAL: ALL BLOCKS
ENG 68. Any utility trenches or other excavations within existing asphalt concrete
pavement of off-site streets required by the proposed development shall be
backfilled and repaired in accordance with City of Palm Springs Standard
Drawing No. 115. The developer shall be responsible for removing, grinding,
paving and/or overlaying existing asphalt concrete pavement of off-site streets as
required by and at the discretion of the City Engineer, including additional
pavement repairs to pavement repairs made by utility companies for utilities
installed for the benefit of the proposed development (i.e. Desert Water Agency,
Southern California Edison, Southern California Gas Company, Time Warner,
Verizon, Mission Springs Water District, etc.). Multiple excavations, trenches,
and other street cuts within existing asphalt concrete pavement of off-site streets
required by the proposed development may require complete grinding and
asphalt concrete overlay of the affected off-site streets, at the discretion of the
City Engineer. The pavement condition of the existing off-site streets shall be
returned to a condition equal to or better than existed prior to construction of the
proposed development.
ENG 69. On phases or elements of construction following initial site grading (e.g., sewer,
storm drain, or other utility work requiring trenching) associated with this project,
the applicant shall be responsible for coordinating the scheduled construction
with the Agua Caliente Band of Cahuilla Indians, Tribal Historic Preservation
Officer or Tribal Archaeologist. Unless the project site has previously been
waived from any requirements for Tribal monitoring, it is the applicant's
responsibility to notify the Tribal Historic Preservation Officer or the Tribal
Archaeologist at (760) 699-6800, for any subsequent phases or elements of
construction that might require Tribal monitoring. If required, it is the
responsibility of the applicant to coordinate scheduling of Tribal monitors during
construction, and to arrange payment of any required fees associated with Tribal
monitoring. Tribal monitoring requirements may extend to off-site construction
2
City Council Resolution
Page 26
performed by utility companies on behalf of the applicant (e.g. utility line
extensions in off-site streets), which shall be the responsibility of the applicant to
coordinate and arrange payment of any required fees for the utility companies.
ENG 70. All proposed utility lines shall be installed underground.
ENG 71. All existing utilities shall be shown on the improvement plans if required for the
project. The existing and proposed service laterals shall be shown from the main
line to the property line. Upon approval of any improvement plan by the City
Engineer, the improvement plan shall be provided to the City in digital format,
consisting of a DWG (AutoCAD 2004 drawing file), DXF (AutoCAD ASCII
drawing exchange file), and PDF (Adobe Acrobat 6.0 or greater) formats.
Variation of the type and format of the digital data to be submitted to the City
may be authorized, upon prior approval of the City Engineer.
ENG 72. The original improvement plans prepared for the proposed development and
approved by the City Engineer (if required) shall be documented with record
drawing "as-built' information and returned to the Engineering Division prior to
issuance of a final certificate of occupancy. Any modifications or changes to
approved improvement plans shall be submitted to the City Engineer for approval
prior to construction.
ENG 73. Nothing shall be constructed or planted in the corner cut-off area of any
intersection or driveway which does or will exceed the height required to maintain
an appropriate sight distance per City of Palm Springs Zoning Code Section
93.02.00, D.
ENG 74. All proposed trees within the public right-of-way and within 10 feet of the public
sidewalk and/or curb shall have City approved deep root barriers installed in
accordance with City of Palm Springs Standard Drawing No. 904.
ENG 75. This property is subject to the Coachella Valley Multiple Species Habitat
Conservation Plan Local Development Mitigation fee (CVMSHCP-LDMF). The
LDMF shall be paid prior to issuance of Building Permit.
ENG 76. If there are any lights from Lighting District No. 1, existing on Tahquitz Canyon
Way and Museum Drive along the Tentative Parcel Map (TPM) 36446 frontage,
those lights shall be removed in conjunction with this project.
ENG 77. Note that some of the existing street lights shown on the Preliminary Grading
and Drainage Plan for TPM36446, do not exist; corrections need to be made to
this plan to reflect what actually exists.
MAP: ALL BLOCKS
33
City Council Resolution
Page 27
ENG 78. In accordance with Government Code Section 66411.1 (b), the Tentative Parcel
Map is a subdivision of five or more lots (parcels), and is subject to construction
of all required public improvements. Prior to approval of a Parcel Map, all
required public improvements shall be completed to the satisfaction of the City
Engineer, or shall be secured by the Project Financing Agreement signed by
Palm Springs Promenade, LLC and the City of Palm Springs on September 7,
2011 (in accordance with Government Code Section 66462) as amended.
TRAFFIC: ALL BLOCKS
ENG 79. A minimum of 48 inches of clearance for handicap accessibility shall be provided
on public sidewalks or pedestrian paths of travel within the development.
Developer shall assure that handicap accessibility is continuous particularly
adjacent to the Hyatt Hotel.
ENG 80. All damaged, destroyed, or modified pavement legends, traffic control devices,
signing, striping, and street lights, associated with the proposed development
shall be replaced as required by the City Engineer prior to issuance of a
Certificate of Occupancy.
ENG 81. Submit traffic striping and signage plans for New Main Street (Lot "A"), Andreas
Road (Lot "D"), and Market Street, prepared by a California registered civil
engineer, for review and approval by the City Engineer. All required traffic
striping and signage improvements shall be completed in conjunction with
required street improvements, to the satisfaction of the City Engineer, and prior
to issuance of a certificate of occupancy.
ENG 82. Relocate the existing traffic signal pole, conduit, pull boxes and all
appurtenances located at the existing crosswalk on Palm Canyon Drive south of
the intersection of New Main Street (Lot "A") and Palm Canyon Drive, in
accordance with the requirements of the City of Palm Springs. The applicant
shall submit traffic signal modification plans prepared by a California registered
civil engineer or traffic engineer for review and approval by the City Engineer.
The traffic signal shall be installed and operational prior to issuance of the
Certificate of Occupancy, unless otherwise allowed by the City Engineer. The
existing crosswalk shall be relocated north.
ENG 83. The applicant shall install a Type R6-1 "One Way" sign at the southwest corner
of Andreas Road (Lot "D") and Palm Canyon Drive, facing eastbound traffic on
Andreas Road, as required by the City Engineer.
ENG 84. Install a stop sign, stop bar, and "STOP" legend for traffic exiting the
development at the following intersections in accordance with City of Palm
Springs Standard Drawing Nos. 620-625 and the California Manual on Uniform
Traffic Control Devices, dated January 13, 2012, or subsequent editions in force
at the time of construction, as required by the City Engineer.
34
City Council Resolution
Page 28
• Southwest corner of Andreas Road (Lot "D") and Palm Canyon Drive,
facing eastbound traffic on Andreas Road
• Southeast corner of Market Street and Andreas Road (Lot "D"), facing
northbound traffic on Market Street
• Northwest corner of Market Street and New Main Street (Lot "A"), facing
southbound traffic on Market Street
ENG 85. Install a street name sign at all corners of all intersections that are a part of the
Downtown Palm Springs project, in accordance with City of Palm Springs
Standard Drawing Nos. 620 through 625 and the California Manual on Uniform
Traffic Control Devices for Streets and Highways, dated January 13, 2012, or
subsequent editions in force at the time of construction, as required by the City
Engineer.
ENG 86. Construction signing, lighting and barricading shall be provided during all
phases of construction as required by City Standards or as directed by the
City Engineer. As a minimum, all construction signing, lighting and
barricading shall be in accordance with Part 6 "Temporary Traffic Control' of
the California Manual on Uniform Traffic Control Devices for Streets and
Highways, dated January 13, 2012, or subsequent editions in force at the
time of construction.
ENG 87. This property is subject to the Transportation Uniform Mitigation Fee which
shall be paid prior to issuance of building permit.
ENG 88. No construction traffic shall enter the project site from N. Palm Canyon Drive or
Tahquitz Canyon Way.
ENG 89. Parking shall be restricted along both sides of Lot "A" and "D" as necessary to
maintain a minimum 24 feet wide clear two-way travel way, except for designated
parallel parking spaces. Regulatory Type R26 "No Parking" signs shall be
installed along Lot "A" and Lot "D", as necessary to enforce parking restrictions.
ENG 90. Approximately one year after the opening of Downtown Palm Springs, a traffic
study shall be submitted and approved by the City Engineer to determine if the
current (at that time) traffic control devices are functioning optimally, and to
determine if traffic signal warrants have been met for any intersection that is a
part of Downtown Palm Springs (such as at the intersection of Tahquitz Canyon
Way and Belardo Road (Lot "B").
ENG 91. Developer shall cooperate with any City-approved events in which public streets
adjacent to the site are temporarily closed by assisting with and not interfering
with said closures.
35
City Council Resolution
Page 29
FIRE DEPARTMENT CONDITIONS
FID 1. These conditions are subject to final plan check and review. Initial fire
department conditions have been determined on the site plan received and
stamped May 27, 2017. The submitted plans do not provide enough detail.
Additional requirements may be required at that time based on revisions to
site plans.
FID 2. Fire Department Conditions were based on the 2010 California Fire Code as
adopted by City of Palm Springs, Palm Springs Municipal Code and latest
adopted NFPA Standards. Four complete sets of plans for private fire service
mains, fire alarm, or fire sprinkler systems must be submitted at time of the
building plan submittal.
FID 3. Buildings and Facilities (CFC 503.1.1): Approved fire apparatus access
roads shall be provided for every facility, building or portion of a building
hereafter constructed or moved into or within the jurisdiction. The fire
apparatus access road shall comply with the requirements of this section and
shall extend to within 150 feet of all portions of the facility and all portions of
the exterior walls of the first story of the building as measured by an approved
route around the exterior of the building or facility.
FID 4. Aerial Fire Access Roads (CFC Appendix D105.1): Buildings or portions of
buildings or facilities exceeding 30 feet in height above the lowest level of fire
department vehicle access shall be provided with approved fire apparatus
access roads capable of accommodating fire department aerial apparatus.
Overhead utility and power lines shall not be located within the aerial fire
apparatus access roadway.
FID 5. Aerial Fire Access Road Width (CFC Appendix D105.2): Fire apparatus
access roads shall have a minimum unobstructed width of 26 feet, exclusive
of shoulders, in the immediate vicinity of any building or portion of building
more than 30 feet in height.
FID 6. Aerial Access Proximity to Building (CFC Appendix D105.3): At least one
of the required access routes for buildings or facility exceeding 30 feet in
height above the lowest level of fire department vehicle access shall be
located within a minimum of 15 feet and a maximum of 30 feet from the
building and shall be positioned parallel to one entire side of the building.
FID 7. Fencing Requirements (8.04.260 PSMC): Construction site fencing with 20
foot wide access gates is required for all combustible construction over 5,000
square feet. Fencing shall remain intact until buildings are plastered or
covered and secured with lockable doors and windows.
36
City Council Resolution
Page 30
FID 8. Access during Construction (CFC 503): Access for firefighting equipment
shall be provided to the immediate job site at the start of construction and
maintained until all construction is complete. Fire apparatus access roads
shall have an unobstructed width of not less than 20 feet and an
unobstructed vertical clearance of not less than 13'-6". Fire Department
access roads shall have an all-weather driving surface and support a
minimum weight of 73,000 lbs.
FID 9. Fire Apparatus Access Gates (8.04.260 PSMC): Entrance gates shall have
a clear width of at least 14 feet and be equipped with a frangible chain and
padlock.
FID 10. Surface (CFC 503.2.3): Fire apparatus access roads shall be designed and
maintained to support the imposed loads of fire apparatus (73,000 lbs. GVW)
and shall be surfaced so as to provide all-weather driving capabilities.
Fire apparatus access roads shall be designed and maintained to support the
imposed loads of fire apparatus (73,000 lbs. GVW) and shall be surfaced so
as to provide all-weather driving capabilities. Decomposed granite (DG),
grass, dirt, sand and other materials that can wash away, develop ruts or be
dug up shall not be used. Interlocking pavers, turf block or other similar
materials may be allowed, subject to the provision of proper base material
and compliance with City Engineering Department compaction requirements.
Prior to permit sign-off, compaction test results shall be submitted to the City
Engineering Department for approval.
FID 11, Turning radius (CFC 503.2.4): Fire access road turns and corners shall be
designed with a minimum inner radius of 25 feet and an outer radius of 43
feet. Radius must be concentric.
FID 12. Dead Ends (CFC 503.2.5): Dead-end fire apparatus roads in excess of 150
feet in length shall be provided with an approved area for turning around fire
apparatus. The City of Palm Springs has two approved turn around
provisions. One is a cul-de-sac with an outside turning radius of 43 feet from
centerline. The other is a hammerhead turnaround meeting the Palm Springs
Public Works and Engineering Department standard dated 9-4-02.
FID 13. Security Gates (CFC 503.6): The installation of security gates across a fire
apparatus access road shall be approved by the fire chief. Where security
gates are installed, they shall have an approved means of emergency
operation. The security gates and the emergency operation shall be
maintained operational at all times. Secured automated vehicle gates or
entries shall utilize a combination of a Tomar StrobeswitchTm, or approved
equal, and an approved Knox key electric switch. Electric gate operators,
where provided, shall be listed in accordance with UL 325. Gates intended for
automatic operation shall be designed, constructed and installed to comply 37
City Council Resolution
Page 31
with the requirements of ASTM F 2200. Secured non-automated vehicle
gates or entries shall utilize an approved padlock or chain (maximum link or
lock shackle size of inch). Approved security gates shall be a minimum of
14 feet in unobstructed drive width on each side with gate in open position.
Gate arms securing parking lots and parking structures shall be equipped
with a combination of a Tomar Strobeswitch TM, or approved equal, and an
approved Knox key electric switch. When activated, the arm or arms shall
open to allow fire and law enforcement access.
In the event of a power failure, the gates shall be defaulted or automatically
transferred to a fail safe mode allowing the gate to be pushed open without
the use of special knowledge or any equipment. If a two-gate system is used,
the override switch must open both gates.
If there is no sensing device that will automatically open the gates for exiting,
a fire department approved Knox electrical override switch shall be placed on
each side of the gate in an approved location.
A final field inspection by the fire code official or an authorized representative
is required before electronically controlled gates may become operative.
Prior to final inspection, electronic gates shall remain in a locked-open
position.
FID 14. Premises Identification (CFC 505.1): New and existing buildings shall have
approved address numbers, building numbers or approved building
identification placed in a position that is plainly legible and visible from the
street or road fronting the property. These numbers shall contrast with their
background Address numbers shall be Arabic numbers or alphabetical
letters. Numbers shall be a minimum of 4 inches high for R-3 occupancies
and 6" - 12" for all other occupancies depending on distance from street with
a minimum stroke width of 0.5 inch. Where access is by means of a private
road and the building cannot be viewed from the public way, a monument,
pole or other sign or means shall be used to identify the structure.
FID 15. Key Box Required to be Installed (CFC 506.1): Where access to or within a
structure or an area is restricted because of secured openings or where
immediate access is necessary for life-saving or fire-fighting purposes, the
fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be flush mount type and shall contain
keys to gain necessary access as required by the fire code official.
FID 16. Key Box Contents (CFC 506.1): The Knox key box shall contain keys to all
areas of ingress/egress, alarm rooms, fire sprinkler riser/equipment rooms,
38
City Council Resolution
Page 32
mechanical rooms, elevator rooms, elevator controls, plus a card containing
the emergency contact people and phone numbers for the building/complex.
FID 17. Water Agency Construction Specifications: All public water mains, fire
hydrants and double check detector assemblies must be installed in
accordance with DWA specifications and standards. Private fire hydrants
shall be painted OSHA safety red. Public fire hydrants shall be painted
equipment yellow.
FID 18. Water Plan (CFC 501.3 & 901.2): A water plan for on-site and off-site is
required and shall include underground private fire main for fire sprinkler
riser(s), public fire hydrant(s), public water mains, Double Check Detector
Assembly, Fire Department Connection and associated valves.
FID 19. Required Water Supply (CFC 507.1): An approved water supply capable of
supplying the required fire flow for fire protection shall be provided to
premises upon which facilities, buildings or portions of buildings are hereafter
constructed or moved into or within the jurisdiction.
FID 20. Fire Hydrant Flow (CFC 507.3): Fire flow requirements for buildings or
portions of buildings and facilities are shall be determined by Appendix B.
FID 21. Fire Hydrant Systems (CFC 507.5): Fire hydrant systems shall comply with
Sections 507.5.1 through 507.5.6 and Appendix C.
FID 22. Operational Fire Hydrant(s) (CFC 507.1, 507.5.1 & 1412.1): Operational
fire hydrant(s) shall be installed within 250 feet of all combustible
construction. They shall be installed and made serviceable prior to and
during construction. No landscape planting, walls, or fencing is permitted
within 3 feet of fire hydrants, except ground cover plantings.
FID 23. Water Systems and Hydrants (CFC 507.1, 507.2, 507.4, 901.5 & 1412.1):
Underground private fire service mains and fire hydrants shall be installed,
completed, tested and in service prior to the time when combustible materials
are delivered to the construction site. (903 CFC) Installation, testing, and
inspection will meet the requirements of NFPA 24, 2010 Edition. Prior to final
approval of the installation, contractor shall submit a completed Contractors
Material & Test Certificate for Underground Piping to the Fire Department.
(NFPA 24: 10.10, 2010 Edition).
FID 24. Identification (CFC 509.1): Fire protection equipment shall be identified in
an approved manner. Rooms containing controls for air-conditioning systems,
sprinkler risers and valves, or other fire detection, suppression or control
elements shall be identified for the use of the fire department. Approved signs
39
City Council Resolution
Page 33
required to identify fire protection equipment and equipment location, shall be
constructed of durable materials, permanently installed and readily visible.
FID 25. Elevator Recall Required (CFC 607.1): Existing elevators with a travel
distance of 25 feet (7620 mm) or more above or below the main floor or other
level of a building and intended to serve the needs of emergency personnel
for fire-fighting or rescue purposes shall be provided with emergency
operation in accordance with ASME Al7.3. New elevators shall be provided
with Phase I emergency recall operation and Phase II emergency in-car
operation in accordance with ASME A17.1 (California Code of Regulations,
Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders).
FID 26. Elevator Stretcher Requirement (CBC 3002.4): Elevators shall be designed
to accommodate medical emergency service. The elevator(s) so designed
shall accommodate the loading and transport of an ambulance gurney or
stretcher 24 inches by 84 inches in the horizontal position. The elevator
entrance shall have a clear opening of not less than 42 inches wide or less
than 78 inches high. The elevator car shall be provided with a minimum clear
distance between walls or between walls and door excluding return panels
not less than 80 inches by 54 inches, and a minimum distance from wall to
return panel not less than 51 inches with a 42 inch side slide door.
FID 27. Fire Dampers (CMC 606.2): They shall be provided where air ducts
penetrate fire-rated walls or ceilings.
FID 28. Maintenance of Fire-Resistance-Rated Construction (CFC 703.1): The
required fire-resistance rating of fire-resistance-rated construction (including
walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-
resistive coatings and sprayed fire-resistant materials applied to structural
members and fire-resistant joint systems) shall be maintained. Such elements
shall be properly repaired, restored or replaced when damaged, altered,
breached or penetrated. Openings made therein for the passage of pipes,
electrical conduit, wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of resisting the
passage of smoke and fire. Openings through fire-resistance-rated
assemblies shall be protected by self- or automatic-closing doors of approved
construction meeting the fire protection requirements for the assembly.
FID 29. Interior Finish, Decorative Materials and Furnishings (CFC 801.1): The
provisions of this chapter shall govern interior finish, interior trim, furniture,
furnishings, decorative materials and decorative vegetation in buildings.
Section 803 shall be applicable to existing buildings. Sections 804 through
808 shall be applicable to new and existing buildings.
40
City Council Resolution
Page 34
FID 30. Decorative Materials Other Than Decorative Vegetation In New and
Existing Buildings (CFC 807.1): In occupancies in Groups A, E, I and R-1
and dormitories in Group R-2, curtains, draperies, hangings and other
decorative materials suspended from walls or ceilings shall meet the flame
propagation performance criteria of NFPA 701 in accordance with Section
807.2 or be noncombustible. Provide samples and documentation to submit
to the Palm Springs Fire Department to prove conformance with the above
criteria above.
FID 31. Acceptance Criteria and Reports (CFC 807.2): Where required to be flame
resistant, decorative materials shall be tested by an approved agency and
meet the flame propagation performance criteria of NFPA 701, or such
materials shall be noncombustible. Reports of test results shall be prepared
in accordance with NFPA 701 and furnished to the fire code official.
FID 32. NFPA 13 Fire Sprinkler System is Required: An automatic fire sprinkler
system is required. Only a C-16 licensed fire sprinkler contractor shall
perform system design and installation. System to be designed and installed
in accordance with NFPA 13, 2010 Edition and using Cp of 0.74 and I/r Ratio
of 200. No portion of the fire sprinkler system shall be installed prior to plan
approval. Prior to final approval of the installation, contractor shall submit a
completed Contractors Material and Test Certificate for Aboveground Piping
to the Fire Department. (NFPA 13: Figure 24.1)
FID 33. Floor Control Valves (CFC903.3.8 & Ordinance 1781: Item 42): Floor
control valves and water-flow detection assemblies shall be installed at each
floor in buildings three or more stories in height. Valve locations will be
determined and approved by the fire code official.
FID 34. Fire Alarm System: Fire alarm system shall comply with the requirements of
NFPA 72, 2010 Edition.
FID 35. Fire Sprinkler Supervision and Alarms System (CFC 903.4/4.1): All valves
controlling the water supply for automatic sprinkler systems, pumps, tanks,
water levels and temperatures, critical air pressures and water-flow switches
on all fire sprinkler systems shall be electrically supervised by a listed Fire
Alarm Control Unit (FACU). The listed FACU alarm, supervisory and trouble
signals shall be distinctly different and shall be monitored at a UL listed
central station service. The fire sprinkler supervision and alarms system shall
comply with the requirements of NFPA 72, 2010 Edition. All control valves
shall be locked in the open position.
FID 36. Central Station Protective Signaling Service (CFC 903.4.1): A UL listed
and certified Protective Signaling Service (Central Station Service) is
required. Provide the Fire Department with proof of listing and current
41
City Council Resolution
Page 35
certificate. The Fire Department shall be notified immediately of change in
service.
FID 37. Audible Water Flow Alarms (CFC 903.4.2 & Appendix K: 4.3): An
approved audible sprinkler flow alarm (Wheelock horn/strobe with WBB back
box or equal) shall be provided on the exterior of the building in an approved
location. The horn/strobe shall be outdoor rated. A second horn/strobe shall
be installed in the interior of the building in a normally occupied location. In
multiple suite buildings, additional interior horn/strobes shall be installed in all
suites with 50 or more occupant load. Power shall be provided from a fire
alarm control unit. Where a building fire alarm system is installed, actuation of
the automatic sprinkler system shall actuate the building fire alarm system.
FID 38. Fire Hydrant & FDC Location: A public commercial fire hydrant is required
within 30 feet of the Fire Department Connection (FDC). Fire Hose must be
protected from vehicular traffic and shall not cross roadways, streets, railroad
tracks or driveways or areas subject to flooding or hazardous material or
liquid releases. A field analysis of existing hydrants has not been conducted
to verify hydrant location or availability. This comment is included to make
you aware that additional fire hydrants may be required.
FID 39. Fire Department Connections: Fire Department connections shall be visible
and accessible, have two 2.5 inch NST female inlets, and have an approved
check valve located as close to the FDC as possible. All FDC's shall have
KNOX locking protective caps. Contact the fire prevention secretary at 760-
323-8186 for a KNOX application form.
FID 40. Location of Fire Department Connections: The connection inlets must face
the street, and be located on the street side of the building. The face of the
inlets shall be 18 inches horizontal from the back edge of sidewalk (or back of
curb, if no sidewalk), and shall be 36 to 44 inches in height to center of inlets
above finished grade. No landscape planting, walls, or other obstructions are
permitted within 3 feet of Fire Department connections. The FDC and
supporting piping shall be painted OSHA safety red.
The address of the building served shall be clearly indicated on the Fire
Department Connection (FDC). A sign with this information shall be placed on
or near the FDC. The sign shall be constructed of metal. The sign face,
lettering, and attachment shall be made of weather and vandal resistant
materials. Sign background will be bright red. Letters will be bright white.
Sign format will be substantially as follows:
F. D. C. SERVES
123 N. P. C.
ALL BLDGS. IN COMPLEX
42
City Council Resolution
Page 36
FID 41 . Standpipe Systems Required (CFC 905.3): Class I Standpipe system is
required in addition to the automatic sprinkler system. Standpipe systems
shall be installed where required by Sections 905.3.1 through 905.3.10. f and
in the locations indicated in Sections 905.4, 905.5 and 905.6. Standpipe
systems are allowed to be combined with automatic sprinkler systems.
FID 42. Fire Extinguisher Requirements (CFC 906): Provide one 2-A:10-B:C
portable fire extinguisher for every 75 feet of floor or grade travel distance for
normal hazards. Show proposed extinguisher locations on the plans.
Extinguishers shall be mounted in a visible, accessible location 3 to 5 feet
above floor level. Preferred location is in the path of exit travel or near an exit
door.
FID 43. HVAC Duct Smoke Detection/Shut Down with a Fire Sprinkler
Supervision & Alarm System or Fire Alarm System (CFC 907.4.1, CMC
609.0 & NFPA 72): All HVAC systems supplying greater than 2,000 CFM
shall require a duct detector and HVAC shut down when smoke is detected.
HVAC shut down shall be on an individual basis, not global. These systems
shall supervise the Duct Detectors and activate the notification appliances.
An accessory module shall be installed for each unit, including alarm LED,
pilot LED and key-operated test/reset switch.
FID 44. Posting of Occupant Load (CFC 1004.3): Every room or space that is
assembly occupancy shall have the occupant load of the room or space
posted in a conspicuous place, near the main exit or exit access doorway
from the room or space. Posted signs shall be of an approved legible
permanent design and shall be maintained by the owner or authorized agent.
FID 45. Means of Egress Illumination (CFC 1006.1 & 2): Any time a building is
occupied, the means of egress shall be illuminated at an intensity of not less
than 1 foot-candle at the floor level.
FID 46. Means of Egress Illumination Power Supply (CFC 1006.3): The power
supply for means of egress illumination shall normally be provided by the
premises' electrical supply. In the event of power supply failure, an
emergency electrical system shall automatically illuminate in defined areas
listed in the CFC.
FID 47. Required Exit Signs (CFC 1011.1): Exits & exit access doors shall be
marked by an approved exit sign readily visible from any direction of egress
travel. Access to exits shall be marked by readily visible exit signs in cases
where the exit or path is not immediately visible to occupants. No point in the
corridor shall be more than 100 feet or the listed viewing distance for the sign,
whichever is less, from the nearest visible sign.
43
City Council Resolution
Page 37
FID 48. Exit Sign Illumination (CFC 1011.2, 4 & 5): Exit signs shall be internally or
externally illuminated. When the face of an exit sign is illuminated from an
external source, it shall have an intensity of not less than 5 foot-candles from
either of two electric lamps. Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.
44
LawOffices of 6ebak Noficy
September 22,2014
Via Hand Delivery
Palm Springs Planning Commission
3200 E Tahquitz Canyon Way
Palm Springs, CA 92262
RE: September 10,2014 Planning Commission approval of
Item 2C,Revised Architectural Application for a two-story commercial
building on Block B of the Downtown Palm Springs Renovation Project and
Item 211, Palm Springs Promenade, LLC, Revised Architectural application
1504 Marsh street for Block A
Son Luis Obispo
Cafrfornio 93401 Advocates for Better Community Development,or ABCD hereby appeals the Palm
ph:805.593.0926 Springs Planning Commission's approval of the above referenced items at its September
tax:805.593.0946 10,2014 meeting. The grounds for this appeal were explained in ABCD's letter to the
Planning Commission dated September 9, 2014, a copy of which is attached hereto.
Do00tnOlicy Qibc®�obol,n®1
Please notify this office as soon as hearing date for this item has been set.
Law Office of Babak Naficy
Z5X 'z'_
Babak Nafic Counsel
y, for AB D
45
b,2:drOd G660C2£09LT:01 9b601:6SS08T OS3 ADIJ NJ NUUJ8:wuJd 01:9T H02-22-d3S
LOW Offices of lobak Naticy
September 9, 2014
Via Email Only
Palm Springs Planning Commission
Care of: David Newell and Douglas Evans
david.newellQ3almsorinas-ca.iwv
douelas.evans!2.palmsprings-ca._ov
RE: September 10,2014 Planning Commission Hearing
Item 2C,Revised Architectural Application for a two-story commercial
building on Block B of the Downtown Palm Springs Renovation Project and
1 504 Marsh Street Item 2B, Palm Springs Promenade,LLC, Revised Architectural application
Son Luis Obispo for Block A
California 93401
ph:805-593-0926 Planning Commissioners,
fox:805.593-0946
I submit this letter on behalf of advocates for Better Community Development, or
babaynalicyesbcglabal.nel ABCD, relative to the above-reference Planning Commission Items. The agenda lists
these items under New Business,meaning that that the items would not be open for
public comment. Pursuant to Specific Plan and the Palm Springs Municipal Cade
(PSMC),however,the City is required to conduct a public hearing for these items.
According to the Museum Market Plaza Specific Plan, once the Planning Department
finds the Major Architectural Application is complete,the Architectural Advisory
Committee must hold a hearing within 30 days,followed by a"public meeting" by the
Planning Commission within 45 days. "The Commission,upon closing the public
hearing,"can request changes to the application and continue the matter,or approve the
project, or deny the project. Actions of the Planning Commission are final unless
appealed to the City Council. Specific Plan, V-2. Thus, according to the Specific Plan,
the Planning Commission must convene a public hearing to consider any Major
Architectural Application.
Accordingly,the Revised Architectural Application for Block B should be considered at
a public hearing subject to public comments. The proposed two-story Project constitutes
a major revision to the previously approved single-story building. Public comments on
the new proposed plans,therefore,are critical.
96
b/£:d6pd b66b£2£09LT:01 9060CGSS081 i9S3 ADIdtlN )IN8HB:w0ad OT:91 t402-22-dM
Likewise,item 28 must also be considered by the Commission at a public hearing. According to
PSMC.§94.4.00(E)(2)(c),Planning Commission review and approval after review by the planning
commission architectural advisory committee"may be placed on the planning commission
consent calendar unless other discretionary actions are required." Accordingly,the approval of
this item too must be subject to a public hearing and opportunity for public comment.
Application Review is premature because development plans have not been submitted
Another problem with the City's handling of these items is that the Staff Report and agenda do
not include the applicant's proposed development plans. The Staff Report states that"staff's
analysis of plans to be completed once submitted by applicant,"making it difficult to understand
how the planning staff could have deemed the Application complete without any plans. According
to PSMC §94.40.00(.E), "[a]n application for new construction and additions shall include a
preliminary landscape plan and drawings showing the exterior elevation of sides of a proposed
building or structure,the types of materials and colors to be used, and the signs to be displayed."
A Commission hearing is to be set only after the staff has deemed the application to be complete.
Likewise, it would appear that the application for architectural review of Block A proposal is
likewise incomplete at the time the Planning Commission first considered this item. This is
evident because according to the Staff Report,the Commission was concerned about the lack of
information about materials and elevations.
Flow can the public, or the Planning Commission,for that matter,conduct an adequate review of
the project and intelligently comment on the project if the proposed plans and the staffs analysis
of the plans are not included in the agenda and available for review? In this regard, I note that the
same problem occurred previously with respect to the same project when the plans to be
considered by the AAC had not been ready and therefore not been submitted for review by the
members of the AAC prior to the AAC meeting on June 23,2014. According to the Planning
Commission Minutes, "Commissioner Klatchko said he attended the AAC meeting when this
project was presented and noted that they received the staff report last minute and were not
prepared." 'Without the actual plans and staffs analysis of same,the public and Commissioners
are deprived of an opportunity to adequately analyze the project and make appropriate comments
at the public hearing.
Based on the foregoing,the Planning Commission cannot undertake the proposed architectural
review until the applicant's plans have been submitted to the City and made available to the
public. Thereafter,the Planning Commission must convene an appropriately noticed public
hearing at which it is prepared to take public testimony.
Sincerely,
/s/
Babak Naficy,Counsel for ABCD
47
bib:d6ed b666£2£09L1 0l 9b60£6SS081 DS3 AJIdtlN )Pd8H8:W6J3 11 :91 h102-22-d3S
"[[Si
CITY OF PALM SPRINGS
RECVD BY: CR 01000068756
PAYOR: ABCD ADVOCATES FOR
TODAY'S DATE: 09/23/14
REGISTER DATE: 09/23/14 TIME: 09:37
DESCRIPTION AMOUNT
OTHER CHARGES SVCS $546.00
CUST ID: APPEAL FEE
----------------
TOTAL DUE: $546.00
CHECK PAID: $546.00
CHECK NO: 1012
TENDERED: $546.00
CHANGE: $.00
"[[4i
co
ABCD ADVOCATES FOR BETTER 1012
COMMUNITY DEVELOPMENT
930 E CHIA AD(760)31M618
PALM SPRINGS,CA 92262 Dale 2,z/by Ie-MI220
950
Da fo tfifie��'' 'L^ o�
$ —4�
Dollars
BankofAmerica �ustoiter s(nre
Pti eau
Spalm sn Ur
Palm sprin CA -
760.34 .IW7
For ... ... .
REQUEST FOR TREASURER'S RECEIPT
TO: FINANCE DEPARTMENT, CASHIER DATE: @ a�
FROM: CITY CLERK'S OFFICE
PLEASE ACCEPT $ JL\65oz
FROM:
FOR: "*W
tX'W IONS�—DD1(J-34106" "
OTHER CHARGES — CURRENT SERVICE — 001-34110
CREDIT ACCOUNT NO. CIRCLED ABOVE BY ORDER OF
49
I
City of Palm Springs
Office of the City Clerk
3200 E.Tahquirz Canyon Way • Palm Springs,CA 92262
lip Tel:(760)323-8204 • Fax:(760)322-8332 • TDD:(760)864-9527 • Web:www.palmspringsca.gov
October 1, 2014
TO: Advocates for Better Community Development (ABCD)
c/o Mr. Babak Naficy
1504 Marsh Street
San Luis,Obispo, CA 93401
Palm Springs Promenade, LLC
c/o Mr. John Wessman
555 S. Sunrise Way, Suite 200
Palm Springs, CA 92264
RE: Appeal of 9/10/2014 Planning Commission Decision on Case No. 3.3606 MAJ
Major Architectural Application for Developing Block B of the Downtown
Renovation Project located at the Northwest Corner of North Palm Canyon
Drive and New Main Street
Mr. Naficy and Mr. Wessman,
This letter serves as notice that the subject appeal has been scheduled for review by the
City Council at the regular meeting of Wednesday, October 15, 2014. The meeting
begins at 6:00 p.m. and will be held in the Council Chamber at City Hall,
3200 E. Tahquitz Canyon Way. A staff report on the matter will be forwarded to you
approximately five (5) days prior to the hearing.
Please feel free to contact me at (760) 323-8204 if you have any questions.
Sincerely,
James Thompson
City Clerk
cc: Planning Department
Post Office Box 2743 9 Palm Springs, California 92263-2743 50
Kathie Hart
From: webcustomerservice@ontrac.com
Sent: Thursday, October 02, 2014 11:50 AM
To: Kathie Hart
Subject: OnTrac Package Delivery Confirmation: C11332500020029
Hello,
This is an automated email response from OnTrac. The package tracking number C11332500020029 has been confirmed
as delivered.
Delivery Name : PALM SPRINGS PROMENADE, LLC POD Signature : lizett Delivery Time : 10/02/2014 11:47 AM
Status Code : DELIVERED
Reference : CITY CLERK
For more information please visit us at our website at http://www.ontrac.com or call us at 800-334-5000.
Thank you for using OnTrac!
51
Kathie Hart
From: webcustomerservice@ontrac.com
Sent: Thursday, October 02, 2014 3:05 PM
To: Kathie Hart
Subject: OnTrac Package Delivery Confirmation: C11332500020011
Hello,
This is an automated email response from OnTrac. The package tracking number C11332500020011 has been confirmed
as delivered.
Delivery Name : ABCD
POD Signature : bob
Delivery Time : 10/02/2014 03:03 PM
Status Code : DELIVERED
Reference : CITY CLERK
For more information please visit us at our website at http://www.ontrac.com or call us at 800-334-5000.
Thank you for using OnTrac!
52
NOTIFICATION OF APPEAL
CITY COUNCIL
CITY OF PALM SPRINGS
APPEAL OF CASE 3.3606 MAJ (MAJOR ARCHITECTURAL APPLICATION)
BLOCK "B" OF THE DOWNTOWN PALM SPRINGS RENOVATION PROJECT
NORTHWEST CORNER OF (NEW) MAIN STREET AND NORTH PALM CANYON DRIVE
NOTICE IS HEREBY GIVEN that the City Council of the City of Palm Springs, California, will
hear an appeal at its meeting of October 15, 2014. The City Council meeting begins at 6:00
p.m., in the Council Chamber at City Hall, 3200 East Tahquitz Canyon Way, Palm Springs.
The purpose is to consider an appeal of the September 10, 2014, Planning Commission's
decision regarding a Major Architectural Application to construct a two-story commercial building
at the northwest corner of (new) Main Street and North Palm Canyon Drive, Zone CBD. The
project proponent is Palm Springs Promenade, LLC. The appellant is Advocates for Better
Community Development (ABCD).
ENVIRONMENTAL DETERMINATION: Review of this Major Architectural Application
(Case No. 3.3606-MAJ) is within the scope of the Specific Plan EIR, as supplemented by the
subsequent Addendums, and none of the circumstances triggering further environmental review
have occurred since the adoption of the Addendums. Thus, no further environmental review is
required. (Public Resources Code § 21166; California Code of Regulations § 15162.)
REVIEW OF PROJECT INFORMATION: The staff report and other supporting documents
regarding this are available for public review at City Hall from 8:00 a.m. to 6:00 p.m., Monday
through Thursday. Please contact the Office of the City Clerk at (760) 323-8204 if you would
like to schedule an appointment to review these documents.
COMMENTS: Response to this notice may be made verbally at the appeal hearing and/or in
writing before the hearing. Written comments may be made to the City Council by letter (for mail
or hand delivery) to:
James Thompson, City Clerk
3200 E. Tahquitz Canyon Way
Palm Springs, CA 92262
Any challenge of the proposed project in court may be limited to raising only those issues raised
at the public hearing described in this notice, or in written correspondence delivered to the City
Clerk at, or prior to, the hearing. (Government Code Section 65009(b)(2)).
An opportunity will be given at said hearing for all interested persons to be heard. Questions
regarding this case may be directed to David Newell, Associate Planner, Planning Services
Department, at (760) 323-8245.
Si necesita ayuda con esta carta, por favor Ilame a la Ciudad de Palm Springs y puede hablar
con Nadine Fiegertelefono (760) 323-8245.
/'James Thompson, City Clerk
53
•OFPPIM SnP,y N
Department of Planning Services wE
N Vicinity Map
<„ea� 5
O
o AMADO RD
0
CU
COD
I -
z
o
z ANDREASRD Ra , _._.
U O
�. .. COD '.._. a�a _. Q
COD 0. a _.. Z
020 .... cc......... ........
tW� O
7 ....... _. COD Z
PD
TAHQUITZ DR
Legend c a U.
® Site J Oi _.... CU
O 50011 Site Radius = ff
R3 COD U RA
Zoning 2
W _J COD
--. Parcels m 14
CL
CITY OF PALM SPRINGS
CASE NO: 3.3605 MAJ (Appeal) DESCRIPTION:
An appeal of the Planning Commission decision
APPELLANT: Advocates for Better regarding a Major Architectural Application to
Community construct a two-story building at the northwest
Development (ABCD) corner of new "Main Street" and North Palm
Canyon Drive, Block "B" of the Museum Market
APPLICANT: Palm Springs Plaza Specific Plan, Zone CBD, Section 15.
Promenade, LLC 54
CITY OF PALM SPRINGS
NOTIFICATION OF APPEAL
oM'~u
Date: October 15, 2014
Subject: APPEAL OF CASE 3.3606 MAJ, MAJOR ARCHITECTURAL
APPLICATION, BLOCK "B" OF THE DOWNTOWN PALM SPRINGS
RENOVATION PROJECT, NORTHWEST CORNER OF (NEW) MAIN
STREET AND NORTH PALM CANYON DRIVE
AFFIDAVIT OF POSTING
I, Kathie Hart, MMC, Chief Deputy City Clerk, of the City of Palm Springs, California, do
hereby certify that a copy of the attached Notice of Public Hearing was posted at City
Hall, 3200 E. Tahquitz Canyon Drive, on the exterior legal notice posting board, and in
the Office of the City Clerk on October 6, 2014.
1 declare under penalty of perjury that the foregoing is true and correct.
�l"a,Aa
Kathie Hart, MMC
Chief Deputy City Clerk
AFFIDAVIT OF MAILING
I, Kathie Hart, MMC, Chief Deputy City Clerk, of the City of Palm Springs, California, do
hereby certify that a copy of the attached Notice of Public Hearing was mailed to each
and every person on the attached list on October 6, 2014, in a sealed envelope, with
postage prepaid, and depositing same in the U.S. Mail at Palm Springs, California.
(70 notices)
14dre(cla`re under penalty of perjury that the foregoing is true and correct.
No
Kathie Hart, MMC
Chief Deputy City Clerk
55
SOUTHERN CALIFORNIA EDISON CO RETTEW,JOEL Current Occupant
513-091-026 513-094-009 513-094-009
PO BOX 800 10424 BROOKSHIRE AVE 201 N INDIAN CANYON DR
ROSEMEAD CA 91770-0800 DOWNEY CA 90241-2609 PALM SPRINGS CA 92262-6424
G&W LEE INVESTMENT CORP Current Occupant SIMMONS, LORI LEE
513-091-005 513-091-005 513-091-008
303 W PALM DR 226 N PALM CANYON DR 939 N CAMINO CONDOR
ARCADIA CA 91007-8240 PALM SPRINGS CA 92262-5510 PALM SPRINGS CA 92262-5926
Current Occupant CITY OF PALM SPRINGS CITY OF PALM SPRINGS
513-091-008 513-560-019 513-091-024
200 N PALM CANYON DR 3200 E TAHQUITZ CANYON WAY PO BOX 2743
PALM SPRINGS CA 92262-5510 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92263-2743
CITY OF PALM SPRINGS CITY OF PALM SPRINGS NOAH,JONATHAN
513-091-023 513-091-022 513-091-010
PO BOX 2743 PO BOX 2743 1138 S LA CIENEGA BLVD APT 10
PALM SPRINGS CA 92263-2743 PALM SPRINGS CA 92263-2743 LOS ANGELES CA 90035-5900
Current Occupant GOLDRING,JUDY J Current Occupant
513-091-010 513-091-011 513-091-011
234 N PALM CANYON DR 1454 E GEM CIR 238 N PALM CANYON DR
PALM SPRINGS CA 92262-5510 PALM SPRINGS CA 92262-2353 PALM SPRINGS CA 92262-5510
CITY OF PALM SPRINGS PROP, MCB Current Occupant
513-091-025 513-091-012 513.091-012
PO BOX 2743 448 E 4TH ST 254 N PALM CANYON DR
PALM SPRINGS CA 92263-2743 HINSDALE IL 60521-4661 PALM SPRINGS CA 92262-5510
CITY OF PALM SPRINGS SPRINGS, PALM PROMENADE SPRINGS, PALM PROMENADE
513-560-012 513-560-011 513-560-018
3200 E TAHQUITZ CANYON WAY 555 S SUNRISE WAY STE 200 555 S SUNRISE WAY STE 200
PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92264-7894
SPRINGS, PALM PROMENADE CITY OF PALM SPRINGS CITY OF PALM SPRINGS
513-560-021 513-560-020 513-560-017
555 S SUNRISE WAY STE 200 3200 E TAHQUITZ CANYON WAY 3200 E TAHQUITZ CANYON WAY
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92262-6959
SPRINGS,PALM PROMENADE REDEVELOPMENT AGENCY CITY OF Current Occupant
513-560-016 PALM SPRINGS 513-091-004
555 S SUNRISE WAY STE 200 513-091-004 261 N IND[AN CANYON DR
PALM SPRINGS CA 92264-7894 PO BOX 2743 PALM SPRINGS CA 92262-6424
PALM SPRINGS CA 92263-2743
CITY OF PALM SPRINGS HENRY,FRANK Current Occupant
513-091-021 513-091-020 513-091-020
PO BOX 2743 550 N CAHUILLA RD 266 N PALM CANYON DR
PALM SPRINGS CA 92263-2743 PALM SPRINGS CA 92262-5678 PALM SPRINGS CA 92262-5510
1� 1D rna%UA
HOTEL, RBD SPRINGS Current Occupant CITY OF PALM SPRINGS
513-560-005 513-560-005 513-560-013
3340 PLAYERS CLUB PKWY STE 200 285 N PALM CANYON DR 3200 E TAHQUITZ CANYON WAY
MEMPHIS IN 38125-8942 PALM SPRINGS CA 92262-5525 PALM SPRINGS CA 92262-6959
CITY OF PALM SPRINGS O DONNELL GOLF CLUB G&W LEE INVESTMENT CORP
513-070-010 009-603-086 513-091-018
PO BOX 2743 301 N BELARDO RD 303 W PALM DR
PALM SPRINGS CA 92263-2743 PALM SPRINGS CA 92262-5600 ARCADIA CA 91007-8240
Current Occupant BRACKEY, ROBERT L Current Occupant
513-091-018 513-094-003 513-094-003
120 E ANDREAS RD 80 ARLINGTON AVE E 201 N INDIAN CANYON DR#3
PALM SPRINGS CA 92262-5502 SAINT PAUL MN 55 1 1 7-4069 PALM SPRINGS CA 92262-6424
BRACKEY,ROBERT L Current Occupant BRACKEY,ROBERT L
513-094-004 513-094-004 513-094-007
80 ARLINGTON AVE E 201 N INDIAN CANYON DR#4 80 ARLINGTON AVE E
SAINT PAUL MN 5 5 1 1 7-4069 PALM SPRINGS CA 92262-6424 SAINT PAUL MN 55117.4069
Current Occupant BRACKEY, ROBERT L Current Occupant
513-094-007 513-094-008 513-094-008
201 N INDIAN CANYON DR#7 80 ARLINGTON AVE E 201 N INDIAN CANYON DR# 8
PALM SPRINGS CA 92262-6424 SAINT PAUL MN 55117-4069 PALM SPRINGS CA 92262-6424
BRACKEY,ROBERT L Current Occupant BRACKEY, ROBERT L
513-094-002 513-094-002 513-094-001
80 ARLINGTON AVE E 201 N INDIAN CANYON DR#2 80 ARLINGTON AVE E
SAINT PAUL MN 55117-4069 PALM SPRINGS CA 92262-6424 SAINT PAUL MN 55117-4069
Current Occupant BRACKEY,ROBERT L Current Occupant
513-094-001 513-094-006 513-094-006
201 N INDIAN CANYON DR# 1 80 ARLINGTON AVE E 201 N INDIAN CANYON DR#6
PALM SPRINGS CA 92262-6424 SAINT PAUL MN 55117-4069 PALM SPRINGS CA 92262-6424
BRACKEY, ROBERT L Current Occupant USA AGUA CALIENTE BAND OF,
513-094-005 513-094-005 CAHUILLA INDIANS
80 ARLINGTON AVE E 201 N INDIAN CANYON DR# 5 O B003
P
SAINT PAUL MN 5 5 1 1 7-4069 PALM SPRINGS CA 92262-6424 PO BOXX 2245
PALM SPRINGS CA 92263-2245
USA AGUA CALIENTE BAND OF, Current Occupant USA 508
CAHUILLA INDIANS 508-041-007 508-041-012
508-041-007 208 N PALM CANYON DR PO BOX 2245
PO BOX 2245 PALM SPRINGS CA 92262- PALM SPRINGS CA 92263-2245
PALM SPRINGS CA 92263-2245
Current Occupant CITY OF PALM SPRINGS CITY OF PALM SPRINGS
508-041-012 513-560-014 513-560-022
200 N PALM CANYON DR 3200 E TAHQUITZ CANYON WAY 3200 E TAHQUITZ CANYON WAY
PALM SPRINGS CA 92262-5510 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92262-6959
SPRINGS, PALM PROMENADE CITY OF PALM SPRINGS Current Occupant
513-560-015 513-560-002 513-560-002
555 S SUNRISE WAY STE 200 3200 E TAHQUITZ CANYON WAY 123 N PALM CANYON DR
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92262-5590
CITY OF PALM SPRINGS CITY OF PALM SPRINGS SPRINGS,PALM PROMENADE
513-560-027 513-560-029 513-560-028
3200 E TAHQUITZ CANYON WAY 3200 E TAHQUITZ CANYON WAY 555 S SUNRISE WAY STE 200
PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92264-7894
CITY OF PALM SPRINGS SPRINGS, PALM PROMENADE CITY OF PALM SPRINGS
513-560-033 513-560-030 513-560-031
3200 E TAHQUITZ CANYON WAY 555 S SUNRISE WAY STE 200 3200 E TAHQUITZ CANYON WAY
PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6959
SPRINGS,PALM PROMENADE PLAZA INVESTMENT INC Current Occupant
513-560-032 513-092-007 513-092-007
555 S SUNRISE WAY STE 200 115 S INDIAN AVE 196 N PALM CANYON DR
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262- PALM SPRINGS CA 92262-5504
Current Occupant WESSMAN, HOLDINGS Current Occupant
513-092-006 513-092-009 513-092-009
180 N PALM CANYON DR 555 S SUNRISE WAY STE 200 165 N INDIAN CANYON DR
PALM SPRINGS CA 92262-5504 PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6420
WESSMAN,HOLDINGS Current Occupant PROP,FRANK
513-092-010 513-092-010 513-092-005
555 S SUNRISE WAY STE 200 146 N PALM CANYON DR 550 N CAHUILLA RD
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-5504 PALM SPRINGS CA 92262-5678
Current Occupant WESSMAN, HOLDINGS Current Occupant
513-092-005 513-092-003 513-092-003
134 N PALM CANYON DR 555 S SUNRISE WAY STE 200 149 N INDIAN CANYON DR
PALM SPRINGS CA 92262- PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262.6420
SPRINGS, PALM PROMENADE CITY OF PALM SPRINGS SPRINGS,PALM PROMENADE
513-560-034 513-560-035 513-560-036
555 S SUNRISE WAY STE 200 3200 E TAHQUITZ CANYON WAY 555 S SUNRISE WAY STE 200
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92264-7894
BRANDENBURG,OASIS PLAZA Current Occupant PALM CORNER ASSOC
513-143-009 513-143-009 513-092-004
1122 WILLOW ST STE 200 101 S PALM CANYON DR 121 S PALM CANYON DR STE 216
SAN JOSE CA 95125-3103 PALM SPRINGS CA 92262-6303 PALM SPRINGS CA 92262-6378
Current Occupant CITY OF PALM SPRINGS CITY OF PALM SPRINGS
513-092-004 513-144-006 513-144-007
100 N PALM CANYON DR PO BOX 2743 PO BOX 2743
PALM SPRINGS CA 92262-5504 PALM SPRINGS CA 92263-2743 PALM SPRINGS CA 92263-2743
PLAZA, LAS FLORES Current Occupant AGUA CALIENTE SPA INC
513-144-001 513-144-001 009-601-686
555 S SUNRISE WAY STE 200 135 E TAHQUITZ CANYON WAY 901 E TAHQUITZ CANYON WAY
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6430 PALM SPRINGS CA 92262-6757
Current Occupant CITY OF PALM SPRINGS USA 508
009-601-686 513-560-026 508-053-003
100 N INDIAN CANYON DR 3200 E TAHQUITZ CANYON WAY 100 N INDIAN CANYON DR
PALM SPRINGS CA 92262-6414 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92262-6414
SPRINGS,PALM PROMENADE CITY OF PALM SPRINGS SPRINGS,PALM PROMENADE
513-560-023 513-560-024 513-560-010
555 S SUNRISE WAY STE 200 3200 E TAHQUITZ CANYON WAY 555 S SUNRISE WAY STE 200
PALM SPRINGS CA 92264-7894 PALM SPRINGS CA 92262-6959 PALM SPRINGS CA 92264-7894
SPRINGS, PALM PROMENADE
513-560-025
555 S SUNRISE WAY STE 200
PALM SPRINGS CA 92264.7894
Planning Commission Minutes
September 10,2014
1. vide new 3D exhibits for the south side of the building and podiums.
2. Pro additional details for the parking structure; the pedestrian access to Palm
Canyon d walkway around the parking structure with an exit onto Alejo Road
and Indian on.
3. The Engineering De ment to provide information regarding the angled parking
and two way streets on 'an Canyon.
4. How will the mechanical are a soundproof for the adjacent neighbors?
5. More details on the materials fo exterior of the building.
Motion: Commissioner Weremiuk, sec o ed by Vice-Chair Klatchko and
unanimously carried 5-0-2 on a roll call vote.
AYES: Commissioner Lowe, Commissioner Middleto Commissioner Weremiuk,
Vice-Chair Klatchko, Chair Hudson
ABSENT: Commissioner Calerdine, Commissioner Roberts
A break was taken at 3:36 pm.
The meeting resumed at 3:57 pm.
2B. PALM SPRINGS PROMENADE, LLC FOR AN UPDATE ON EXTERIOR
ELEVATIONS OF BLOCK A OF THE DOWNTOWN PALM SPRINGS
y RENOVATION PROJECT LOCATED AT THE NORTHWEST CORNER OF
ANDREAS ROAD AND PALM CANYON DRIVE, ZONE CBD (CASE 3.3605
MAJ). (DN)
2C. PALM SPRINGS PROMENADE, LLC FOR A REVISED ARCHITECTURAL
APPLICATION TO CONSTRUCT A TWO-STORY COMMERCIAL BUILDING ON
BLOCK B OF THE DOWNTOWN PALM SPRINGS RENOVATION PROJECT
LOCATED AT THE SOUTHWEST CORNER OF ANDREAS ROAD AND PALM
CANYON DRIVE, ZONE CBD (CASE 3.3606 MAJ). (DN)
Interim Director Evans provided background information for Building A. Mr. Evans
reported that Building B is the middle building that is fully approved as a single-story
building with the exception of bringing back architectural details for the Commission. He
stated that the applicant has submitted the revised drawings, a new two-story building
and an alternate proposal for this site.
Associate Planner Newell presented the proposed projects as outlined in the staff
report.
Chair Hudson opened the public comment portion of the meeting:
5
G6
Planning Commission Minutes
September 10,2014
JOHN WESSMAN, applicant, explained the overall project and the open-space. He
requested the opportunity to provide an alternate plan for Block B and does not want to
give up approvals he already has. He has worked very hard to move this project forward
and has signed leases with major tenants and will accrue large penalties if project is
delayed.
CHRIS PARDO, Chris Pardo Design, provided an overview of Block A and the new
proposed Block B. He said the landscape is a concept in general. Mr. Pardo described
the proposed new walkways, railings, the element fins, materials, building height, sun
shade study, balcony railings and planter features.
With no other appearances coming forward public comments was closed.
The Commission requested clarification and/or commented on:
-The location of the fin element for Building A seems to divide the the building in half;
suggested moving it closer to the end of the building.
-The connection between A & B is very solid; however, the connection between B & C
looks heavy with lighter architecture.
JOHN WESSMAN explained that whole idea from the beginning is these buildings
would be built at different times and not look all the same. It is downtown and not a mall;
does not have a problem moving the fin by one bay.
COMMISSIONER MIDDLETON said that although the process has been very difficult
progress has been made. She noted that she was unimpressed with the original
Building B; with the new renderings the new roof lines draw Block A and C together
more nicely.
JOHN WESSMAN commented that they have given the Hyatt an easement to
incorporate into the project. The Hyatt will bring it forth for approval. Mr. Wessman
clarified that the landscaping will be submitted at a later time to the Commission.
ACTION: Determine that the revised exterior elevations fulfill Condition of Approval No.
10 of Planning Commission Resolution No. 6412, as amended:
-The fin be moved one bay to the north and the panel is expanded one additional bay.
Motion Vice-Chair Klatchko, seconded by Commissioner Lowe and unanimously
carried "-2 on a roll call vote.
AYES: Commissioner Lowe, Commissioner Middleton, Commissioner Weremiuk,
Vice-Chair Klatchko, Chair Hudson
6 57
Planning Commission Minutes
September 10, 2014
ABSENT: Commissioner Calerdine, Commissioner Roberts
ACTION: Approve Bock B, as presented with the condition that the obscured glass is
not backlit.
Motion: Commissioner Weremiuk, seconded by Commissioner Middleton and
unanimously carried 5-0-2 on a roll call vote.
AYES: Commissioner Lowe, Commissioner Middleton, Commissioner Weremiuk,
Vice-Chair Klatchko, Chair Hudson
ABSENT: Commissioner Calerdine, Commissioner Roberts
Vice-Chair Klatchko thanked Mr. Evans for his assistance during the interim pen
PLANNING DIRECTOR'S REPORT:
Interim Director Evans provided background information on the or nal intent of a final
Planned Development District for architecture.
ADJOURNMENT:
The Planning Commission adjourned at 5:09 pm Wednesday, September 24, 2014,
at 1:30 pm, City Hall, Council Chamber, 3200 t Tahquitz Canyon Way,
Douglas Evans
Interim Director of Planning Services
58
;O�pPLM Spy
iy
G+
U N
a a
`0 Planning Commission Staff Report
UFOit�
DATE: September 10, 2014
SUBJECT: PALM SPRINGS PROMENADE, LLC FOR A REVISED
ARCHITECTURAL APPLICATION TO CONSTRUCT A TWO-STORY
COMMERCIAL BUILDING ON BLOCK B OF THE DOWNTOWN
PALM SPRINGS RENOVATION PROJECT LOCATED AT THE
SOUTHWEST CORNER OF ANDREAS ROAD AND PALM CANYON
DRIVE, ZONE CBD (CASE 3.3606 MAJ).
FROM: Department of Planning Services
SUMMARY
The Planning Commission will review a revised Major Architectural application for the
development of block "B" within the downtown renovation project. The applicant
proposes a new two-story commercial building with ground floor retail / restaurants and
second floor offices. Plans are being prepared and will be presented at next week's
Architectural Advisory Committee and Planning Commission meetings.
RECOMMENDATION:
Review revised plans and if desired approve, subject to conditions.
ISSUES:
• Staff analysis of plans to be completed once submitted by applicant
BACKGROUND:
Specific Plan Yes Museum Market Specific Plan
Design Plan Yes Museum Market Specific Plan
Airport Overlay None
Indian Land None
59
Planning Commission Staff Report
September 10,2014--Page 2
Case 3.3606 MAJ—Downtown Palm Springs Renovation Project, Block B
Dec. 2, 2009 The City Council made findings, adopted a Mitigation Monitoring and
Reporting Program, adopted a Statement of Overriding
Considerations, and certified the Museum Market Specific Plan
Environmental Impact Report ("Specific Plan EIR") and adopted
Ordinance 1764, thereby approving the Museum Market Plaza Speck
Plan. The Specific Plan covers the design guidelines and development
standards for the area commonly known as the Desert Fashion Plaza.
Sept. 29, 2011 The City and Palm Springs Promenade, LLC, entered into a Project
Financing Agreement applicable to the financing, development,
redevelopment, creation and refurbishment of public and private
improvements within the Specific Plan area (the "Agreement"). The
Agreement included, among other things, a Site Plan and Project
Description depicting the proposed improvements.
Oct. 17, 2012 The City Council approved Amendment No. 2 to the Project Financing
Agreement between the City and Palm Springs Promenade, LLC (the
"Amendment'). The Amendment included an Updated Site Plan and
"Updates to Project Description" reflecting modifications to the
proposed improvements originally approved in the Agreement. The
Amendment provided that the Updated Site Plan and Updates to
Project Description amended and superseded the original Site Plan
and Project Description, respectively, in the Agreement. On October
17, 2012, the City Council also conducted a conformity review of the
project described in the Amendment, as allowed by the Museum
Market Plaza Specific Plan, and concluded that the project conformed
to the policies and objectives of the Specific Plan. In support of these
actions, the City Council adopted an Addendum to the Specific Plan
EIR pursuant to the California Environmental Quality Act("CEQA").
The City Council found that the proposed project described in the
Amendment was within the scope of the Specific Plan EIR, and, based
on the Specific Plan EIR and Addendum, found that no further
environmental review was required. (Public Resources Code § 21166;
California Code of Regulations, Title 14, §§ 15162, 15164.
Dec. 5, 2012 The Planning Commission adopted resolutions recommending the
Tentative Parcel Map and approving the three Major Architectural
Approvals and the Planned Development District permit.
Dec. 6, 2012 The City received Counclimember request to review the Planning
Commission actions on the project.
Dec. 19, 2012 The City Council approved the following applications as they relate to
Downtown Palm Springs Project:
• Tentative Tract Map 36446 to subdivide approx. 13.57 acres
into 14 parcels for development and four lots for public
infrastructure (Resolution 23226)
• Planned Development District for a hotel with approximately 185
60
Planning Commission Staff Report
September 10, 2014—Page 3
Case 3.3606 MAJ—Downtown Palm Springs Renovation Project, Block B
rooms, restaurants, meeting rooms, retail uses and ancillary
uses on Block C (Resolution 23270)
• Major Architectural Applications as they relate to development
of:
o Block A (Resolution 23267)
o Block B (Resolution 23268)
o Block C Resolution 23269
Feb. 13, 2013 The Planning Commission accepted the redesign of the facade and
materials for the proposed hotel located on block C-1 with the following
recommendations:
-A stronger emphasis be given to the landscape design.
-A more integrated attitude about the public art component.
-The design team to propose the colors for the building.
Mar. 6, 2014 The City Council approved the revised hotel elevations and determined
Condition of Approval No.1 of Resolution 23270 has been satisfied.
May 28, 2014 The Planning Commission reviewed Block C elevations and provided
comments to City Council.
June 18, 2014 The City Council reviewed and approved Block C elevations.
June 23, 2014 The Architectural Advisory Committee (AAC) reviewed and tabled
architectural applications to develop Block A with a three-story building
and Block B with a one-story building.
June 25, 2014 The Planning Commission approved Major Architectural applications
for the development of Block A with a three-story building and Block B
with a one-story building.
Aug. 27, 2014 The Planning Commission reviewed revised elevations for the
proposed three-story building on Block A and continued the item with
direction to the applicant to provide additional exhibits and three-
dimensional simulations showing the building within the overall
downtown prolect.
Sept. 8, 2014 I The AAC will review the proposed revisions to the three-story building
on Block A and the revised application for a two-story building on Block
B.
BACKGROUND AND SETTING
Previously referred to as the Museum Market Plaza, the Downtown Palm Springs
Project is located in the heart of the City's Business District, specifically at the northwest
corner of North Palm Canyon Drive and West Tahquitz Canyon Way. The irregularly
shaped property is bounded by Belardo Road to the north, Tahquitz Canyon Way to the
south, Museum Drive to the west and North Palm Canyon Drive to the east.
The original Desert Fashion Plaza was built in the late 1960's; since then there have
been several renovations and additions especially around the 1980's. The entire project
site has been razed with the exception of a majority of the parking structure.
61
Planning Commission Staff Report
September 10,2014-Page 4
Case 3.3606 MAJ-Downtown Palm Springs Renovation Project, Block B
PROJECT DESCRIPTION AND ANALYSIS:
At its public hearing of December 19, 2012, the City Council reviewed and approved the
Downtown Palm Springs Project consisting of a tentative tract map (TTM36446), three
Major Architectural applications, and a Planned Development District application for a
hotel in excess of sixty (60) feet. The three Architectural applications included Blocks A,
B and C.
On June 25, 2014, the Planning Commission approved a Major Architectural application
for a one-story retail building on Block B with direction to modify and enhance the
building design. The applicant is now seeking approval of a revised Major Architectural
application with an entirely redesigned building for Block B.
The project has been described by the applicant as follows:
• Ground floor footprint generally remains the same (approx. 17,450-square feet)
as the project approved by Planning Commission on June 25, 2014
• Second story office added
• Building height to range from 27 to 37 feet in height
• Setbacks to be consistent with previous approval
Based on the above, the project analysis will change slightly from that which was
completed for the building approved by the Planning Commission on June 25th (see
attached report).
The revised building will be reviewed by the Architectural Advisory Committee on
September 8, 2014. A summary on the Committee's discussion and action will be
provided to the Planning Commission.
Should the Planning Commission decide to approve the revised project, staff has
attached the prior approval resolution (Planning Commission Resolution No. 6413) to
this report for reference as most conditions would be the same with some minor
adjustments. A complete analysis and draft resolution will be provided to the
Commission prior to the meeting on September 10th.
avid A. Qewell Douglas RAvans
Associate Planner Interim Director of Planning Services
Attachment:
1. 6/25/2014 Planning Commission Meeting Minutes (excerpt)
2. 6/25/2014 Planning Commission Staff Report (excerpt)
62
Piartrting Commtsslon Minutes
June 25,2014
ION: Approve, subject to conditions, as amended:
• 11 meet all requirements set by City Engineer.
• Mesquite to shield adjoining 2353 Cantina Way.
• Prop e be continuously maintained.
Motion: Comma r Klatchko, seconded by Commissioner Lowe and j
unanimously carrie roil call vote.
AYES: Commissioner 'ne, Commissioner Klatchko, Commissioner Lowe,
Commissioner R ommissioner Weremiuk, Vice Chair Hudson and
Chair Donenfeld
AS. MARK TEMPLE, OWNER, FOR OR ARCHITECTURAL APPLICATION
FOR A NEW 3,602-SQUARE HOUSE ON A MODIFICATION
REQUESTING AN INCREASE IN BUIL HEIGHT AT OCATED AT 771 LA
MIRADA DRIVE, ZONE R-7 A, SECTION ASE 3,3733 MAJ AND 7.1423
fI AMM) (GNU
I ASSOCIATE PLANNER.NEWELL presented the pro as outlined in the
staff report
ACTION:Approve, subject to conditions.
Motion: Commissioner Roberts,seconded by Commissioner Weremiuk.
unanimously carried on a roll can vote.
AYES: Commissioner Calerdine, Commissioner Matchko, Commissioner
Commissioner Roberts, Commissioner Weremiuk, Vice Chair Hudson and
Chair DonAnfairt
4C. PALM SPRINGS PROMENADE, LLC FOR ARCHITECTURAL REVIEW
OF BLOCKS A AND B OF THE DOWNTOWN PALM SPRINGS
RENOVATION PROJECT LOCATED AT THE NORTHWEST AND
SOUTHWEST CORNER OF ANDREAS ROAD AND PALM CANYON
DRIVE, RESPECTIVELY; ZONE CBD. (CASE 3.3605 MAJ AND 3.3806
MAJ)- (DN)
DIRECTOR WHEELER presented an overview on the proposed project.
COMMISSIONER CALERDINE questioned Block A parking access. Behind Block A Is
that pedestrian only? Where willthe loading actually occur?
ASSOCIATE PLANNER NEWELL addressed the access points.
g 63
Planning Commission Minutes
Jurre 26,2D14
VICE-CHAIR HUDSON asked if there Is language in the Specific Plan that requires 313
Images, to see them together.
COMMISSIONER LOWS questioned if there would be a model. He would like a model
for such a huge project, i
COMMISSIONER ROBERTS ex
pressed frustration in how it will work together.
COMMISSIONER KLATCHKO said he attended the AAC meeting when this project was
presented and noted that they received the staff report last minute and were not
prepared. He reported the comments from the AAC: they felt pressure earlier, colors
did not match board, shading concern and floor plan is Block B may change regarding
tenants.
ASSOCIATE PLANNER NEWELL distributed a perspective rendering of the entire
project
EMILY HEMPHILL, LEGAL REPRESENTATION FOR THE APPLICANT, reiterated that
the project and part of the financing agreement will be reviewed by the City Council in.
July. She said that it Is very critical of moving forward through the,Planning process to
show to prospective tenants.
MICHAEL BRAUN, APPLICANT, provided details pertaining to the project
VICE-CHAIR HUDSON commented on the following: Block A is truly architecture;
Block B has fallen apart; certain portions of the buildings are designed one way and the
other part is being designed a different way. It's mundane and not up to the high
standard of the development
COMMISSIONER WEREMIUK asked what about the width of Market Street and type of
materials. She would like 4' continuous shade around the building and questioned If
Block B Includes storefronts?She likes Block A, however, colors feel heavy.
MICHAEL BRAUN said they will oertainly have colors return to the Planning
Commission,
COMMISSIONER WEREMIUK said attention to detail in rear is important. Market
Street and Paseo must be as user friendly as Palm Canyon.
COMMISSIONER ROBERTS said he met with Michael Braun earlier this week and
thinks Block A is heavy and "blocky". He would Ike to move this forward. Block B
needs to connect to other buildings architecturally. He suggested moving It forward and
Possibly have It come back with a,subcommittee for design, material and color review.
He said the Specific Plan is very clear on the requirements. Cooling systems are not
shown. He sees miles and miles of concrete..Move this forward and come back with
beCer design.
10 64
I
i
Planning Commisslon Minutes
June 2b,2014
i
CHAIR DONENF'ELD.said some basic elements are very important esp. shading, user-
friendly and comfortable amenities. The colors shown are very dark.'
MICHAEL BRAUN talked about the development which will include a misting system,
umbrellas and street furniture, water features and free-Wi-Fi. This will return along with
the landscape plan.
VICE-CHAIR HUDSON said it will take much more than colors or materials to make this
a better building. He does not feel confident with this project and it does not incorporate
any solar elements.
ACTION:Approve, subject to conditions, as amended:
• Shading and cooling plan to return.
• Review lighter color palette and materials to return.
• Improve architectural style for Block B
• Passive energy conservation to return.
• Condition ENG#36 to be removed and in ENG63 remove reference to Market St.
and ENG82#2 change north to south and add to last sentence*to be relocated
north'
COMMISSIONER WEREMIUK proposed a substitutes motion:
ACTION: Applicant to move forward;to review colors and materials, shading and
misting system.
COMMISSIONER CALERDINE prefers strong statements In order to move forward,
COMMISSIONER ROBERTS said this convoluted and is not about the building size,
COMMISSIONER WEREMIUK withdrew her motion.
-.COMMISSIONER ROBERTS proposed an amendment to the motion:
• Redesign Block B within current size.
• Adhere to guidelines
• Passive energy for shading and solar to return.
• . Building A-different colors and materials.
COMMISSIONER KLATCHKO said not a redesign and proposed an amendment:
• When tenants return shade,�solar, misting and landscaping must be a part of
proposal submitted.
65
Planning Commission Minutes
June 26,2014
i
COMMISSIONER LOWE agreed with Vice-Chair Hudson and does not think its right to j
move forward when so many items are not agreed upon.
COMMISSIONER CALERDINE proposed an amendment to his motion: Improve the I
architectural style for Block B.Accepted by CHAIR DONENFELD.
i
COMMISSIONER WEREMIUK said come back with landscape plan of Paseo.
COMMISSIONER ROBERTS said architectural style needs to be approved separately.
Motion: Commissioner Calerdine,seconded by Chair Donenfeld and carried 64-0
on a roll call vote.
AYES: Commissioner Calerdine, Commissioner Matchko, Commissioner Lowe, '
Commissioner Roberts, Commissioner Weremiuk and Chair Donenfeld i
NOES: Vice Chair Hudson
A recess was taken at 5:28 pm.
The meeting reconvened at 5:34 prn.
3 FO
PALM SPRINGS ZONING: CODE (PSZC) SECTION 94,02.01 RELATIN
LAND USE PERMITS. (CASE S.1343 ZTA) (M )
COMMISSIONER ROBERTS noted a conflict of interest.due to prope rshlp In
the area and would be abstaining from the discussion and vote. eft the Council
-Chamber.
DIRECTOR WHEELER presented the proposed project [nod in the staff report
and discussed the administrative procedure.
JOHN RAYMOND, DIRECTOR OF COMMU AND REDEVELOPMENT, addressed
-the boundaries of the proposed amend the opportunities for this type of
development.
ACTION: Recommend app the City Council.
Motion: Commissio eremiuk, seconded by Commissioner Lowe and carried on a
roll call vote.
AYES: ommissioner Calerdine, Commissioner Klatchko, Commissioner
Lowe, Commissioner Weremiuk, Vice Chair Hudson and Chair Donenfeld
N: Commissioner Roberts
Commissioner Roberts re-entered the Council Chamber at 5:48 pm.
12
66
......... _.
��f p ALAI gpp
ig
a a
v' a
�. r .• Planning Commission Staff Report
cq<rFoad�P
DATE: June 25, 2014
SUBJECT. PALM SPRINGS PROMENADE, LLC FOR ARCHITECTURAL REVIEW
OF BLOCKS A AND B OF THE DOWNTOWN PALM SPRINGS
RENOVATION PROJECT LOCATED AT THE NORTHWEST AND
SOUTHWEST CORNER OF ANDREAS ROAD AND PALM CANYON
DRIVE, RESPECTIVELY; ZONE CBD. (CASE 3.3605 MAJ AND 3.3606
MAJ).
FROM: Department of Planning Services
SUMMARY
The Planning Commission will review two architectural applications for the development
of two downtown blocks, known as Blocks W and "B". Block A is proposed to be three-
stoy building with ground floor retail / restaurants and second and third floor offices.
Block B is proposed to be single-story retail.
RECOMMENDATION:
Approve, subject to conditions.
ISSUES:
• Minimal sidewalk shading proposed. Additional sidewalk shading should be
considered via extended overhangs or other means.
BACKGROUND:
T! rt
n Yes Museum Market S cfflc Plan
Yes Museum Market Specific Plan
ta None
None
67
_............_.......__............____.._------__._�.----______m.__..__._ _____-_
Planning Commission Staff Report
June 25,2014-Page 2
Case 3.3605 MAJ and 3.3606 MAJ-Downtown Palm Springs Redevelopment Project, Blocks A and B
Weseas
troris tti..�D:a><xn ` �,a1rar a sue" .�t��s� �' . ,Dec. 2, 2009 Council made findings, adopted a Mitigation Monitoring andProgram, adopted a Statement of Overriding Considerations, andhe Museum Market Specific Plen Environmental Impact ReportPlan EIR") and adopted Ordinance 1764, thereby approving thearket Plaza Specific Plan. The Specific Plan covers the design and development standards for the area commonly known as theshion Plaza.
Sept.29, 2011 The City and Palm Springs Promenade, LLC, entered Into a Project Financing
Agreement applicable to the financing, development, redevelopment, creation
- and refurbishment of public and private improvements within the Specific Plan
area (the "Agreement"). The Agreement included, among other things, a Site
Plan and Project Description cinnic.4im the proposed Improvements.
Oct. 17,2012 The City Council approved Amendment No. 2 .to, the Project Financing
Agreement between the City and Palm Springs Promenade, LLC (the
"Amendment"). The Amendment included an Updated Site Plan and
"Updates to Project Description" reflecting modifications to the proposed
Improvements originally approved in the Agreement The Amendment
provided that the Updated Site Plan and Updates to Project Description
amended and superseded the original Site Plan and Project Description,
respectively, in the Agreement On October 17, 2012, the City Council also
conducted a conformity review of the project described in the Amendment, as
allowed by the Museum Market Plaza Specific Plan, and concluded that the
project conformed to the policies and objectives of the Specific Plan. In
support of these actions, the City Council adopted an Addendum to the
Specific Plan EIR pursuant to the California Environmental Quality Act
("CEQA"). The City Council found that the proposed project described in the
Amendment was within the scope of the Specific Plan EIR, and, based on the
Specific Plan EIR and Addendum, found that no further environmental review
was required. (Public Resources Code g 21166; California Code of
R ulations, Title 14, 15162, 15164.
Dec. 5, 2012 The Planning Commission adopted resolutions recommending the Tentative
Parcel Map and approving the three Major Architectural Approvals and the
Planned Develo ment.District permit
Dec. 6, 2012 The City received Councilmember request to review the Planning Commission
actions on the project.
Dec. 19, 2012 The City Council approved the following applications as they relate to
Downtown Palm Springs Project:
• Tentative Tract Map 36446 to subdivide approx. 13.57 acres into 14
parcels for development and four lots for public infrastructure
(Resolution 23226)
• Major Architectural Applications as they relate to development of:
o Block A(Resolution 23267)
o Block B (Resolution 23268)
o Block C Resolution 23269
Feb. 13, 2013 The Planning Commission accepted the redesign of the facade and materials
for the proposed hotel located on block C-1 with the followin
68
Planning Commission Staff Report
June 25, 2014—Page 3
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project, Blocks A and B
recommendations:
-A stronger emphasis be given to the landscape design.
A more integrated attitude about the public art component.
-The design team to propose the colors for the building.
Mar.6, 2014 The City Council approved the revised hotel elevations and determined
Condition of Approval No.1 of Resolution 23270 has been satisfied.
May 28, 2014 The Planning Commission reviewed Block C elevations and provided
comments to City Council.
June 18, 2014 The City Council reviewed and approved Block C elevations.
June 23,2014 The Architectural Advisory Committee will review the proposed project. Staff
Will Drovida a recommendation summary to the Planning Commission.
BACKGROUND AND SETTING
Previously referred to as the Museum Market Plaza, the Downtown Palm Springs
Project is located in the heart of the City's Business District, specifically at the northwest
comer of North Palm Canyon Drive and West Tahquitz Canyon Way. The irregularly
shaped property Is bounded by Belardo Road to the north, Tahquitz Canyon Way to the
south, Museum Drive to the west and North Palm Canyon Drive to the east.
The original Desert Fashion Plaza was built in the late 1960's; since then there have
been several renovations and additions especially around the 1980's. The entire project
site has been razed with the exception of a majority of the parking structure.
.PROJECT DESCRIPTION AND ANALYSIS:
At its public hearing of December 19, 2012, the City Council reviewed and approved the
Downtown Palm Springs Project consisting of a tentative tract map (1TM36446), three
Major Architectural applications, and a Planned Development District application for a
hotel in excess of sixty(60)feet. The three Architectural applications included Blocks A,
B and C. The applicant Is seeking approval of revised applications for the Palm Canyon
Drive frontages of Blocks A and B.
Staff analyzed the current project against the General Plan, Specific Plan approved
Dec. 2, 2009 and Conformity Review approved on October 17 and December 19, 2012.
A description and analysis of each block is provided below.
BLOCK A
Located west of North Palm Canyon Drive, north of the new extension of Andreas Road,
south of the existing Hyatt Hotel, and east of the new Belardo Road extension, Block A
is proposed to be developed In two phases. Phase 1 is located on the east side of the
dividing pedestrian paseo which will extend from a new Hyatt Hotel entry / exit to the
intersection of Market Street and Andreas Road. Phase 2 is west of the pedestrian
paseo and will be submitted and reviewed at a later date.
69
Planning Commission Staff Report
June 25, 2014—Page 4
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Protect, Blooks A and B
This phase Includes a three-story commercial shell building used for retail, office and
restaurant space. The ground floor wi11 be roughly 16,468 sq. ft. and the second and
third floors will each be about 17,508 sq. ft. for a total building area of approximately
51,484 sq. ft.
BLOCK A— General Plan
CEO(Central Business District) Combination Yes
The CBD serves as the main activity center and cultural core of the of office and
community and, as such, theatres, museums, retail, and other retail uses
entertainment venues are encouraged here. Uses such as grocery stores, —1.7 FAR
hardware stores, and convenience or pharmacy stores that provide
services to the Downtown's residential population are also encouraged.
The Central Business District is subdivided into zones or areas that
provide for diversity in development standards and land use intensities.
The Downtown Central Core(roughly bounded by Amado Road,Tahqultz
Canyon Way, Museum Drive, and Indian Canyon Drive)and the Gateway
areas (at roughly the north and south ends of the CBD) may be
developed with a maximum FAR of 3.5. If projects in these areas provide
substantial public spaces or plazas, an FAR of up to 4.0 may be
developed upon approval of a Planned Development District or Spook
Plan.
BLOCK A—Develo ment Standards
Specific Plan 12/19/12 Current
Requirement Approval Proposal
Minimum Setbacks:
- Front Setback' or Street Side Setback(Feet)
• Palm Canyon Drive, west side 15 17 23
• All Other Streets (including Andreas) 10 12 19'-4" m
- Rear Setback(Feet) 0 0 17'-4"
-Side Yard Setback Feet 0 Not defined 17'-9"
Maximum Building Heigh (Feet)
- Building 60 20'-6" 53
- Permitted Projections 15 (and no 8 8 (and less than
more than 15% of roof
15%of roof) area
' Exceptions to the minimum setback requirements are listed under Section III-E.5 of the Museum Market
Speoffic Plan.
?'Building height shall be measured from the highest point of the building pad to the top of the roottine.
70
Planning Commission Staff Report
June 25,2014—Page 5
Case 3.3606 MAJ and 3.3606 MAJ--Downtown Palm Springs Redevelopment Project, Blocks A and B
Specific Plan 12/19/12 Current N
Requirement Approval Proposal
U
Minimum Building Height Stepbacks (Feet)
- Palm Canyon Drive
-0-30 Feet in Height 0 Height under Varies from 20
30 ft. to 25 from P/L
- Over 30 Feet In Height 20 N/A Varies from 23
to 25 from P/L
- Internal and Private Streets(including Andreas)
-0-30 Feet in Height 0 Height under 12 from P/L
-Over 30 Feet in Height 10 30 ft. 12 from P/L
Minimum Public/Common Area Open Space 10% 21.6% 44.6%
Maximum Building S uare Footage 220,000 52,507 51,484 RL
Maximum Building Mass Cubic Feet 2-10-0-0-10-00- 472,563 463 356
Projections Into the Right-of-Way(Feet)
- Awnings 10 None None
- Architectural features 10
- Arcades, trellis features and similar coverings Face of curb
- Balconies and terraces 6
Parking Requirements: (The PFA waives the 1 space/ 52,507 sq.ft. 51,484 sq. ft.
parking requirement as there is sufficient parking 325 sq. ft. requires 162 requires 158 ql
In the existin UG arkin . spaces spaces
Loadin Faculties Required Not defined On-street
Trash Enclosure Required Not defined Within Bldg.
Building Height Block A been modified from retaining and renovating the existing
building to demolishing existing and constructing a new building. The applicant has
proposed to follow the development standards of the spec plan. Based on the
specific plan, the project conforms. Furthermore, a table displaying building square
footage, mass (cubic square footage) and open space for all blocks within the
Downtown Palm Springs Project shows the proposal does not exceed that which was
previously approved (see attached).
BLOCK A—Architectural Review
The Palm Springs Zoning Code Section 94.04.00(D) provides guidelines for the
architectural review of development projects, with conformance evaluated based on the
following guidelines:
3 Stepbacks are defined as the horizontal distance a building face must be set back from the property line
at each given height The area required for a stepback can be used for balconies and terraces.Stepbacks
shall be measured from the faro of a structure to the property line at a 90 degree angle from the building
face.
71
Planning Commission Staff Report
June 25,2014--Page 6
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project,Blocks A and B
1. Site layout, orientation, location of structures and relationship to one
another and to open spaces and topography. Definition of pedestrian and
vehicular areas;i.e., sidewalks as distinct from parking lot areas;
The project proposes a new three-story building with pedestrian circulation
around entire building. Pedestrian pathways will be separated from
vehicular streets with curbs and landscape treatment. Pavers,
landscaping and sidewalk furniture will provide an enhanced experience
on the site. Sidewalks and other walkways are provided to accommodate
the change In topography across the site. Pedestrian access Is provided
to the underground parking via interior stairways and elevator.
Z Harmonious relationship with existing and proposed adjoining
developments and in the context of the Immediate neighborhood /
community, avoiding both excessive variety and monotonous repetition,
but allowing similarity of style, IF warranted;
The proposed structure will be lower in height than the existing hotel
located to the north but higher than the proposed an
to the south.
The proposed architecture is of a contemporary style consistent with
surrounding development, but introduces design elements, colors and
materials of a higher quality than the existing development In the vicinity.
The selection of design elements differs from those of the adjacent blocks
within the Museum Market Plaza Specific Plan area, yet they contribute to
the overall identity of an up-scale contemporary center.
3. Maximum height, area, setbacks and overall mass, as well as parts of any
structure (buildings, walls, screens, towers or signs) and effective
concealment of all mechanical equipment;
The proposed building's overall height will be fifty-three (53) feet, and
exterior elevations show projections at building edges. Portions of the
building wails will be.set back to provide greater outdoor access and
Interior I exterior shading. Parapets and other design elements will
provide screening of proposed rooftop equipment.
4. Building design, materials and colors to be sympathetic with desert
surroundings;
The building architecture is contemporary in style, with a color and
material palette that introduces muted desert colors, with limited use of
accent colors via metal, stone and glass.
72
Planning Goinmission Staff Report —
June 25,2014—Page 7
Case 3.3005 MAJ and 3.3606 MAJ-Downtown Palm Springs Redevelopment Project, Blocks A and B
6. Harmony of materials, colors and composition of those elements of a
structure, Including overhangs, roofs, and substructures which are visible
simultaneously;
The building architecture is contemporary in style, with a color and
material palette that Introduces muted desert colors, with limited use of
accent colors via metal, stone and glass. Covered walkways for outdoor
seating, pedestrian circulation and solar control are integrated into the
building design.
6. Consistency of composition and treatment;
The building design uses consistent forms and treatments across each
elevation. The contemporary elements interact with each other in a
consistent and rhythmic manner.
7. Location and type of planting, with regard for desert climate conditions.
Preservation of specimen and landmark trees upon a site, with proper
irrigation to insure maintenance of all plant materials;
Landscape plans have not been submitted at this time. Required review
at a later is Incorporated Into the attached conditions of approval.
8 Signs and graphics, as understood in architectural design including
materials and colors;
A sign program not been submitted to evaluate against this guideline and
recommendations for further review are incorporated into the attached
conditions of approval.
BLOCK B
-Located west of North Palm Canyon Drive, north of the New Main, south of the new
Andreas Road extension, and east of the new Belardo Road extension, Block B is also
proposed to be developed in two phases. Similar to Block A, this proposed phase
(Phase 1) includes development of the Palm Canyon Drive frontage between Andreas
Road, new Main Street and Market Street. Phase 2 is west of the Market Street and will
be submitted and reviewed at a later date.
The development consists of a one-story commercial shell building used for retail, office
and restaurant space. The building area will be approximately 17,000 sq. ft. in size.
73
Planning Commission Staff Report
June 25,2014—Page 8
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project,Blocks A and B
BLOCK B—General Plan
WEIZEN
COD(Central Business District) Retail and Yes
The CBD serves as the main activity center and cultural core of the commercial
oanmunhy and, as such, theatres, museums, retail, and other uses at
entertainment venues are encouraged here.Uses such as grocery stores, 0.6 FAR
hardware stores, and convenience or pharmacy stores that provide
services to the Downtown's residential population are also encouraged.
The Central Business District is subdivided into zones or areas that
provide for diversity in development standards and land use intensities.
The Downtown Central Core(roughly bounded by Amado Road, Tahqultz
Canyon Way, Museum Drive,and Indian Canyon Drive)and the Gateway
areas (at roughly the north and south ends of the CBD) may be
developed with a maximum FAR of 3.5. If projects in these areas provide
substantial public spaces or plazas, an FAR of up to 4.0 may be
developed upon approval of a Planned Development District or Specific
Plan.
BLOCK B— Development Standards
I
Specific Plan 12/19/12 Current
Requirement Approval Proposal
Minimum Setbacks:
- Front Setbacks or Street Side Setback(Feet)
• Palm Canyon Drive,west side 15 18 15 to 21
• All Other Streets
o New Main Street 12 14 12
o Andreas Road 12 15 13
Side Yards Feet 0 0 25
Maximum Building Heigh —(Feet) ,
-Building 16 38 20' to 28'-3"
Permitted Projections 15(and no 7 Not defined B
more than
Minimum Building Height Stepbacks (Feet} 15% of roc
=Palm Canyon Drive 10
4 Exceptions to the minimum setback requirements are listed under Section III-E.5 of the Museum Market
Specific Plan.
e Building height shall be measured from the highest point of the building pad to the top of the roofilne.
s Stepbacks are defined as the horizontal distance a building face must be set back from the property line
at each given height.The area required for a stepback can be used for balconies and terraces.Stepbacks
shall be measured from the face of a structure to the property line at a 90 degree angle from the building
face.
74
. Planning Commission Staff Report ~—�-.-- --�------- . -_ -._.-----��
June 25,2014-Page 9
Case 3.3605 MAJ and 3.3606 MAJ-Downtown Palm Springs Redevelopment Project, Blocks A and B
- 0-30 Feet In Height 0 Not defined Height under
30 ft.
-Over 30 Feet in Height 20 70 N/A
- Intemak and Private Streets
Andreas Road
-0-30 Feet in Height 0 0 Height under
30 ft.
-Over 30 Feet in Height 10 14 N/A
New Main
- 030 Feet in Height 0 0 Height under
30 ft.
- Over 30 Feet In Height 10 15 N/A
Minimum Public/Common Area Open Space 90% 33% (Blocks B 37.5%
&B-1
Maximum Building Square Footage 3,000 75,562 (Blocks 17,000
B & B-1
Maximum Building Mass Cubic Feet 27,000 301,203 153,000
Projections Into the Right-of--Way(Feet)
- Awnings 10 None None
- Architectural features 10
Arcades,trellis features and similar coverings Face of curb
- Balconies and terraces 6
Parking Requirements: 1 space/ 42,082 sq.ft. 17,000 sq. ft.
325 sq.ft. requires 129 requires 52
s aces s aces
Loading Facilities Required Not Defined On-street
Trash Enclosure Re uired Not Defined Within Bldg.
Building height, Open Space, Square Footage and Building Mass: The Specific Plan
envisioned Block B as a green space with few buildings, thus the high open space
requirements and minimal development standards for building. On October 17, 2012,
the City Council conducted a conformity review on the Downtown Palm Springs Project,
approved a proposal for the development of Block B, pursuant to Section V.2
"Conformity Renew Procedure"of the Specific Plan, and approved Amendment No. 2 to
the Project Financing Agreement which Included designation of Block E of the Specific
Plan as an Event Area, an open space, public recreation area. On this basis, the
Council approved the architectural application on 12/19/2012 as shown In the table
above. Since the proposal is consistent with these standards, the project is considered
conforming. Furthermore, a table displaying building square footage, mass (cubic
square footage) and open space for all blocks within the Downtown Palm Springs
Project shows the proposal does not exceed that which was previously approved (see
attached).
75
Planning Commission Staff Report
June 26, 2014—Page 10
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project, Blocks A and B
BLOCK B—Architectural Review
The Palm Springs Zoning Code Section 94.04.00(D) provides guidelines for the
architectural review of development projects, with conformance evaluated based on the
following guidelines:
I. Site layout, orientation, location of structures and relationship to one
another and to open spaces and topography. Definition of pedestrian and
vehicular areas;Le., sidewalks as distinct from parking lot areas;
The project proposes a new one-story building with pedestrian circulation-
around entire building. Pedestrian pathways will be separated from
vehicular streets with curbs and landscape treatment. Pavers, landscaping
and sidewalk furniture will provide an enhanced experience on the site.
Sidewalks and other walkways are provided to accommodate the change
In topography across the site.
2. Harmonious relationship with existing and proposed adjoining
developments and in the context of the immediate neighborhood /
community, avokfing both excessfve variety and monotonous repefftion,
but allowing similarity of style, if warranted,
The proposed structure will be lower than both buildings across streets to
the north and south. The varying structure height from 20 to 28 feet is
generally consistent with other structures in the downtown vicinity. The
proposed architecture is of a contemporary style consistent with
surrounding development, but introduces design elements, colors and
materials of a higher quality than the existing development in the vicinity.
The selection of design elements differs from those of the adjacent blocks
within the Museum Market Plaza Specific Plan area, yet they contribute to
the overall identity of an up-scale contemporary center.
3. Maximum height, area, setbacks and overall mass, as well as parts of any
structure (buildings, walls, screens, towers or signs) and effective
concealment of all mechanical equipment;
The proposed building's overall height will be twenty-eight (28) feet
consistent with the standards of the Specific Plan. The building has
varying roof heights along street frontage to break up massing. Parapets
and other design elements will provide screening of proposed rooftop
equipment.
4. Building design, materials and colors to be sympathetic with desert
surroundings;
76
__..._..__.-..__._ .............. ..................._..... ...... ... .. . .. _ ..... —
Planning Commission Staff Report
June 26, 2014--Page 11
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project, Blocks A and B
i
The building architecture is contemporary in style, with a color and
material palette that Introduces muted desert colors, with limited use of
accent colors via metal, stone and glass.
5. Harmony of materials, colors and compositon of those elements of a
structure, including overhangs, roofs, and substructures which are visible
simultaneously,•
The building architecture is contemporary in style, with a color and
material palette that introduces muted desert colors, with limited use of
accent colors via metal, stone and glass. Covered walkways for outdoor
seating, pedestrian circulation and solar control are integrated into the
building design.
6. Consistency of composition and treatment;
The building design uses forms and treatments across each tenant
elevations In a consistent and well composed manner. The contemporary
elements and planes are used around all sides of the building.
7. Location and type of planting, with regard for desert climate conditions.
Preservation of specimen and landmark trees upon a site, with proper
irrigation to insure maintenance of ali plant materials
Landscape plans have not been submitted at this time. Required review
at a later is incorporated into the attached conditions of approval.
8. Signs and graphics, as understood in architectural design Including
materials and colors;
A sign program not been submitted to evaluate against this guideline and
recommendations for further review are incorporated into the attached
conditions of approval.
'ENVIRONMENTAL DETERMINATION:
An Addendum to a Final Environmental Impact Report was approved by the City
Council on October 17, 2012. The City Council certified that the certified Specific Plan
EIR and the Addendum together are adequate to support approval of each component
of the proposed project as approved in the Amendment and any future discretionary
approvals needed to implement the project. The entitlements currently under
consideration by the Planning Commission simply implement the project approved in
the Amendment for CEQA purposes on October 17, 2012 No further environmental
77
Planning Commission Staff Repo ri T
June 25,2014—Page 11
Case 3.3605 MAJ and 3.3606 MAJ—Downtown Palm Springs Redevelopment Project,Blocks A and B
The building design uses forms and treatments across each tenant
elevations in a consistent and well composed manner. The contemporary
elements and planes are used around all sides of the building.
7. Location and type of planting, with regard for desert climate conditions.
Preservation of specimen and landmark trees upon a site, with proper
irrigation to insure maintenance of all plant materials;
Landscape plans have not been submitted at this time. Required review
at a later is incorporated into the attached conditions of approval.
8. Signs and graphics, as understood in architectural design Including
materials and colors;
A sign program not been submitted to evaluate against this guideline and
recommendations for further review are incorporated into the attached
conditions of approval.
ENVIRONMENTAL DETERMINATION:
An Addendum to a Final Environmental Impact Report was approved by the City
Council on October 17, 2012. The City Council certified that the certified Specific Plan
EIR and the Addendum together are adequate to support approval of each component
of the proposed project as approved in the Amendment and any future discretionary
approvals needed to implement the project. The entitlements currently under
consideration by the Planning Commission simply implement the project approved in
the Amendment for CEGA purposes on October 17, 2012 No further environmental
review Is required. (Public Resources Code § 21166; California Code of Regulations,
Tltfe 14, § 16162.)
David A. Newell M. MArgo WIT6efer, FAICP
Associate Planner Director of Planning Services
chments:
It Resolution—Block A
2. Dra on—Block B
3. Museum aza Specific Plan— Design Guidelines (excerpt)
4. Table of maximum re footage, building mass and open space provided by
Applicant
5. Proposed Downtown Palm Sp Project Site Plan
6. Block A Elevations and Perspectiv
7. Block B Elevations and Perspectives
8. 12/19/12 City Council Reviewed Elevations rspectives
78
� �pPLA7f p4'a
CITY OF PALM SPRINGS
</FOR
'41FOR'4 " DEPARTMENT OF PLANNING SERVICES
C4 N,p
MEMORANDUM
Date: September 10, 2014
To: Planning Commission
From: Department of Planning Services
Subject: ITEM 2C — PALM SPRINGS PROMENADE, LLC FOR A REVISED
ARCHITECTURAL APPLICATION TO CONSTRUCT A TWO-STORY
COMMERCIAL BUILDING ON BLOCK B OF THE DOWNTOWN
PALM SPRINGS RENOVATION PROJECT LOCATED AT THE
SOUTHWEST CORNER OF ANDREAS ROAD AND PALM CANYON
DRIVE, ZONE CBD (CASE 3.3606 MAJ).
As noted in the staff report for this item, staff prepared the following analysis for the
proposed two-story building on Block B.
BLOCK B
The revised application consists of a two-story building with a complete redesign. Both
floors will be retail and other commercial uses as permitted by the Museum Market
Specific Plan. First floor is proposed at 17,500 square feet and second floor at 14,300
square feet for a total of 31,800 square feet.
BLOCK B — General Plan
CBD (Central Business District) Retail and Yes
The CBD serves as the main activity center and cultural core of the commercial
community and, as such, theatres, museums, retail, and other uses at
entertainment venues are encouraged here. Uses such as grocery stores, 0.77 FAR
hardware stores, and convenience or pharmacy stores that provide
services to the Downtown's residential population are also encouraged.
The Central Business District is subdivided into zones or areas that
provide for diversity in development standards and land use intensities.
The Downtown Central Core (roughly bounded by Amado Road, Tahquitz
Canyon Way, Museum Drive, and Indian Canyon Drive) and the Gateway
areas (at roughly the north and south ends of the CBD) may be
developed with a maximum FAR of 3.5. If projects in these areas provide
substantial public spaces or plazas, an FAR of up to 4.0 may be
developed upon approval of a Planned Development District or Specific
Plan. _
79
Planning Commission Memorandum September 10.2014
Case 3.3606 MAJ—Block B of Downtown Renovation Project Page 2 of 3
BLOCK B — Development Standards
N
Specific Plan 12/19/12 Current €
Requirement Approval Proposal o
U
Minimum Setbacks:
- Front Setback' or Street Side Setback (Feet)
• Palm Canyon Drive, west side 15 18 15
• All Other Streets
o New Main Street 12 14 12
o Andreas Road 12 15 12
- Side Yards Feet 0 0 11
Maximum Building Height (Feet)
- Building 16 38 26'-6" to 36'-6"
- Permitted Projections 15 (and no 7 None
more than (equipment
15% of roof within well
Minimum Building Height Stepbacks (Feet)
- Palm Canyon Drive
- 0-30 Feet in Height 0 Not defined 15
- Over 30 Feet in Height 20 70 20
- Internal and Private Streets
Andreas Road 121
- 0-30 Feet in Height 0 0 12
- Over 30 Feet in Height 10 14 17
New Main
- 0-30 Feet in Height 0 0 12
- Over 30 Feet in Height 10 15 20
Minimum Public / Common Area Open Space 90% 33% (Blocks 42%
B & B-1
Maximum Building Square Footage 3,000 75,562 31,800
(Blocks B &
B-1
Maximum Building Mass Cubic Feet 27,000 301,203 286,200
Projections Into the Right-of-Way (Feet)
- Awnings 10 None None
- Architectural features 10 91
- Arcades, trellis features and similar coverings Face of curb
- Balconies and terraces 6
1 Exceptions to the minimum setback requirements are listed under Section III-E.5 of the Museum Market
Specific Plan.
2 Building height shall be measured from the highest point of the building pad to the top of the roofline.
3 Stepbacks are defined as the horizontal distance a building face must be set back from the property line
at each given height. The area required for a stepback can be used for balconies and terraces. Stepbacks
shall be measured from the face of a structure to the property line at a 90 degree angle from the building 8 O
face.
rParking
ing Commission Memorandum September 10,2014
3.3606 MAJ—Block B of Downtown Renovation Project Page 3 of 3
equirements: 1 space / 42,082 sq. ft. 31,800 sq. ft-
325 sq. ft. requires 129 requires 98
spaces spaces
Loading Facilities Re uired Not Defined On-street
Trash Enclosure Required Not Defined Within Bldg.
Building height, Open Space and Square Footage and Building Mass:: The Specific
Plan envisioned Block B as a green space with few buildings, thus the high open space
requirements and restrictive development standards for buildings. On October 17,
2012, the City Council conducted a conformity review on the Downtown Palm Springs
Project and approved a proposal for the development of Block B, pursuant to Section
V.2 "Conformity Review Procedure" of the Specific Plan. On this basis, the council
approved the architectural application on 12/19/2012 as shown in the table above.
Since the proposal is consistent with these standards, the project is considered
conforming.
Staff has prepared a draft resolution for Planning Commission consideration.
t:
1 Dra n
sl
Architectural Advisory Committee Meeting Agenda
September 8, 2014
7. PALM SPRINGS PROMENADE, LLC FOR A REVISED ARCHITETURAL
APPLICATION TO CONSTRUCT A TWO-STORY COMMERCIAL BUILDING
ON BLOCK B OF THE DOWNTOWN PALM SPRINGS RENOVATION
PROJECT LOCATED AT THE SOUTHWEST CORNER OF ANDREAS ROAD
AND PALM CANYON DRIVE, ZONE CBD. (CASE 3.3606 MAJ)
ASSOCIATE PLANNER NEWELL presented the proposed project (Building B)
as outlined in the staff memorandum.
MEMBER HIRSCHBEIN asked if the green vertical panels come out on an
angle, if they are wedge-shaped, and if they are metal.
CHRIS PARDO replied that they do in fact come out at an angle; they are
wedge-shaped, and metal. The proposed building will have shade provide by
another building as well its own design features.
MEMBER SECOY-JENSEN questioned if the pictured dark material was Rhine
zinc.
THE APPLICANT explained that the lower portions would be a white stucco, that
would be the main element and the black Rhine zinc would use as an accent.
The objective is to further define certain features.
CHAIR FAUBER spoke in favor of the project; it's refreshing and modern.
MEMBER HIRSCHBEIN stated that a linear flat roof does not look cohesive with
the overall design.
THE APPLICANT responded that the Planning Commission and Architectural
Advisory Committee feedback suggested a more linear design; the current
projection is not the ideal. Chris Prado had an idea to have an alternative roof
design that would start high on the left and go low on the right, then start high on
the right and go low on the left.
CHRIS PARDO stated that the original concept consisted only of retail space
and didn't encourage the unique aspect of Palm Springs. The Alley and La
Plaza, although different architecturally, they both convey the spirit of Palm
Springs and were used as inspiration. The swopping roofs and the other
elements that those two buildings have were incorporated into the design.
THE APPLICANT said that the storefronts, the enclosed area the retail specs
have, can be redesign as to the owner's desire, but will be subject go before the
Planning Commission and the Architectural Advisory Committee.
6
82
Architectural Advisory Committee Meeting Agenda
September S, 2014
CHRIS PARDO explained that the current store front design consists of spandrel
glass with a white stucco box that incases the individual store fronts that is
accented with the aforementioned black Rhine zinc. This adds a pop to the
design. The upper level would have a light gray material that has wooden
accents. Spandrel glass will also be used in the above office space; the depicted
screens would provide the space for retail logos.
THE BOARD encouraged that the use of spandrel glass on tenant store front to
remain consistent and allow change of material.
CHRIS PARDO stated that the structure will have adequate shading; by 3:00 pm
there should be complete shading on the front facade. The planting scheme is a
horsetail in the balconies. The mechanical fixtures (AC units) will be covered.
FRANK TYSON, public comment, expressed his concern that the new project will
not be consistent with the classic Palm Springs design. He then read a couple
online comments that spoke against the project. He then suggested that some
Spanish architecture accents be included. He would like the applicant to keep
the Palm Springs charm as much as possible.
THE BOARD asked what would be the result if the back roof design was
swapped and at what point does the back drop roof disappear.
CHRIS PARDO responded that the higher roof is unseen from the other side of
the street.
MEMBER HIRSCHBEIN suggested keeping the spandrel glass above the
overhang. He also asked if the store front frames were based on their lease
plans or would the frames be adjusted in the future.
CHRIS PARDO answered that the spaces have preliminary leases designed for
with the leases in mind.
MEMBER HIRSCHBEIN asked if the spaces already have certain owners why
not built the store front to comply with the preliminary leases.
PLANNING COMISSIONER HUDSON questioned if the spandrel glass is
alumminated.
CHRIS PARDO answered it is not, the renderings did not depicted it correctly.
CHAIR FAUBER spoke in favor of the AC covering [mechanical equipment]. He
suggested that the spandrel glass be expressed differently.
MEMBER SECOY-JENSEN commented that the Bank of America had a similar
7 83
Architectural Advisory Committee Meeting Agenda
September 8,2014
design to cover the mechanical equipment and then their demand for
heating/cooling grew as such the structure had to be replaced. She suggested
when designing the mechanical equipment screen to keep in mind future
development and use. She also spoke in favor of the project, commenting that it
was heading in the appropriate manner.
THE BOARD remarked that the proposed project would be viewed in the future
as the way architecture in Palm Springs looked like in 2014. It provides a step up
for future developments.
MEMBER SONG stated that the choice of materials, horsetail landscape, softens
the overall design.
THE BOARD is pleased to see the landscape integrated into the architecture
and will be submitted at a later date. The only drawback is that horsetail is fast
growing and in the long run may not be the most sustainable option. He
suggested looking into slow-growing desert plants.
M/S/C (Fauber/Fredricks 7-0) Block B approved as submitted.
STAFF MEMBER COMMENTS: No comments.
ADJOURNMENT: The Architectural Advisory Committee of the Ci Palm Springs
adjourned at 6:25 pm to the next regular meeting at 3:00 pm on tember 22, 2014,
Council Chamber, City Hall, 3200 East Tahquitz Canyon Way, m Springs.
ouglas Evans
Interim Director of Planning Services
8 84
Palm Springs Ad Museum / /i '
MA1,11biloul Dr.
4
_. ------------� U
w
EffiTNG CITY OWPED E6TNG OTY OWIED
AND �.
A dE XATEO AW dHtATED
EELOW CPARKING,OE PAN IELOW GRADE PARKING,
EXISTING EXISTING
BELOW GRADE UPPER LEVEL
PARKING GARAGE PARKING GARAGE
i
1 _- tl6TN0 MY O SED1 rye
EMT OPEIWRP
�IDELAND
PA Ow GRADE I M6 -
nn
I
I I
I I
I I ullYllY
BLOCK E
MY OWIFD AND TEO
PEM1IAIENi PL'fLn IC
j d@14ACf _
c
~ BLOCK D I '
FUTURE DEVELOPI.ENT
TnAORARY IESTAUNM/HOTEL r
1
VALET PNgNG
• XI
r BLOCAKPA'lG
OVER EXISTING CITY ON
Low U DE ELDuD OPERATED GRADE rANGNG BLOCK F TEIP CM ESTAANMiA'E NT.-,
TEL
UD FIMOTE VALET PPfSTRO01A8 OYIPESTAML / ETAL ✓ �F /^\�\ 1I
I`\V E=TIVG GTY OwIED Ili \\VV\\ / �DOn11� CWrM
O o I 3 ND dEMTED BELO P W MADE Aeu4 'V/
____. . ._•—.___. _.___.
i• u
_ 0� � � � IETNAN'E1 PAYIYJ 4 d BNaIFL Road
r Vic.---
G T W
-BLOCK C' GnuWSTAun '�� ... .... -
4,169
a
aErne/xEmAwAPr 1 BLOCK B h 2 I BLOCK A(ph 2) Q 'b
WITH L ABOVE
I Hof � � � FUTURE DEVELdAENT I FUTURE DEYELOPLENL Z Snaaen
I I I
.r
m
I I
I I I
I I I
I I
EXISTING
I r.
.. - HVATTHOTEL
< K D
j Market Sheet r d PeP..
IENHANCE D PAVINGI E „� I R
I y 1
it AL REST M RETAL PET
rm do / r LO K B I BLOCK
it IE A ! I
m C Drrvs • -_ - - _ - - - -- _ I
_ anyon o � o
^ a
1 Vy
EXISTING RETAL/RESTAURANT E EIASTING iL XETA /Pf5TA1,PAIn EATNG IETAL STAUMM F,
� E%IbTNG IETA RE6fAUMM .I
® DOWNTOWN PALM SPRINGS 0 ED aD 200
��}})/���T LJE55MAN DEVELLOPI"PENT SCALEr"°' !f
SANBORl\ Prep�w by 4A160EI1 A/EEG-AEOETECTIFE-0UL PGfL£bG SWVE�-7N 420-060D IE�
ARCHITECTURE V
C'VIL ENGINEERING
LAND 9
CRRIS PAROO RESIGN
EtEMEA'4Wx T:_ruuE
i5A itm Are Suite c
$Mlp WAWIf
Deal Mesa
ME.TAWx Cd We
Su.A
PYm STalnps.CA
fmnfxrrya��mn
Y
DOOO
R�bpEnMR
mo
O ( E S z
i
3 . 3606
Downtown
RECEIVED Redevelopment
Renderings
�`lo 10 2014 W.
PLANNING SERVICES
DEPARTMENT R1 .00
8
ti
� � � � _ �
s�� k� i � a
_'`' s , f �
,r �. , .
,,,
'�r;
{
.. �_ � r ,, .r,::
�( „h
1
��'
�_ Yf. '� —
ih w.
� r- � -�
.��, i
� . � �k . �,
?� � '. a P�l� '�d � �. t
M �
� . 1 �
tl � ��r/i j �'•� '.
u � � � _ �.
� .�.
� �
,,¢-�; .;
'�_ % � �•
}I4�R
� I++�L y� �(1 j � r
'♦}K�� i*�� II � ♦ *� � f
'``��$$�
1 : �
i
I
R; �fC!
'.�
I
II
�I
mac
�a
�-FS
CNRIS PARDO DESIGN
ELWN-fl AR:41 .TUFE
�. im I11R Me 5Ule G
•, rLC8�YA1G
ME Te &Cempn W,
$XA
ram sprnw.cA azzez
1R
4/�• � a y1�r�—__ —�_�- _ _ - ___ — —__�_ Ili r - - ,1
aw µ t Downtown
Redevelopment
Renderings
R1 .02
CRRIS PARDO RESIGN
EL:M:VnE AKA r:-1uEE
16N 11N Me Sidle G
S WWAWIM
r"I0 J1
100E Te ft Um WW
SYABA
Palm$pnAp fA&18[
amoy�uc
`va�u m.r.�v.we
d
Downtown
Redevelopment
L
I
;l I
l � _
IW
I w • �,> >A� 1 tiu .,.i 1
iih it } l I I
r11"� ,. l � vv\A• w v 1 ' w. wu Ea.
-
I�
vv
9 JilI I vv �o F •
l i t i v` d v X • .— _. _
T�•� V*_ .� ! Ste. :. - —
- _ Downtown
Redevelopment
Renderings
R1 .03
89
r.A
I CHRIS PAROO RESIGN
EI-M:A 4IPa ii-IUU
F�
I... I� 1521 I1M M95
e....q WR99M R2
I I2O3�59155i
S*A
Ptlm Splrg..GSP26P
r 1
h
i f
x ri
1' yy
' Y,'� 1 OOWMOWn
ReCavalopmeM
G
N
,I
yr
Downtown
Redevelopment
�� — - - - -- Renderings
R1 .04
CNRIS PARRR RESIGN
�cn-n a,x.�l:aaei
isal iim A,e suaec
$eMIb WNBB172
IN9�YJIW
100E Tel UC.ry .,
$ A
Palm 5P�^P.CA&162
F
p
f
a .
y
e
y SPA
AZUL
i
rn.os aew
Downtown
Redevelopment
Renderings
R1 .05
CNPIS PA0.D0 DESIGN
�I�M+1 V ,Ma I .IYY4
_ f
_ ISAtl S
Seedle WA WR�MI'JI
_� —�' R Izx73zalfsa
_ iCV E.Ta1gYWA WaY
5iXe4
.1 ___ Poem Epmw.U maz
------
----------
----------
---
NeMEebpnH4t
+1
i
Downtown
Redevelopment
Renderings
R1 .06
s2
N OI g o
r
f
y'.
Y
Wt
f t
I
t
Z
i
r
I
IL k, _
1
lip
i
4J a.
.F
a } i
u
U�1i -
._ �'
. �
; �
_� ,
i
1
{ ;, .
� :�°
� i
, .
��
:;
_ ,
�,
�u fm.
i � ��
w
I �� __ ,�
���
N
�L R .��'�
� �
I _
I --3.
� L e
F c1 }
�� his i_ I tiW
.., Aiiifff � fi�,
Kt''4!r
�.
.._ _ ... . �.4 � .rs I _ ��
i ' }Y �a _
�. _�..
��.;_.
-..
_ `
i�le -� I
!,,
��
� . ��,
* � �,.,,
.� ' ��,�
�F�f ,iir � � �
■
'1'�t � .
it_. ,
/ � !
� � q� `_�!
f
mse
w
� �:
CHRIS PARDO DESIGN
aitliNrL�A_�1_LUAE
1�2(I 111M1 Mo Suita p
, $eal�le WA 90122
f2C6132&1650
]W F Tal,,,Canym Way
Polm Spinps.G 92262
d YO BIN
LOBBY
3 YD BIN
__ I omvmown
RETAIL RETAILS emeveropme�rt
RETAIL 1 RETAIL 6I,
RETAIL 3 RETAIL 4 RETAIL 5 RETAIL 7
�� uo oam
0 0
Block B Building - first floor plan
SCALE: 1/8"= W' Total Sq Ft 17500
Downtown
Redevelopment
Floor Plan
No.
A2.00 9 6
CHRIS_PARDO DESIGN
III 1y 111M1ACSUIIOG
$rb111C WA� 1612
' 2061 2s-1650
IW E rnnQu,z C,way
8vile P
PoIm SW,nT GU22 2
L---------—
mmp�u
-------------------
Downtown
RWp IoPment
I
OFFICE
II w oae i>�.
I
� I
I
Block B Building - second floor plan
SCALE: 1/8"= 1'-0"Sq Ft 14300
Downtown
Redevelopment
Floor Plan
A2.01 97
s�rr1
ME 11119
�r loss _ 11 11 III Bill
V ' Iu ! III oIII n II 1
on mom
II��I� ®®®®�■�� �liili II' 1
��rnllln ■■■■■■■
ST�1r1CF'C'ED ' I
IIIII111dil 11 I�it ;1111II
■ 11 11111 11 11 ��.. e
T T�, I III li ��Ir � '� I I II, �,I illgn
�� io ■� ■■■6 ■� 1
Fill 1111111111, C�Ioll �l
�. 11 ■11 � 11 ���. ■
gnaw I �� IN 14
_ ! 11 _
mama
all
If' '171
[Ism IBM
Ili■�I�M, I yll�ll '� �IMI, IIIIIL•�i .;l■■Ill��l �i� 1 1
MINE
Rendering
oil
11
Sun Shade
.� _ .. CHRIS PARDO DESIGN
wi
Block B
r-
5
I ill IIII ■ 'T ter. •I I.1111 I � I cif .
I
Sun Shade
Study
y'��'N� �I � — - IIYI �'—u■—RI � I � 1 �■I�n■ �s� � � I� 1 � �
I
11 I� ■ i
���
99
Exterior Color and Materials Wessman Development Company
Downtown Redevelopment- Block B 555 S. Sunrise Way, Suite 200
Palm Springs, CA Palm Springs, CA 92264
September 08, 2014 CHRIS PARDO DESIGN
iL-N-F- L 19-4 7;JUE
Smll4 WAN1V
E1f6I'.1'�1B.A'
]OJE Te ft Cyan Wry
&b A
WLn SpnW,G9?282
Yamwb>+enw li
wmo.mmm
PRODEMA RAINSCREEN SOFFIT
OAF Block B
FIBER CEMENT WALL PANELS
•T
il ij
BLACKED STEEL AWNINGS and
WHITE PLASTERWAIIR
II 11
ZINK CLAD WALL PANELING
w EW Wu
4
�a
W
RETAIL STORE FRONT CONCEPT
HORSETAIL PLANTING CONCEPT
Block B
Material
Samples
1520 11TH AVENUE STE G 700 E.TAHQUITZ CANYON STE A
Seattle WA 98122 CHRIS PARDG DESIGN PALMS SPRINGS,CA 92262
SAM P.
1 .00 100
Low Offices of Babak Noficy
2014 OCT 14 PM 12: OS
October I4, 2014 JA; i f•`vi
CITY CLERK
Via Email and U.S. Mail
Palm Springs City Council
City of Palm Springs, c/o City Clerk
32(H) E.Tahquitz Canyon Way
Palm Springs, California 92202
citecicrk(a pabnspr(ugti-ca.00t_
Stc�c_'ougnctla_taaln_zp�rings-raao�
Qiris.V ills a Ndnnpttnly t- t gov
Ginnv.FoatCrup:dnringti-ctt.gov
R,ick.Fb itcheson('u palmsprings-ca Qm�
�sr;4 Mar.F s; eet Paul.Lcwin(n palnts�xinsc=i.gov
San Lab Otr+�per
c r�rnia Q3401 RE: City Council Oct 15, 2014 Hearing
Appeal of ABCD of the Decision by Planning Commission to approve a
ph 805-'93.0926 Major Architectural Application for Construction of a Two-Story
lax,855,993,3946 Building on Block "B" of the Museum Market Plaza
Dear Councilmembers,
Advocates for Better Community Development, or ABCD, submits this letter in support
of its appeal of the Planning Commission's approval of a Major Architectural
Application ('MAA") for a building on Block "B" of the Museum Market Plaza.
In addition to the appeal grounds raised in our September 9, 2014 letter, ABCD
contends that the approval of the MAA must be set aside also because, as we previously
explained (in a September 16, 2014 letter to the City Council opposing the approval of
the fourth amendment to the Project Financing Agreement or PFA), the City's original
determination that the conversion of Block B from a public plaza to a site for
commercial development is consistent with the Museum Market Plaza Specific Plan is
no longer valid and must be set aside. This is because the City's original consistency
determination was based on a"conformity review" of the applicant's (Wessman)
renovation proposal which preserved the existing structure on Block A. But now that
the structure on Block A has been demolished and there will be no renovation on Block
A, the over-all Museum Market Plaza project can no longer be considered a
"renovation" project: meaning the City can no longer rely on a "conformity
determination" as the basis for approval of the building on Block B. The City must
therefore go back to the drawing board and reconsider whether the conversion of Block
B from public plaza to commercial building is consistent with the Museum Market Plaza
Specific Plan.
aciott'f iD
Palm Springs City Council
October 14, 2014
Page 2of3
In its September 9, 2014 letter to the Planning Commission,ABCD argued that the MAA must be
considered at a public hearing, where the public is afforded an opportunity to specifically
comment on the MAA. The Staff Report's disagreement with ABCD's point is based on an
incorrect reading of the Specific Plan (Section V) according to which a"public hearing" is
required if only if the Commission engages in environmental review of the project consistent with
CEQA. The text of the Specific Plan does not support the Staffs contention.
In relevant part, the Specific Plan provides:
When found complete by the Planning Department, a meeting for the Major Architectural
Application shall be held within 30 days by the Architectural Advisory Committee, aqd a
public meeting shall be scheduled, within 45 days, before the Planning Commission. Such
review shall include any evaluation required under the California Environmental Quality
Act(CEQA). The Commission, upon closing the public hearing, shall:
1. Request changes to the application and continue the matter; or
2.Approve the project, including the addition or modification of project conditions;
Or
3. Deny the project.
Actions of the Commission can be appealed to the City Council. The decision of the City
Council shall be final. Specific Plan, page V-1.
The Specific Plan thus does not support the Staffs contention that a public hearing is required
only if the Planning Commission engages in environmental review of the project pursuant to
CEQA. Moreover, the fact that the Commission allowed public comments is not dispositive as
the public notice indicated that public comments would not be allowed on the subject, thereby
discouraging members of the public from attending the meeting. The MAA must be brought back
before the Planning Commission following a public notice that clearly indicates that the public
would be able to comment on the project.
The other issue raised on appeal is the Planning Department's premature decision to schedule the
MAA for review by both the Architectural Advisory Committee ("AAC")and the Planning
Commission before the MAA application had been completed. The Staff Report grossly
misrepresents the point of ABCD's contention in this regard. In its letter to the Planning
Commission,ABCD argued that the scheduling of both the AAC and Planning Commission
meetings were premature because the Staff Report indicated that as of the date of the Planning
Commission Agenda and Staff Report on this item, the applicant had not submitted a project plan
including exterior renderings. Staff now tries to confuse the issue by pretending that ABCD's
chief complaint is that these plans were not included with the agenda for its own use. This is not
accurate. ABCD's main complaint was that owing to the absence of the plans, the staff report did
not include any meaningful analysis of the project. The absence of plans also precluded members
of the AAC from reviewing the plans prior to the AAC meeting on the project. As ABCD pointed
out in its letter to the Planning Commission, this is not the first time Staff has prematurely
scheduled hearings on MAAs related to the Museum Market Plaza.
Palm Springs City Council
October 14, 2914
Page 3 of 3
Staff contends that the public (and presumably, members of the AAC) could have reviewed the
plans at the AAC and Planning Commission meeting. This contention does not address (and
thereby implicitly concedes)ABCD's point that prior to scheduling AAC and Planning
Commission meetings for this project, the Planning Department was required to ensure the project
application was complete. According to the Palm Springs Municipal Code. "An application fir
new construction and additions shall include a preliminary landscape plan and drawings showing
the exterior elevation of sides of a proposed building or structure, the types of materials and
colors to be used, and the signs to be displayed." 94.0400(E)(2). The Planning Commission Staff
Report admitted that "Plans are being prepared and will be presented at next week's Architectural
Advisory Committee and Planning Commission meetings." Accordingly, it is very clear that the
drawings showing the building's exterior and landscape plans had not been submitted to the Citv
as of September 5, 2014, merely three (3) days before the AAC meeting to discuss the project.
By not responding to this argument, Staff essentially concedes that the applicant's MAA was
incomplete at the time the Planning staff scheduled the AAC and Planning Commission meetings
to consider the project.
For all of the aforementioned reasons, the City Council should grant this appeal and set aside the
Planning Commission's approval of the MAA for Block B.
Sine el ,
Y.
8aabak Naficy
Counsel for ABCD
VD A ) �� I�e►� ��
Kathie Hart
From: Kathie Hart
Sent: Wednesday,September 24, 2014 4:27 PM
To: 'frankjtysen@gmail.com'
Subject: Appeal of Planning Commission 9-10-2014 Action(s)
Mr. Tysen:
For the record I would like to summarize what had transpired this week.
• ABCD submitted a letter dated September 22, 2014, appealing the decision of the Planning
Commission action taken on September 10, 2014,to the Office of the City Clerk, on the following
items:
1. Revised Architectural Application for a two-story commercial building on Block B of the
Downtown Palm Springs Renovation Project.
2. Palm Springs Promenade, LLC, Revised Architectural application for Block A.
• The Office of the City Clerk accepted the letter and a check in the amount of$546.00, appealing the
Revised Architectural Application for a two-story commercial building on Block B of the Downtown
Palm Springs Renovation Project. (action taken by the Planning Commission on 09-10-2014)
• In a subsequent telephone conversation staff advised you that the Planning Department did not feel
that the action taken by the Planning Commission regarding Block A was appealable. In consultation
with the City Attorney, it was determined to be appealable.
• Staff on September 23, 2014, contacted you relaying this information and a fee of$546.00 would need
to be paid to appeal the Planning Commission's 09-10-2014 decision as it relates to Block A.
• Staff made a courtesy call to you on September 24, 2014, to reiterate the last day to file an appeal to
the 09-10-2014 Planning Commission action is Thursday, 09-25-2014. We spoke of the City Attorney's
determination that the action taken by the Planning Commission regarding Block A may be appealed.
• You told me that ABCD will not be appealing the 09-10-2014, Planning Commission action as it relates
to Block A.
Mr. Tysen, please feel free to contact our office if there are any questions.
Kathie Hart, MMC
Chief Deputy City Clerk
City of Palm Springs T(760)323-8206
3200 E. Tohqui tz Canyon Way 8 (760)322-8332
Palm Springs, CA 92262 L�Kathie.14art@PalmSorinosCA.00v
Please note that City Nall is open 8 a.m. to 6 pm,. Monday through Thursday,and closed on Fridays at this time.
1