Loading...
HomeMy WebLinkAbout2020-1190i y. I i A Msp City of Palm Springsoy u Department of Building and Safety Taja Sims .Plans Examiner Supervisor yC0* ORATFO•`,', ` 3200 East Tahquitz Canyon Way .Palm Springs,CA 92262 cg4IFORN%P Tel: 760.323.8242 x 8713 .Fax: 760.322.8349 Email:taja.sims@palmspringsca.gov LETTER OF EXPIRATION Date: 2 November 2022 To: Miralon Amenity Center 4097 Miralo Way Palm Springs,Ca 92262 Regarding:Plan Check Number: 2020-1190 Project Address: 4097 Miralon Way, Palm Springs,Ca Project Description:PV System The above referenced plan check was submitted 4/30/2020. The Uniform Administrative Code allows for a plan check to remain active for 180 days.As this plan check has been active in excess of 180 days,it is expired by limitations. The plans and documents must be picked up within 15 calendar days of this notice or the plans will be discarded.E Additionally,an outstanding plan check fee of$135 is due and payable to the City of Palm Springs,(see the calculation below). Respectfully,_ - T`' I Plans Examiner Supervisor ICC Certified Cc: Plan Check File Fee Calculation: Total plan check fee(UBC) minus Deposit paid at time of submittal equals fees due the City 135 0 135 e' z EsGil A SAFEbuilV Company I DATE: 5-14-'20 APPLICANT JURIS. JURISDICTION: Palm Springs F PLAN CHECK#.: 2020-1190.e SET: I k PROJECT ADDRESS: North Indian Canyon Drive PROJECT NAME: Miralon Amenity Center Commercial PV System, 78kW The plans transmitted herewith have been corrected where necessary and 'substantially comply with the jurisdiction's codes. e El The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. a The check list transmitted herewith is for your information. The plans are,being held at.EsGil until corrected plans are submitted for recheck. The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. The applicant's copy of the check list has been sent to: EsGil staff did not advise the applicant that the plan check has been completed. EsGil staff did advise-the applicant that the plan check has been completed. Person contacted: Jarrod Fisk. Telephone#: 619 363 3890 Date contacted: by: ) Email: Iarrod(a-),rooftechenergy.com Mail Telephone Fax In Person REMARKS: Note to design engineer/contractor/installer, be sure to indicate compliance with the new Rapid Shutdown (RSD) requirements in the California Electrical Code 690.56(C)(1) through C)(3). Note the following, font type, size, color, title wording, location. By: Scott Humphrey Enclosures: EsGil 5-5-20 9320 Chesapeake Drive,Suite 208 San Diego,'California 92123 (858)560-1468 Fax(858)560-1576 Palm Springs 2020-1190.e 5-14-20 PLANS 1. Please make all corrections and submit two new complete sets of prints, to the Palm Springs building department. Please note: Before correcting the plans, you should wait until you've received comments from other city departments (Fire, Planning, etc.). 2. The City of Palm Springs requires the following identified on the plans: a) Wind design using 123 m.p.h. b) Wind exposure C must be used. c) California Structural Engineer (PE) stamp on all structural attachment details. k MISCELLANEOUS 3. To speed up the review process, note on this list (or a copy) where each correction item has been addressed, i.e., plan sheet, note or detail number, calculation page, etc. 4. Please indicate here if any changes have been made to the plans that are not a result of corrections from this list' If there are other changes, please briefly describe them and where they are located in the plans. Have changes been made to the plans not resulting from this correction list? Please indicate: Yes 0 No O 5. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact Scott Humphrey at EsGil. Thank you. a Palm Springs 2020-1190.e 5-14-20 4 ADO NOT PAY— THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: Palm Springs PLAN CHECK#.: 2020-1190.e PREPARED BY: Scott Humphrey DATE: 5-14-20 P BUILDING ADDRESS: North Indian Canyon Drive BUILDING OCCUPANCY: BUILDING AREA Valuation Reg. VALUE ($) PORTION Sq. FL) Multiplier Mod. E. Y f I + 4 Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code N/A 1997 UBC Building l g Permit Fee n T_ 1997 UBC Plan Check Fee 4 Type of Review: Complete Review Structural Only Repetitive Fee Other Repeats Hou 1.5 Hrs. @ EsGil Fee 90.00 135.00 Based on hourly rate Comments: In addition to the above fee, an addltlonal fee of$ _,,. u__.Is due4(°m._hour.`@ hr.) for the CalGreen review. Sheet of i